DETAILED COOLING CAPACITIES#
EVAPORATOR AIR |
|
|
|
|
|
|
| CONDENSER ENTERING AIR TEMPERATURES ° F (° C) |
|
|
|
|
|
|
| ||||||
|
|
| 75 (23.9) |
|
| 85 (29.4) |
|
| 95 (35) |
|
| 105 (40.6) |
|
|
| 115 (46.1) |
|
| 125 (51.7) |
| |
CFM | EWB | Capacity MBtuh | Total | Capacity MBtuh | Total | Capacity MBtuh | Total | Capacity MBtuh |
| Total | Capacity MBtuh | Total | Capacity MBtuh | Total | |||||||
|
| System |
|
| System |
|
|
| System |
|
|
| System |
|
| System |
|
| System | ||
° F (° C) |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
| Total | Sens‡ | KW** | Total | Sens‡ | KW** | Total |
| Sens‡ | KW** | Total | Sens‡ |
| KW** | Total | Sens‡ | KW** | Total | Sens‡ | KW** | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
213ANA060---D Outdoor Section With FY4ANB060 Indoor Section
72 (22.2)
70.34
35.38
4.52
67.10
34.14
4.98
63.63
32.83
5.48
60.01
31.48
6.03
56.06
30.03
6.63
51.70
28.45
7.27
| 67 (19.4) | 64.72 | 44.25 | 4.46 | 61.72 | 42.98 | 4.92 | 58.50 | 41.62 | 5.42 | 55.15 | 40.23 | 5.97 | 51.50 | 38.73 | 6.57 | 47.50 | 37.11 | 7.21 |
1750 | 63 (17.2)†† | 60.52 | 42.98 | 4.41 | 57.68 | 41.67 | 4.87 | 54.66 | 40.31 | 5.37 | 51.50 | 38.90 | 5.92 | 48.09 | 37.40 | 6.52 | 44.37 | 35.78 | 7.17 |
| 62 (16.7) | 59.39 | 53.03 | 4.40 | 56.60 | 51.67 | 4.86 | 53.67 | 50.23 | 5.36 | 50.63 | 48.68 | 5.91 | 47.46 | 47.46 | 6.51 | 44.40 | 44.40 | 7.17 |
| 57 (13.9) | 57.36 | 57.36 | 4.38 | 55.12 | 55.12 | 4.84 | 52.73 | 52.73 | 5.35 | 50.21 | 50.21 | 5.90 | 47.45 | 47.45 | 6.51 | 44.40 | 44.40 | 7.17 |
| 72 (22.2) | 71.28 | 36.87 | 4.64 | 67.97 | 35.64 | 5.09 | 64.37 | 34.31 | 5.59 | 60.64 | 32.95 | 6.14 | 56.56 | 31.48 | 6.74 | 52.07 | 29.88 | 7.39 |
| 67 (19.4) | 65.71 | 46.88 | 4.58 | 62.60 | 45.59 | 5.03 | 59.26 | 44.22 | 5.53 | 55.79 | 42.80 | 6.08 | 52.01 | 41.28 | 6.69 | 47.89 | 39.62 | 7.33 |
2000 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
63 (17.2)†† | 61.54 | 45.45 | 4.53 | 58.58 | 44.14 | 4.99 | 55.44 | 42.75 | 5.49 | 52.17 | 41.32 | 6.04 | 48.63 | 39.78 | 6.64 | 44.80 | 38.11 | 7.28 | |
| 62 (16.7) | 60.48 | 56.64 | 4.52 | 57.63 | 55.18 | 4.98 | 54.66 | 54.31 | 5.48 | 51.85 | 51.85 | 6.03 | 48.91 | 48.91 | 6.64 | 45.66 | 45.66 | 7.30 |
| 57 (13.9) | 59.46 | 59.46 | 4.51 | 57.07 | 57.07 | 4.97 | 54.53 | 54.53 | 5.48 | 51.85 | 51.85 | 6.03 | 48.92 | 48.92 | 6.64 | 45.67 | 45.67 | 7.30 |
| 72 (22.2) | 71.96 | 38.30 | 4.75 | 68.56 | 37.06 | 5.21 | 64.87 | 35.72 | 5.71 | 61.04 | 34.35 | 6.26 | 56.86 | 32.87 | 6.86 | 52.26 | 31.26 | 7.50 |
| 67 (19.4) | 66.40 | 49.38 | 4.70 | 63.21 | 48.09 | 5.15 | 59.77 | 46.69 | 5.65 | 56.21 | 45.25 | 6.20 | 52.34 | 43.69 | 6.80 | 48.13 | 41.98 | 7.44 |
2250 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
63 (17.2)†† | 62.26 | 47.81 | 4.65 | 59.21 | 46.48 | 5.10 | 55.98 | 45.06 | 5.60 | 52.62 | 43.60 | 6.15 | 49.00 | 42.02 | 6.75 | 45.07 | 40.30 | 7.40 | |
| 62 (16.7) | 61.41 | 59.80 | 4.64 | 58.65 | 58.65 | 5.10 | 55.97 | 55.97 | 5.61 | 53.15 | 53.15 | 6.16 | 50.06 | 50.06 | 6.77 | 46.64 | 46.64 | 7.42 |
