Bryant 664B installation instructions Troubleshooting, START-UP Checklist

Page 19

Step 4 — Outdoor Coil, Indoor Coil, and Condensate Drain Pan

Inspect the condenser coil, evaporator coil, and condensate drain pan at least once each year.

The coils are easily cleaned when dry; therefore, inspect and clean the coils either before or after each cooling season. Remove all obstructions, including weeds and shrubs, that interfere with the airflow through the condenser coil.

Straighten bent fins with a fin comb. If coated with dirt or lint, clean the coils with a vacuum cleaner, using the soft brush attachment. Be careful not to bend the fins. If coated with oil or grease, clean the coils with a mild detergent and water solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, wiring, or air filter(s). For best results, spray condenser coil fins from inside to outside the unit. On units with an outer and inner condenser coil, be sure to clean between the coils. Be sure to flush all dirt and debris from the unit base.

Inspect the drain pan and condensate drain line when inspecting the coils. Clean the drain pan and condensate drain by removing all foreign matter from the pan. Flush the pan and drain trough with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s). If the drain trough is restricted, clear it with a “plumbers snake” or similar probe device.

Step 5 — Outdoor Fan

!CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution may result in damage to unit components.

Keep the condenser fan free from all obstructions to ensure proper cooling operation. Never place articles on top of unit.

1.Shut off unit power supply and install lockout tag.

2.Remove outdoor-fan assembly (grille, motor, motor cover, and fan) by removing screws and flipping assembly onto unit top cover.

3.Loosen fan hub setscrews.

4.Adjust fan height as shown in Fig. 19.

5.Tighten setscrews.

6.Replace outdoor-fan assembly.

15/32-in. (12 mm)

A08004

Fig. 19 - Outdoor Fan Adjustment

Step 6 — Electrical Controls and Wiring

Inspect and check the electrical controls and wiring annually. Be sure to turn off the electrical power to the unit.

Remove access panel to locate all the electrical controls and wiring. Check all electrical connections for tightness. Tighten all screw connections. If any smoky or burned connections are noticed, disassemble the connection, clean all the parts, re-strip the wire end and reassemble the connection properly and securely.

Check to ensure no wires are touching refrigerant tubing or sharp sheet metal edges. Move and secure wires to isolate from tubing and sheet metal edges.

After inspecting the electrical controls and wiring, replace all the panels. Start the unit, and observe at least one complete cooling cycle to ensure proper operation. If discrepancies are observed in operating cycle, or if a suspected malfunction has occurred, check each electrical component with the proper electrical instrumentation. Refer to the unit wiring label when making these checks.

Step 7 — Refrigerant Circuit

Inspect all refrigerant tubing connections and the unit base for oil accumulation annually. Detecting oil generally indicates a refrigerant leak.

If oil is detected or if low performance is suspected, leak test all refrigerant tubing using an electronic leak detector, or liquid-soap solution. If a refrigerant leak is detected, refer to Check for Refrigerant Leaks section.

If no refrigerant leaks are found and low performance is suspected, refer to Checking and Adjusting Refrigerant Charge section.

Step 8 — Indoor Airflow

The heating and/or cooling airflow does not require checking unless improper performance is suspected. If a problem exists, be sure that all supply- and return-air grilles are open and free from obstructions, and that the air filter is clean.

Step 9 — Metering Devices

Refrigerant cooling metering device is an AccuRater (024-042) or TXV (048 and 060) located upstream of the indoor coil distributor assembly. Refrigerant heating mode metering device is an AccuRater located upstrem of the outdoor coil distributor assembly.

Step 10 — Liquid Line Strainers

The liquid line strainers (to protect metering devices) are made of wire mesh and are located in the liquid lines on the inlet side of the metering devices.

Step 11 — High Flow Valves

High flow valves are located on the compressor hot gas and suction tubes. Large black plastic caps distinguish these valves with O-rings located inside the caps. These valves can not be accessed for service in the field. Ensure the plastic caps are in place and tight or the possibility of refrigerant leakage could occur.

TROUBLESHOOTING

Refer to the Troubleshooting Chart (Table 9) for troubleshooting information.

START-UP CHECKLIST

Use the Start-Up Checklist at the back of this manual.

664B

19

Image 19
Contents Table of Contents Installation InstructionsReceiving and Installation Safety ConsiderationsIntroduction Connect Condensate Drain Configuring Units for Downflow Vertical DischargeUnit Damage Hazard Unit Base Dimensions, 664B024-060 Typical Installation Minimum Airflow for Safe Electric Heater Operation Install Electrical ConnectionsUnit Component Damage Hazard FIRE, EXPLOSION, Electrical Shock Hazard PRE-START-UPRefrigerant Charge Start-Up Cooling and Make Adjust- mentsSTART-UP Check for Refrigerant LeaksRequired Subcooling Indoor Airflow and Airflow Adjust- mentsFor 208/230V Blower Motors Compressor Rotation Unit ControlsSequence of Operation Typical Single-Phase Unit Electrical Diagram Sizes A06405 Typical Three-Phase Unit Electrical Diagram Sizes A06326 Single-Phase Accessory Electric Heater Wiring Volt Horizontal Discharge Unit Unit Top Removal MaintenanceCooling Charging Chart Air FilterFilter Pressure Drop in. wc Accessory Electric Heat Pressure Drop in. wcIndoor Blower and Motor Wet Coil Pressure DropSTART-UP Checklist TroubleshootingTypical Heat Pump Operation, Heating Mode Symptom Cause Remedy Troubleshooting ChartIII. START-UP START-UP Checklist Remove and Store in JOB FilePreliminary Information II. PRE-START-UP

664B specifications

The Bryant 664B is a notable addition to the furnace market, recognized for its reliable performance and energy efficiency. Designed for residential applications, this model is particularly well-suited for homeowners looking to improve their heating systems without sacrificing comfort or efficiency.

One of the standout features of the Bryant 664B is its variable-speed blower motor. This technology allows the furnace to adjust its airflow based on the heating demands of the home, resulting in more consistent temperatures and reduced energy usage. By operating at different speeds, the furnace can provide quieter operation, ensuring that homeowners can enjoy a peaceful environment while the system works effectively.

Energy efficiency is a key characteristic of the Bryant 664B, boasting an Annual Fuel Utilization Efficiency (AFUE) rating of up to 80%. This rating indicates that the furnace converts 80% of the fuel it consumes into usable heat, making it a cost-effective choice for homeowners looking to lower their utility bills. The unit's efficient performance not only benefits the household budget but also contributes to a reduced carbon footprint, aligning with modern environmental expectations.

In terms of construction, the Bryant 664B features a robust cabinet that ensures durability and helps to minimize operational noise. Its compact design allows for easy installation in various home configurations, making it a versatile option for many homeowners. The furnace is equipped with advanced diagnostic capabilities, enabling easier troubleshooting and maintenance, thus reducing the potential for costly repairs.

Another noteworthy aspect of the Bryant 664B is its compatibility with smart home technology. Homeowners can integrate the furnace with their existing smart systems, providing enhanced control over their home’s heating environment. This integration allows for remote monitoring and adjustments, ensuring optimal comfort tailored to individual needs.

The Bryant 664B also includes a dependable warranty, providing added peace of mind for homeowners. This warranty underscores the manufacturer’s commitment to quality and customer satisfaction.

Overall, the Bryant 664B is an efficient, reliable, and technologically advanced heating solution. Its combination of variable-speed technology, energy efficiency, solid construction, and integration with smart home systems makes it a compelling option for anyone in need of a modern furnace. Its focus on comfort and performance solidifies its place in the competitive HVAC market.