Carrier 50PSW036-360 Field Selectable Inputs, Complete C Control Jumper Settings See Fig

Page 13

FIELD SELECTABLE INPUTS

Jumpers and DIP (dual in-line package) switches on the control board are used to customize unit operation and can be configured in the field.

IMPORTANT: Jumpers and DIP switches should only be clipped when power to control board has been turned off.

Complete C Control Jumper Settings (See Fig. 4-6)

WATER COIL FREEZE PROTECTION (FP1) LIMIT SETTING — Select jumper 3, (JW3-FP1 Low Temp) to choose FP1 limit of –12.2 C or –1.1 C. To select –1.1 C as the limit, DO NOT clip the jumper. To select –12.2 C as the limit, clip the jumper.

ALARM RELAY SETTING — Select jumper 1 (JW1-AL2 Dry) for connecting alarm relay terminal (AL2) to 24 vac (R) or to remain as a dry contact (no connection). To connect AL2 to R, do not clip the jumper. To set as dry contact, clip the jumper.

Complete C Control DIP Switches — The Complete C control has one DIP switch block with five switches. See Fig. 4-6.

PERFORMANCE MONITOR (PM) — DIP switch 1 will enable or disable this feature. To enable the PM, set the switch to ON. To disable the PM, set the switch to OFF.

STAGE 2 — DIP switch 2 will enable or disable compressor delay. Set DIP switch to OFF for Stage 2 in which the compres- sor will have a 3-second delay before energizing. DIP switch 3 is not used. DIP switch 4 is not used. DIP switch 5 is used to initiate one or 3 tries for the FP1 fault. If water freeze protec- tion for the water coil is needed, then DIP switch 5 can be set to lock out on the FP1 fault after one try.

Deluxe D Control Jumper Settings (See Fig. 7)

WATER COIL FREEZE PROTECTION (FP1) LIMIT SETTING — Select jumper 3, (JW3-FP1 Low Temp) to choose FP1 limit of –12.2 C or –1.1 C. To select –1.1 C as the limit, DO NOT clip the jumper. To select –12.2 C as the limit, clip the jumper.

ALARM RELAY SETTING — Select jumper 4 (JW4-AL2 Dry) for connecting alarm relay terminal (AL2) to 24 vac (R) or to remain as a dry contact (no connection). To connect AL2 to R, do not clip the jumper. To set as dry contact, clip the jumper.

LOW PRESSURE SETTING — The Deluxe D control can be configured for Low Pressure Setting (LP). Select jumper 1 (JW1-LP Norm Open) for choosing between low pressure in- put normally opened or closed. To configure for normally closed operation, do not clip the jumper. To configure for nor- mally open operation, clip the jumper.

Deluxe D Control DIP Switches — The Deluxe D control has 2 DIP switch blocks. Each DIP switch block has 8 switches and is labeled either S1 or S2 on the circuit board. See Fig. 7.

DIP SWITCH BLOCK 1 (S1) — This set of switches offers the following options for Deluxe D control configuration: Performance Monitor (PM) — Set switch 1 to enable or dis- able performance monitor. To enable the PM, set the switch to ON. To disable the PM, set the switch to OFF.

Compressor Relay Staging Operation — Switch 2 will en- able or disable compressor relay staging operation. The com- pressor relay can be set to turn on with Stage 1 or Stage 2 call from the thermostat. This setting is used with dual stage units

(units with 2 compressors and 2 Deluxe D controls) or in mas- ter/slave applications. In master/slave applications, each com- pressor and fan will stage according to its switch 2 setting. If switch is set to Stage 2, the compressor will have a 3-second delay before energizing during Stage 2 demand.

NOTE: If DIP switch is set for Stage 2, the alarm relay will not cycle during Test mode.

Heating/Cooling Thermostat Type — Switch 3 provides selec- tion of thermostat type. Heat pump or heat/cool thermostats can be selected. Select OFF for heat/cool thermostats. When in heat/cool mode, Y1 is used for cooling Stage 1, Y2 is used for cooling Stage 2, W1 is used for heating Stage 1 and O/W2 is used for heating Stage 2. Select ON for heat pump applications. In heat pump mode, Y1 used is for compressor Stage 1, Y2 is used for compressor Stage 2, W1 is used for heating Stage 3 or emergency heat, and O/W2 is used for RV (heating or cooling) depending upon switch 4 setting.

O/B Thermostat Type — Switch 4 provides selection for heat pump O/B thermostats. O is cooling output. B is heating out- put. Select ON for heat pumps with O output. Select OFF for heat pumps with B output.

Switches 5, 6, 7, 8 — Not used.

DIP SWITCH BLOCK 2 (S2) — Used for accessory relay configurations.

Deluxe D Control Accessory Relay Configura- tions (See Tables 4 and 5) — The following acces- sory relay settings are applicable for Deluxe D control only:

CYCLE WITH COMPRESSOR — In this configuration, the relay will be ON any time the compressor relay is on.

DIGITAL NIGHT SETBACK (NSB) — In this configura- tion, the relay will be ON if the NSB input is connected to ground C.

