Carrier 38BYC, 38BYG instruction manual Make Electrical Connections

Page 4

Table 1—Refrigerant Connections And Recommended Liquid- And Vapor-Tube Diameters (In.)

UNIT

LIQUID

 

VAPOR

 

VAPOR (LONG LINE)

SIZE

Connection Diameter

 

Tube Diameter

Connection Diameter

 

Tube Diameter

Connection Diameter

Tube Diameter

 

 

 

 

 

 

 

 

 

018

3/8

 

3/8

5/8

 

5/8

5/8

3/4

024

3/8

 

3/8

3/4

 

3/4

3/4

3/4

030, 036

3/8

 

3/8

3/4

 

3/4

3/4

7/8

042

3/8

 

3/8

7/8

 

7/8

7/8

1-1/8

048, 060

3/8

 

3/8

7/8

 

1-1/8

7/8

1-1/8

 

 

 

 

 

 

 

 

 

NOTES:

1.Tube diameters are for lengths up to 50 ft. For tubing lengths greater than 50 ft horizontal, or greater than 20 ft vertical differential, consult the Application Guideline and Service Manual — Air Conditioners and Heat Pumps.

2.Do not apply capillary tube indoor coils to these units.

OUTDOOR UNIT CONNECTED TO FACTORY APPROVED INDOOR UNIT

Outdoor unit contains correct system refrigerant charge for opera- tion with indoor unit of same size when connected by 15 ft of field-supplied or factory accessory tubing. Check refrigerant charge for maximum efficiency.

REFRIGERANT TUBING

Connect tubing to fittings on outdoor unit vapor- and liquid- service valves. (See Table 1.) Use refrigerant grade tubing.

SWEAT CONNECTION

To avoid valve damage while brazing, service valves must be wrapped in a heat sink material such as a wet cloth.

Remove plastic retainer holding outdoor piston in liquid service valve and connect sweat/flare adapter provided to valve. (See Fig. 7.) Connect refrigerant tubing to fittings on outdoor unit vapor- and liquid-service valves. Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, tubing set can be brazed to service valve using either silver bearing or non-silver bearing brazing material. Consult local code requirements. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.

PISTON BODY

PISTON

PISTON

RETAINER

STRAINER

SWEAT/FLARE ADAPTER

A97512

Fig. 7—Liquid-Service Valve

IMPORTANT: Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close

attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.

Step 10—Make Electrical Connections

To avoid personal injury or death, do not supply power to unit with compressor terminal box cover removed.

Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit- protection device.

NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit rating plate. Do not install unit in system where voltage may fluctuate above or below permissible limits.

NOTE: Use copper wire only between disconnect switch and unit.

NOTE: Install branch circuit disconnect of adequate size per NEC to handle unit starting current. Locate disconnect within sight from and readily accessible from unit, per Section 440-14 of NEC.

ROUTE GROUND AND POWER WIRES

Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box.

The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes. Failure to follow this warning can result in an electric shock, fire, or death.

CONNECT GROUND AND POWER WIRES

Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig. 8.

CONNECT CONTROL WIRING

Route 24v control wires through control wiring grommet and connect leads to control wiring. See Thermostat Installation Instructions for wiring specific unit combinations. (See Fig. 9.)

Use No. 18 AWG color coded, insulated (35°C minimum) wire. If thermostat is located more than 100 ft from unit, as measured along the control voltage wires, use No. 16 AWG color coded wire to avoid excessive voltage drop.

All wiring must be NEC Class 1 and must be separated from incoming power leads.

4

Image 4
Contents Safety Considerations Installation RecommendationsInstallation DimensionsTXV Check Outdoor AccuRater Piston Make Piping ConnectionsCheck Defrost Thermostat Make Electrical Connections Accessory Usage Install Electrical AccessoriesStart-Up Compressor Crankcase HeaterSequence of Operation CoolingDefrost HeatingRequired Liquid-Line Temperature F COOLING-ONLY Procedure ExampleHeating Check Chart Procedure Defrost Control Speedup Timing SequenceCare and Maintenance Final Checks

38BYG, 38BYC specifications

The Carrier 38BYC and 38BYG are part of Carrier's innovative range of commercial HVAC systems, specifically engineered to offer superior cooling and heating solutions. With their modular design, these units cater to a variety of commercial applications, providing energy-efficient climate control that meets the diverse needs of businesses.

One of the standout features of the Carrier 38BYC and 38BYG is the incorporation of advanced inverter technology. This technology allows the system to adjust its compressor speed in real time, optimizing energy consumption while ensuring consistent indoor comfort. This capability significantly reduces operational costs compared to traditional HVAC systems that operate at fixed speeds.

Both models boast enhanced cooling and heating capabilities with high energy efficiency ratings, helping businesses reduce their carbon footprint while enjoying substantial savings on energy bills. The efficiency is further reinforced by the use of environmentally friendly refrigerants, aligning with global efforts to minimize the impact of refrigeration technologies on the environment.

Another key characteristic of the 38BYC and 38BYG is their quiet operation. Engineered with sound-dampening features, these units provide a comfortable indoor experience without the disruptive noise often associated with HVAC systems. This makes them particularly suitable for commercial spaces where a peaceful environment is crucial, such as offices, hotels, and healthcare facilities.

Connectivity is a significant aspect of these models. Equipped with smart technology, the Carrier 38BYC and 38BYG support remote monitoring and control through mobile applications. This allows facility managers to adjust settings, monitor performance, and schedule maintenance tasks from virtually anywhere, enhancing operational efficiency and convenience.

In terms of installation and maintenance, both models are designed with ease of access in mind. The modular design simplifies installation and servicing, ensuring that downtime is minimized, and system longevity is maximized. Their compact footprint makes them versatile enough to fit in various architectural spaces, making them an ideal choice for retrofitting or new constructions.

Overall, the Carrier 38BYC and 38BYG systems encapsulate modern HVAC technology with their emphasis on energy efficiency, quiet operation, smart connectivity, and ease of maintenance. These traits not only serve businesses’ immediate cooling and heating needs but also contribute to a more sustainable and cost-effective future. Whether for a small office or a large commercial establishment, these units deliver a comprehensive climate control solution tailored for today’s ever-evolving business landscape.