Whirlpool W4GH6 installation instructions Connect Liquid and Suction Lines, Refrigerant Charge

Page 7

6.Tighten to 20 to 30 ft lbs. Use backup wrench on all wrench flats.

NOTE: Overtightening may crush the Teflon® seal and cause a leak.

7.Connect the external equalizer line to the equalizer port on the suction line.

8.Tighten to 8 ft lbs.

9.Attach the superheat sensing bulb to the suction header with the strap provided with the thermal expansion valve.

A B

F

C

E

D

A. Equalizer port

D. Liquid line

B. Superheat sensing bulb

E. Suction line

C. Thermal expansion valve

F. Equalizer line

NOTE: If installing a thermal expansion valve on an indoor coil that previously used a fixed orifice, be sure to remove the existing fixed orifice. Failure to remove a fixed orifice when installing a thermal expansion valve to the indoor coil may result in improper operation and damage to the system.

Connect Liquid and Suction Lines

1.Route the suction and liquid lines from the fittings on the indoor coil to the fittings on the heat pump. Run the lines in as direct a path as possible, avoiding unnecessary turns and bends.

2.For product efficiency, be sure that the suction line is insulated over the entire exposed length and that both suction and liquid lines are not in direct contact with floors, walls, ductwork, floor joists, or other piping.

3.Remove valve cores.

4.Wrap the service valves with a wet rag.

5.Connect the suction and liquid lines, using a brazing compound. Braze with an alloy of silver or copper and phosphorus with a melting point above 1,100°F.

NOTE: Do not use soft solder.

6.Make sure indoor coil has been put in place according to the Installation Instructions and is connected to the refrigerant lines.

7.Replace valve cores.

8.Pressurize the lines and indoor coil with a pressure not to exceed 20 psig.

9.Leak test the lines with a pressure not to exceed 20 psig.

10.Evacuate the indoor coil and lines to a minimum of

500 microns to remove contamination and moisture, then disconnect the vacuum pump.

11.Open the suction and liquid service valves fully.

12.Insulate the suction line with refrigerant line insulation material of ¹⁄₄" or more wall thickness.

13.Pack insulating material around refrigerant lines where they penetrate the structure to protect the lines and to minimize vibration transmission.

Refrigerant Charge

Refrigerant lines must be connected by a licensed, EPA certified refrigerant technician in accordance with established procedures.

IMPORTANT:

Refrigerant charge adjustment will be required for line set lengths greater than 15 ft and for evaporator coils not matched to the systems.

The heat pump is factory charged with the proper refrigerant charge amount for a matching evaporator and 15 ft of refrigerant line. Refer to the heat pump rating plate for the exact amount of this factory charge.

Adjustment of the refrigerant charge will be necessary based on the system combination and line length. To adjust the refrigerant size for increased line lengths, add the following amount of refrigerant.

For line set lengths greater than 15 ft, add refrigerant by weighing in 0.60 oz per ft of ³⁄₈" O.D. liquid line.

If necessary, adjust the refrigerant charge for compatibility with the evaporator coil.

In heat pump systems, horizontal suction lines should be slightly sloped toward the heat pump. Piping must avoid dips or low spots, which can collect oil.

Check Charge Using Normal Operating Pressures

Use Normal Operating Pressures chart to perform maintenance checks.

NOTES:

The Normal Operating Pressures chart is not a procedure for charging the system.

Minor variations in these pressures may be due to differences in installations.

Significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system.

7

Image 7
Contents Installation Requirements Heat Pump SafetySystem Requirements Tools and PartsLocation Requirements Line Set Isolation Installing Horizontal RunsInstalling Vertical Runs new construction shown Minimum ClearancesFlushing Connections Electrical RequirementsInspect Shipment Flush Refrigerant LinesOrifice Thermal Expansion ValveConnect Refrigerant Lines Install Thermal Expansion ValveThermal Expansion Valve Installation To install the thermal expansion valveConnect Liquid and Suction Lines Check Charge Using Normal Operating PressuresRefrigerant Charge Heating-2nd Stage High Capacity Cooling-1st Stage Low CapacityCooling-2nd Stage High Capacity Heating-1st Stage Low CapacityLiquid Line Sizes Single Phase Electrical ConnectionsMake Electrical Connections Suction Line SizesWithout Auxiliary Heat Typical Wiring Connection low voltage circuitOutdoor Unit Typical Wiring Diagram Complete InstallationDefrost Cycle Sequence of OperationCooling Cycle Heating CycleAdjust Defrost System Troubleshoot the Defrost System Defrost Control Setting Defrost Test Cycle TimeHeat Pump Fails to Operate Properly LED Description TroubleshootingSystem Diagnostic Module Diagnostic LEDs InterpretationLED Status Fault Description Troubleshooting Information VAC Power Wiring Thermostat Demand WiringIncorrectly Wired Module Troubleshooting Assistance or ServiceAccessories Incorrectly Wired Module CodesPage Page All rights reserved 48488A006

W4GH6 specifications

The Whirlpool W4GH6 is a cutting-edge refrigerator designed to meet the demands of modern households. With its sleek design and advanced features, it stands out as a reliable appliance that combines functionality with style.

One of the main features of the W4GH6 is its generous storage capacity. This refrigerator provides ample space for all your food storage needs, ensuring that you can store everything from fresh produce to large party platters without any hassle. The adjustable shelves allow for customizable configurations, accommodating items of various sizes.

Equipped with advanced cooling technologies, the Whirlpool W4GH6 ensures that your food stays fresher for longer. The refrigerator incorporates a multi-air flow system, which efficiently circulates cool air throughout the compartments, maintaining consistent temperatures. This technology helps prevent hotspots and ensures that all items, whether on the top or bottom shelf, receive equal cooling.

Energy efficiency is another hallmark of the W4GH6. It features an Energy Star certification, indicating that it meets strict energy efficiency guidelines set by the US Environmental Protection Agency. This means you can enjoy substantial savings on your energy bills while minimizing your environmental footprint.

The W4GH6 also offers a range of intelligent features designed for user convenience. The refrigerator comes with a temperature management system that allows users to set and monitor temperatures easily. Additionally, its frost-free operation means that you won't have to deal with the hassle of manual defrosting, making maintenance straightforward.

In terms of design, the Whirlpool W4GH6 boasts a modern aesthetic that complements any kitchen décor. The stainless steel finish not only adds a touch of elegance but also resists fingerprints and smudges, ensuring the appliance remains looking pristine.

For families with busy lifestyles, the Whirlpool W4GH6 includes a water and ice dispenser, providing easy access to chilled water and ice on demand. This feature is particularly convenient for hydration during hot days or for quickly preparing drinks for guests.

In summary, the Whirlpool W4GH6 is a versatile refrigerator that excels in both performance and style. Its spacious interior, advanced cooling technologies, and energy-efficient design make it a perfect choice for anyone looking to upgrade their kitchen appliances. With user-friendly features and a contemporary look, the W4GH6 is tailored to enhance your culinary experience while keeping your food fresher for longer.