Bryant 664B Install Electrical Connections, Minimum Airflow for Safe Electric Heater Operation

Page 6

664B

Table 2 – Minimum Airflow for Safe Electric Heater Operation

Unit Size

 

Minimum Airflow (CFM)

 

5kW

7.5kW

10kW

15kW

20kW

 

024

500

650

750

--

--

030

600

800

1050

--

--

 

 

 

 

 

 

036

600

800

1050

1150

1200

042

600

800

1050

1150

1200

 

 

 

 

 

 

048

600

800

1050

1150

1200

060

600

800

1050

1150

1200

Step 7 — Install Electrical Connections

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

The unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground screw in the control compartment, or conduit approved for electrical ground when installed in accordance with NEC, ANSI/NFPA 70 American National Standards Institute/ National Fire Protection Association (latest edition) (in Canada, Canadian Electrical Code CSA C22.1) and local electrical codes.

!CAUTION

UNIT COMPONENT DAMAGE HAZARD

Failure to follow this caution may result in damage to the unit being installed.

1.Make all electrical connections in accordance with NEC ANSI/NFPA 70 (latest edition) and local electrical codes governing such wiring. In Canada, all electrical connections must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.

2.Use only copper conductor for connections between field-supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE.

3.Be sure that high-voltage power to unit is within operating voltage range indicated on unit rating plate. On 3-phase units, ensure phases are balanced within 2 percent. Consult local power company for correction of improper voltage and/or phase imbalance.

4.Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc.

HIGH-VOLTAGE CONNECTIONS

The unit must have a separate electrical service with a field-supplied, waterproof disconnect switch mounted at, or within sight from the unit. Refer to the unit rating plate, NEC and local codes for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing.

The field-supplied disconnect may be mounted on the unit over the high-voltage inlet hole when the standard power and low-voltage entry points are used. See Fig. 6 and 7 for acceptable location.

Operation of unit on improper line voltage constitutes abuse and may cause unit damage that could affect warranty.

ROUTING POWER LEADS INTO UNIT

Use only copper wire between disconnect and unit. The high-voltage leads should be in a conduit until they enter the unit; conduit termination at the unit must be watertight. Run the high-voltage leads through the hole on the control box side of the unit (See Fig. 7). When the leads are inside the unit, run leads to the control box (See Fig. 8). For single-phase units, connect leads to the black and yellow wires (See Fig. 9).

CONNECTING GROUND LEAD TO UNIT GROUND

Connect the ground lead to the chassis using the unit ground in the control box (See Fig. 8 and 9).

ROUTING CONTROL POWER WIRES (24-V)

Form a drip-loop with the thermostat leads before routing them into the unit. Route the thermostat leads through grommeted hole provided in unit into unit control box (See Fig. 7). Connect thermostat leads and unit power leads as shown in Fig. 9, 10 and 11.

Route thermostat wires through grommet providing a drip-loop at the panel. Connect low-voltage leads to the thermostat as shown in Fig. 10 & 11.

The unit transformer supplies 24-v power for complete system including accessory electrical heater. Transformer is factory wired for 230-v operation.

ACCESSORY ELECTRIC HEAT WIRING

Refer to accessory electric heat installation instructions for information on installing accessory electric heat. Accessory electric heat wiring is shown in Fig. 17 and 18.

HIGH-VOLTAGE POWER

LOW-VOLTAGE WIRING

WIRING ENTRY HOLE

 

ENTRY HOLE

 

 

 

 

 

(grommet hole)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A08407

Fig. 7 - Unit Electrical Connection

6

Image 6
Contents Installation Instructions Table of ContentsSafety Considerations Receiving and InstallationIntroduction Configuring Units for Downflow Vertical Discharge Connect Condensate DrainUnit Damage Hazard Unit Base Dimensions, 664B024-060 Typical Installation Install Electrical Connections Minimum Airflow for Safe Electric Heater OperationUnit Component Damage Hazard PRE-START-UP FIRE, EXPLOSION, Electrical Shock HazardCheck for Refrigerant Leaks Start-Up Cooling and Make Adjust- mentsSTART-UP Refrigerant ChargeIndoor Airflow and Airflow Adjust- ments Required SubcoolingFor 208/230V Blower Motors Unit Controls Compressor RotationSequence of Operation Typical Single-Phase Unit Electrical Diagram Sizes A06405 Typical Three-Phase Unit Electrical Diagram Sizes A06326 Single-Phase Accessory Electric Heater Wiring Volt Horizontal Discharge Unit Air Filter MaintenanceCooling Charging Chart Unit Top RemovalWet Coil Pressure Drop Accessory Electric Heat Pressure Drop in. wcIndoor Blower and Motor Filter Pressure Drop in. wcTroubleshooting START-UP ChecklistTypical Heat Pump Operation, Heating Mode Troubleshooting Chart Symptom Cause RemedyII. PRE-START-UP START-UP Checklist Remove and Store in JOB FilePreliminary Information III. START-UP

664B specifications

The Bryant 664B is a notable addition to the furnace market, recognized for its reliable performance and energy efficiency. Designed for residential applications, this model is particularly well-suited for homeowners looking to improve their heating systems without sacrificing comfort or efficiency.

One of the standout features of the Bryant 664B is its variable-speed blower motor. This technology allows the furnace to adjust its airflow based on the heating demands of the home, resulting in more consistent temperatures and reduced energy usage. By operating at different speeds, the furnace can provide quieter operation, ensuring that homeowners can enjoy a peaceful environment while the system works effectively.

Energy efficiency is a key characteristic of the Bryant 664B, boasting an Annual Fuel Utilization Efficiency (AFUE) rating of up to 80%. This rating indicates that the furnace converts 80% of the fuel it consumes into usable heat, making it a cost-effective choice for homeowners looking to lower their utility bills. The unit's efficient performance not only benefits the household budget but also contributes to a reduced carbon footprint, aligning with modern environmental expectations.

In terms of construction, the Bryant 664B features a robust cabinet that ensures durability and helps to minimize operational noise. Its compact design allows for easy installation in various home configurations, making it a versatile option for many homeowners. The furnace is equipped with advanced diagnostic capabilities, enabling easier troubleshooting and maintenance, thus reducing the potential for costly repairs.

Another noteworthy aspect of the Bryant 664B is its compatibility with smart home technology. Homeowners can integrate the furnace with their existing smart systems, providing enhanced control over their home’s heating environment. This integration allows for remote monitoring and adjustments, ensuring optimal comfort tailored to individual needs.

The Bryant 664B also includes a dependable warranty, providing added peace of mind for homeowners. This warranty underscores the manufacturer’s commitment to quality and customer satisfaction.

Overall, the Bryant 664B is an efficient, reliable, and technologically advanced heating solution. Its combination of variable-speed technology, energy efficiency, solid construction, and integration with smart home systems makes it a compelling option for anyone in need of a modern furnace. Its focus on comfort and performance solidifies its place in the competitive HVAC market.