Bryant 661G, 661S, 661C VII. Check Defrost Thermostat, VIII. Make Piping Connections

Page 3

TABLE 1—REFRIGERANT CONNECTIONS AND RECOMMENDED LIQUID AND VAPOR TUBE DIAMETERS (IN.)

UNIT

LIQUID

 

VAPOR

 

VAPOR (LONG LINE)

SIZE

Connection Diameter

 

Tube Diameter

Connection Diameter

 

Tube Diameter

Connection Diameter

Tube Diameter

018, 024

3/8

 

3/8

5/8

 

5/8

5/8

3/4

060, 036

3/8

 

3/8

3/4

 

3/4

3/4

7/8

042, 048

3/8

 

3/8

7/8

 

7/8

7/8

1-1/8

060

3/8

 

3/8

7/8

 

1-1/8

7/8

1-1/8

 

 

 

 

 

 

 

 

 

NOTES:

1.Tube Diameters are for lengths up to 50 ft or 20 ft vertical differential. For tubing lengths greater than 50 ft, consult the Application Guideline and Service Manual for Air Conditioners and Heat Pumps Using R-22 Refrigerant.

CAUTION: Remove indoor coil piston if unit is to be installed on system with a TXV metering device.

Check outdoor unit piston. Remove retainer on liquid service valve and check piston size with matching number listed on outdoor unit rating plate.

VII. CHECK DEFROST THERMOSTAT

Check defrost thermostat to ensure it is properly located and securely attached. There is a liquid header with a brass distributor and feeder tube going into outdoor coil. At the end of 1 of the feeder tubes, there is a 3/8-in. O.D. stub tube approximately 2 in. long. (See Fig. 5.) The defrost thermostat should be located on stub tube. Note that there is only 1 stub tube used with liquid header, and on most units it is the bottom circuit.

FEEDER TUBE

STUB TUBE

DEFROST

THERMOSTAT

A97517

Fig. 5—Defrost Thermostat Location

VIII. MAKE PIPING CONNECTIONS

WARNING: Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death. Use all service ports and open all flow-control devices, including solenoid valves.

CAUTION: If ANY refrigerant tubing is buried, provide a 6 in. vertical rise at service valve. Refrigerant tubing lengths up to 36 in. may be buried without further special consideration. For lengths above 36 in., consult your local distributor.

—3—

CAUTION: To prevent damage to unit or service valves observe the following:

•Use a brazing shield.

•Wrap service valves with wet cloth or use a heat-sink material.

Outdoor units may be connected to indoor section using accessory tubing package or field-supplied refrigerant grade tubing of correct size and condition. For tubing requirements beyond 50 ft in length or 20 ft vertical differential, substantial capacity and performance losses can occur. Following the recommendations in the Residen- tial Split System Long-Line Application Guideline will reduce these losses. Refer to Table 1 for field tubing equivalent line length.

If refrigerant tubes or indoor coil are exposed to atmosphere, they must be evacuated to 500 microns to eliminate contamination and moisture in the system.

A.Outdoor Unit Connected to Factory-Approved In- door Unit

Outdoor unit contains correct system refrigerant charge for opera- tion with indoor unit of same size when connected by 15 ft of field-supplied or factory-accessory tubing. Check refrigerant charge for maximum efficiency.

B. Refrigerant Tubing

Connect tubing to fittings on outdoor unit vapor and liquid service valves. (See Table 1.) Use refrigerant grade tubing. Refer to appropriate section below for type of service valves installed on unit.

C. Sweat Connection

CAUTION: To avoid valve damage while brazing, ser- vice valves must be wrapped in a heat-sinking material such as a wet cloth.

Remove plastic retainer holding outdoor piston in liquid service valve and connect sweat/flare adapter provided to valve. (See Fig. 6.) Connect refrigerant tubing to fittings on outdoor unit vapor and liquid service valves. Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, tubing set can be brazed to service valve using either silver bearing or non-silver bearing brazing material. Consult local code require- ments. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.

D. Final Tubing Check

IMPORTANT: Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.

Image 3
Contents Installation Recommendations Safety ConsiderationsIII. Clearance Requirements Installation Check Equipment and JOB SiteII. Install on a SOLID, Level Mounting PAD DimensionsVIII. Make Piping Connections VII. Check Defrost ThermostatXI. Compressor Crankcase Heater XII. Install Electrical AccessoriesIX. Make Electrical Connections Compressor Crankcase HeaterBryant ONE Programmable Thermostat Other HP Thermostat Sequence of Operation l Phase Monitor ControlDefrost Control SPEED-UP Timing Sequence Heating Check Chart ProcedureCare and Maintenance XIV. Check Charge

661S, 661C, 661G specifications

The Bryant 661 series, comprising the models 661G, 661C, and 661S, represents a significant advance in heating and cooling technology, offering efficiency, reliability, and smart capabilities for modern homes. These models are designed to cater to various climate conditions while ensuring optimal comfort and energy savings.

The Bryant 661G model is primarily a gas furnace that boasts impressive AFUE (Annual Fuel Utilization Efficiency) ratings, which can exceed 96%. This efficiency translates into substantial savings on energy bills, making it an environmentally friendly choice. The 661G features a variable-speed blower motor, which adjusts airflow to meet specific heating needs. Additionally, its dual-stage gas valve allows for enhanced comfort and efficiency, providing a quiet operation and steady temperature control throughout the home.

The Bryant 661C model stands out with its focus on air conditioning capabilities. It utilizes advanced inverter technology that allows for precise temperature control and enhanced energy efficiency. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 661C significantly reduces energy consumption during hot months. Furthermore, the model is equipped with advanced filtration systems that ensure high indoor air quality by capturing allergens and pollutants, making it an excellent choice for allergy sufferers.

Lastly, the Bryant 661S is a comprehensive solution combining both heating and cooling in a single unit. This model is designed for versatility and efficiency, making it suitable for various residential applications. It offers smart technology integration, allowing homeowners to control their HVAC systems remotely via smartphone apps. The 661S's high-efficiency heat pump technology provides substantial savings in energy costs while maintaining optimal comfort year-round.

All three models feature durable construction with corrosion-resistant materials, ensuring longevity and minimal maintenance. The Bryant Comfort Shield technology enhances operational reliability by providing protection against environmental stressors. Moreover, the ease of installation and compatibility with existing Bryant systems adds to their appeal.

In conclusion, the Bryant 661G, 661C, and 661S models combine modern technology with energy-efficient performance, making them ideal choices for those looking to improve their home comfort while reducing energy costs. With their advanced features, homeowners can enjoy a cozy living environment while contributing to a more sustainable future.