NOTE: If there are no relays configured for digital NSB, then the NSB and OVR inputs are automatically configured for mechanical operation.

MECHANICAL NIGHT SETBACK — When NSB input is connected to ground C, all thermostat inputs are ignored. A thermostat setback heating call will then be connected to the OVR input. If OVR input becomes active, then the Deluxe D control will enter night low limit (NLL) staged heating mode. The NLL staged heating mode will then provide heating during the NSB period.

WATER VALVE (SLOW OPENING) — If relay is config- ured for water valve (slow opening), the relay will start 60 sec- onds prior to starting compressor relay.

CAUTION

To avoid equipment damage, DO NOT leave system filled in a building without heat during the winter unless anti- freeze is added to system water. Condenser coils never fully drain by themselves and will freeze unless winterized with antifreeze.

Table 4 — DIP Switch Block S2 —

Accessory 1 Relay Options

ACCESSORY 1

DIP SWITCH POSITION

RELAY OPTIONS

1

2

3

Digital NSB

Off

On

On

Water Valve — Slow Opening

On

Off

On

LEGEND

 

 

 

NSB — Night Setback

NOTE: All other DIP switch combinations are invalid.

13

Image 13
Contents Safety Considerations ContentsGeneral Installation50PSW Unit Physical Data Overall Cabinet Electric Access Plugs50PSW HWG Unit Size50PSW180,360 Unit Teflon* tape thread sealant is recommended to minimize Condition Closed Open Loop and Recirculating Well Water Quality GuidelinesRECIRCULATING† 50PSW Electrical Data Wire Electrical ConnectionsMIN/MAX RLA LRA QTY FLA FP2 FP1JW1 LEDComp AstatDTS HpwsCompressor Field Wiring Terminal Block Compressor Contactor Alarm Relay Contacts Motor SwitchHot Water Generator Field Line Voltage Wiring Jumper Wire for Alarm Field Low Voltage WiringTypical Aquazone 50PSW360 Deluxe D Control Wiring, 3-Phase PRE-START-UP Wire Low Voltage ConnectionsDeluxe D Control Jumper Settings See Fig Complete C Control Jumper Settings See FigDIP Switch Block S2 Accessory 1 Relay Options Accessory DIP Switch Position Relay OptionsSTART-UP DIP Switch Block S2 Accessory 2 Relay OptionsOperating Limits See Table Unit Start-UpUnit Size Heat Exchanger Pressure DropUnits with Aquazone Complete C Control OperationUnits with Aquazone Deluxe D Control System TestLED Status Description Alarm Relay Operation Complete C Control LED Code Fault DescriptionsLED Fault Description Code Aquazone Deluxe D Control LED IndicaDescription Status LED Test LED ServiceESD Refrigerant Charging TroubleshootingFP1 and FP2 Thermistor Location Fault Heating Cooling Possible Cause Solution TroubleshootingCopyright 2010 Carrier Corporation II. START-UP 50PSW START-UP ChecklistDescription Heating Cooling Heating and Cooling Cycle AnalysisCLG HTG

50PSW036-360 specifications

The Carrier 50PSW036-360 is a highly efficient and reliable rooftop unit designed for commercial applications. It combines advanced technologies and innovative features to provide optimal indoor comfort while ensuring energy savings and ease of operation. Its robust construction and numerous functionalities make the 50PSW036-360 an ideal choice for various building types, from retail spaces to office complexes.

One of the main features of the Carrier 50PSW036-360 is its efficient cooling and heating capabilities. It employs state-of-the-art scroll compressors, which deliver consistent performance and lower noise levels while consuming less energy compared to conventional compressors. This translates into significant energy savings, making it a cost-effective solution for businesses aiming to reduce their operational expenses.

The unit is equipped with a range of advanced technologies, including Carrier’s EcoBlue™ technology, which optimizes airflow and enhances energy efficiency. This technology helps achieve higher SEER (Seasonal Energy Efficiency Ratio) ratings, allowing users to benefit from lower utility bills without sacrificing comfort. Additionally, the unit comes with smart control options, enabling users to easily manage and monitor temperature settings, fan speeds, and energy consumption through intuitive interfaces.

The Carrier 50PSW036-360 also emphasizes versatility and adaptability. It has a compact design that makes it easy to install on rooftops, while its extensive selection of options, such as electric heat and economizers, allows it to be configured to meet various application requirements. Its advanced filtration system ensures high indoor air quality by removing dust, allergens, and other pollutants, which is essential for maintaining a healthy indoor environment.

Durability is another characteristic that sets the Carrier 50PSW036-360 apart. The unit is constructed using high-quality materials designed to withstand the rigors of outdoor environments. This ensures longevity and reliability, making it an excellent long-term investment for businesses.

In summary, the Carrier 50PSW036-360 is a top-of-the-line rooftop unit, ideal for commercial applications. Its blend of energy efficiency, advanced technologies, and robust construction makes it a preferred choice for maintaining optimal indoor climate conditions. With its versatility, durability, and ease of use, this system ensures comfort for occupants while helping businesses achieve their sustainability goals.