INSTALLATION

Condensing Unit Location

The condensing unit should be located outdoors as close as possible to the evaporator. Consider the following factors:

Clearances

The air inlet should be located at least 12" from a wall or other obstruction for unrestricted air flow.

The air outlet should be located so as to direct discharged air away from the building. Three feet of clearance around the unit and a minimum of six feet clearance above the unit is required to avoid recirculation of condenser discharge air on vertical discharge models. Avoid locating unit under low overhanging roofs.

Support

Mount the unit on a sturdy base approximately four to six inches above the ground. In areas known for snow accumulation, the unit should be elevated at least 18" above the ground. A concrete slab is recommended. Concrete slab should not contact the building foundation to prevent possible sound or vibration transmission.

Rooftop installation is acceptable in areas of low snow accumulations, provided the roof will support the unit and provisions are made for water drainage and the noise or vibration through the structure.

Exposure

If practical, unit should be located on the south side of the structure away from northerly winds to minimize the effects of blowing snowdrifts and freezing rain. A wind screen or wind block can also be used.

Placement of the unit should be in a well-drained area, or the unit must be supported high enough so run-off will not enter the unit.

Avoid installations under roof overhangs without guttering. Water draining from the roof onto the unit could produce excessive noise and may cause ice to build up on the coil or fan during cold weather.

Locate unit away from windows, patios, decks, etc. where unit operation sound may disturb customer.

Do not locate where heat, lint or exhaust fumes will be discharged on the unit (as from dryer or furnace vent).

112

 

Rain Gutters

 

 

Six feet

 

clearance

 

above the

 

unit

Three feet

Three feet

clearance

 

clearance

Concrete slab

 

Proximity to Evaporator

Locating the condenser as close as possible to the evaporator will increase the system capacities by reducing the line set refrigerant pressure drop, and will make the system less susceptible to liquid migrations due to less refrigerant charge.

Electrical Connections

WARNING

BEFORE PERFORMING ANY WORK ON THIS EQUIPMENT, POWER SUPPLY MUST BE TURNED OFF AT THE HOUSEHOLD SERVICE BOX TO AVOID THE POSSIBILITY OF SHOCK, INJURY, DEATH OR DAMAGE TO EQUIPMENT.

WARNING

ELECTRICAL EQUIPMENT SHOULD BE INSTALLED BY A QUALIFIED, LICENSED ELECTRICIAN. IMPROPER ELECTRICAL HOOK-UP MAY DAMAGE EQUIPMENT, CAN CREATE A HAZARD, CAUSE PERSONAL INJURY OR DEATH, AND WILL VOID THE WARRANTY.

1.The installer shall check available power to make certain it matches the unit rating plate (located inside control box cover) and that constant voltage can be maintained to the unit. Unsatisfactory performance would otherwise result. The local power company should be contacted regarding any problems or questions concerning power supply.

113Control box cover

Opening for line voltage conduit or cable

Opening for low-voltage wiring

114

Wiring diagram and rating plate are located inside control box cover

2.Install a line service disconnect switch within sight of the condensing unit. The line voltage service wiring for the condensing unit should include a fused disconnect switch.

3.Use correct wire size and fuse size. To ensure that adequate voltage will be available at the condensing unit, the line voltage service wiring must be of adequate size. Minimum recommended wire ampacities and maximum fuse sizes are listed on the unit name plate.

4.Two holes are provided in the control box.

a.One is for the connection of the line voltage conduit or cable. The hole is sized for 3/4" conduit.

b.One is for low-voltage wiring. (Refer to the wiring diagram attached to electrical box cover for connection.)

5.Be sure to ground the condensing unit by securing the ground wire to the grounding lug inside the control box.

6.Be sure to follow National Electrical Code and all local codes.

2

Image 3
Contents Through 5 Ton Heat Pump Table of ContentsCodes Recognize Safety SYMBOLS, Words and LabelsWhat You Need To Know About Safety Instructions Introduction114 InstallationCondensing Unit Location Electrical Connections117 Service Valve ConnectionsLiquid Line Sizes PrecautionsConnect Refrigerant Piping 118Cooling Operation Final Checks for InstallerModel SUB-COOLING ChargingDefrost Operation Maintenance InstructionsModel C10 Limited Warranty

CH18ABD1 specifications

The Fedders CH18ABD1 is a powerful and efficient air conditioning unit that is designed for residential and light commercial applications. This model is particularly popular for its ability to deliver rapid cooling and heating, making it an ideal choice for various climates and seasonal changes.

One of the standout features of the Fedders CH18ABD1 is its robust 18,000 BTU cooling capacity. This allows it to efficiently cool large spaces, making it suitable for medium to large rooms. The unit also offers a heating capacity, which provides flexibility for year-round comfort. The ability to switch between cooling and heating modes allows users to enjoy a comfortable indoor environment no matter the weather outside.

The Fedders CH18ABD1 is designed with advanced technologies that enhance its efficiency and performance. A key technology is its use of a high-efficiency compressor, which significantly reduces energy consumption while maintaining effective temperature control. Additionally, this model includes a programmable thermostat that allows users to set precise temperatures and schedules, promoting energy savings and convenience.

In terms of noise levels, the Fedders CH18ABD1 operates quietly, making it suitable for settings where noise is a concern, such as bedrooms or offices. The unit’s design incorporates sound-dampening features that minimize operational sound, ensuring an unobtrusive climate control experience.

Installation and maintenance of the Fedders CH18ABD1 is relatively straightforward. The unit is designed for easy mounting in windows or through walls, providing flexibility in placement. Regular maintenance is facilitated by accessible filters that can be easily cleaned or replaced, helping sustain optimal performance over time.

Furthermore, the unit is equipped with various modes, such as fan-only and auto-restart functions. The fan mode allows for air circulation without cooling, while the auto-restart function ensures the unit resumes its previous settings after a power outage.

In summary, the Fedders CH18ABD1 stands out for its powerful cooling and heating capabilities, advanced efficiency technologies, and user-friendly features. Its flexible operation, quiet performance, and ease of maintenance make it a reliable choice for anyone seeking an effective and efficient air conditioning solution. This unit is an excellent investment for those aiming to maintain a comfortable living environment throughout the year.