| 57 (13.9) | 61.16 | 61.16 | 4.64 | 58.65 | 58.65 | 5.10 | 55.97 | 55.97 | 5.61 | 53.16 | 53.16 | 6.16 | 50.07 | 50.07 | 6.77 | 46.65 | 46.65 | 7.42 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| COOLING INDOOR | CAPACITY | POWER | FURNACE MODEL |
| COOLING INDOOR | CAPACITY | POWER | FURNACE MODEL |
| COOLING INDOOR | CAPACITY | POWER | FURNACE MODEL |
| MODEL |
| MODEL |
| MODEL | |||||||||
|
|
|
|
|
|
|
|
|
|
|
| |||
| *FY4ANB060 | 1.00 | 1.00 |
|
| CSPH*6012A** | 1.00 | 0.96 | 315(A,J)AV066135 |
| CSPH*6012A** | 0.99 | 0.99 | 355(A,C)AV060100 |
| FE4ANB006 | 1.02 | 0.98 |
|
| CAP**6024A** | 1.00 | 0.96 | 315(A,J)AV066155 |
| CAP**6024A** | 0.98 | 0.98 | 355(A,C)AV060120 |
| FV4BNB006 | 1.02 | 0.96 |
|
| CNPH*6024A** | 0.99 | 0.96 | 315(A,J)AV066155 |
| CNPH*6024A** | 0.98 | 0.98 | 355(A,C)AV060120 |
| FX4CN(B,F)060 | 1.01 | 0.97 |
|
| CNPV*6024A** | 0.99 | 0.96 | 315(A,J)AV066155 |
| CNPV*6024A** | 0.98 | 0.98 | 355(A,C)AV060120 |
| CAP**6021A** | 0.99 | 0.99 |
|
| CSPH*6012A** | 1.00 | 0.96 | 315(A,J)AV066155 |
| CSPH*6012A** | 0.99 | 0.99 | 355(A,C)AV060120 |
| CAP**6024A** | 0.99 | 0.99 |
|
| CNPH*6024A** | 0.98 | 1.01 | 353AAV048080 |
| CAP**6021A** | 0.99 | 0.97 | 313*AV048090 |
| CNPH*6024A** | 0.99 | 0.99 |
|
| CSPH*6012A** | 0.98 | 1.01 | 353AAV048080 |
| CNPH*6024A** | 0.98 | 0.97 | 313*AV048090 |
33 | CNPV*6024A** | 0.99 | 0.99 |
|
| CAP**6021A** | 0.99 | 0.97 | 353AAV060100 |
| CSPH*6012A** | 0.99 | 0.97 | 313*AV048090 |
| CSPH*6012A** | 1.00 | 1.00 |
|
| CNPH*6024A** | 0.99 | 0.97 | 353AAV060100 |
| CAP**6021A** | 1.00 | 0.98 | 313*AV060110 |
| CAP**6021A** | 0.99 | 0.97 | 315(A,J)AV060110 |
| CSPH*6012A** | 0.99 | 0.97 | 353AAV060100 |
| CNPH*6024A** | 0.99 | 0.97 | 313*AV060110 |
| CNPH*6024A** | 0.99 | 0.97 | 315(A,J)AV060110 |
| CAP**6024A** | 0.99 | 0.97 | 353AAV060120 |
| CSPH*6012A** | 1.00 | 0.98 | 313*AV060110 |
| CSPH*6012A** | 1.00 | 0.98 | 315(A,J)AV060110 |
| CNPH*6024A** | 0.99 | 0.97 | 353AAV060120 |
| CAP**6024A** | 0.99 | 0.97 | 313*AV060135 |
| CAP**6024A** | 0.99 | 0.97 | 315(A,J)AV066135 |
| CNPV*6024A** | 0.99 | 0.97 | 353AAV060120 |
| CNPH*6024A** | 0.99 | 0.97 | 313*AV060135 |
| CNPH*6024A** | 0.99 | 0.97 | 315(A,J)AV066135 |
| CSPH*6012A** | 1.00 | 0.98 | 353AAV060120 |
| CNPV*6024A** | 0.99 | 0.97 | 313*AV060135 |
| CNPV*6024A** | 0.99 | 0.97 | 315(A,J)AV066135 |
| CAP**6021A** | 0.98 | 0.98 | 355(A,C)AV060100 |
| CSPH*6012A** | 1.00 | 0.98 | 313*AV060135 |
* Tested combination.
{Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
}Sensible capacities shown are based on 80_F (27_C) entering air at the indoor coil. For sensible capacities at other than 80_F (27_C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80_F (27_C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80_F (27_C).
#Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard
** System kw is total of indoor and outdoor unit kilowatts.
{{ At TVA rating indoor condition (75_F edb/63_F ewb). All other indoor air temperatures are at 80_F edb.
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice. EWB — Entering Wet Bulb
213A