5.If you are using one extension cord for more than one tool, add the nameplate amperes and use the sum to determine the required minimum cord size.

(See Table A.)

6.If you are using an extension cord outdoors, make sure it is marked with the suffix “W-A” (“W” in Canada) to indicate it is acceptable for outdoor use.

7.Make sure the extension cord is properly wired and in good electrical condition. Always replace a damaged extension cord or have it repaired by a qualified electrician before using it.

8.Protect the extension cords from sharp objects, excessive heat, and damp or wet areas.

RECOMMENDED MINIMUM WIRE GAUGE FOR EXTENSION CORDS*

(120 VOLT)

NAMEPLATE

EXTENSION CORD

 

LENGTH

 

AMPERES

 

 

25’

50’

75’

100’

150’

(at full load)

 

 

 

 

 

 

 

 

 

 

 

0 – 2.0

18

18

18

18

16

2.1

– 3.4

18

18

18

16

14

3.5

– 5.0

18

18

16

14

12

5.1

– 7.0

18

16

14

12

12

7.1 – 12.0

18

14

12

10

-

12.1

– 16.0

14

12

10

-

-

16.1

– 20.0

12

10

-

-

-

TABLE A

* Based on limiting the line

voltage drop to five volts at

150% of the rated amperes.

Symbology

Double Insulated

 

Canadian Standards Association

 

 

 

Underwriters Laboratories, Inc.

 

 

V~

Volts Alternating Current

A

Amperes

 

 

 

n0 xxxx/min.

No Load Revolutions per Minute

(RPM)

SKU 96035

For technical questions, please call 1-800-444-3353.

Page 7

Image 7
Contents For technical questions or replacement parts, please call Horsepower industrial breaker hammer kitSave This Manual General Power Tool Safety WarningsSave all warnings and instructions for future reference Power tool will increase the risk of electric shock Breaker Hammer Safety Warnings Vibration Safety Grounded Tools Tools with Three Prong Plugs GroundingExtension Cords 25’ 50’ 75’ SymbologyUnpacking SpecificationsInstructions for putting Into use AssemblyWithout a Collar Installing a ChiselSKU For technical questions, please call With a CollarUse this tool only with a AMP Circuit Breaker Work Piece and Work Area Set UpOperating Instructions General OperationSlide Cover off top of Breaker Hammer. See Figure Slide Gearbox open so that Wire Board Wire Fixing Board Cleaning, Maintenance, Lubrication Maintenance ServicingProblem Possible Causes Likely Solutions TroubleshootingPart Description Qty Parts ListAssembly Drawing Record Product’s Serial Number Here Limited 90 DAY Warranty