ECOi Mini 4-6HP 2 Way Inverter Heat Pump VRF Systems

ECOi 2 Way - features at a glance

 

 

 

 

 

 

 

 

 

 

 

SANYO’s policy of product development continues with the expansion of the ECOi Mini, the 2 pipe heat pump small VRF system specifically designed for the European market.

Offering between 11kW and 16kW cooling capacity in 3 sizes and up to 9 indoor units connected, the ECOi Mini sets new standards of performance and flexibility.

Utilising R410A and DC inverter technology, SANYO offers VRF to a new and growing market.

Forming a new key part of the SANYO VRF line up, the ECOi Mini is compatible with the same indoor units and controls of the electric and gas powered VRF range.

Features at a glance

Single phase or three phase power supply

One AMP start current

DC inverter technology combined with R410A for excellent efficiency

COP of up to 4.34

Diversity ratio 50-130%

150m pipe runs

Cooling operation to -10°C

Full range of indoor units and control options

Compact outdoor unit 1230x940x340mm

Highest COPs - lowest running costs

HP

4

5

6

EER Cooling

4.06

3.66

3.39

COP Heating

4.34

4.10

3.84

 

 

 

 

Wide operating range

The operating range for heating operation is to -20°C, the cooling range is to -10°C. The remote controller temperature setting offers a range from 16°C to 30°C.

ECOi 2 Way is a high-performance heat pump system with excellent energy-saving features, designed for creating a comfortable environment when either heating or cooling is required.

Heat pump systems offer heating or cooling

Single footprint size for all unit capacities

DC inverter technology combined with R410A for excellent efficiency

System configuration from 8HP to 48HP

Diversity ratio 50-130%

Industry low outdoor unit sound levels: from 54.5dB(A)

Quiet mode offers a further 3dB(A) reduction

Extended pipe runs of up to 150m

COPs up to 4.10

Heating capacity to -20°C

Connectability of 40 indoor units from 24HP upwards

Units available from 8-16HP as single units

Extended compressor life

The compressor running time is monitored and optimised by a microcomputer to ensure that there is no imbalance in the operation times of compressors on the same refrigerant circuit.

Longer piping means greater installation area

Reducing the refrigerant volume by reducing piping size has extended the piping actual length to 150m (175m equivalent piping length).

Save on piping cost

HP

 

4

5

 

6

Model name

 

SPW-CR365GXH56B/SPW-CR365GXH8B

SPW-CR485GXH56B/SPW-CR485GXH8B

SPW-CR605GXH56B/SPW-CR605GXH8B

Power supply

 

 

230V, 1 phase, 50/60Hz/400, 3 phase, 50/60Hz

 

Cooling capacity

kW

11.20

14.00

 

15.50

Heating capacity

kW

12.50

16.00

 

17.60

EER Cooling

 

4.06

3.66

 

3.39

R410A with low pressure loss enables smaller pipe sizes. This means reduced piping space, improved workability at the site and reduced piping material costs.

Extended operating range - better output at lower temperatures

System difference of elevation: 50m *1

COP Heating

 

 

4.34

4.10

3.84

 

 

Running

A

14.1/4.34

19.6/6.02

23.4/7.18

 

Cooling

amperes

Electric rating

 

Power input

kW

2.76

3.83

4.57

 

Running

A

14.7/4.52

19.9/6.13

23.4/7.19

 

 

 

Heating

amperes

 

 

Power input

kW

2.88

3.90

4.58

Recommended fuse size (motor

1ph 3ph

 

25/16

 

32/16

rated)

 

 

 

 

 

 

 

Dimensions (H/W/D)

mm

 

 

1,230x940x340

 

Net weight

kg

 

 

104

 

The operating range for heating has been extended to

 

-15°C. The remote controller temperature setting for heating

 

operation has also been extended from 16°C to 30°C.

Difference in elevation

 

between indoor units: 15m

Actual length: 150m*2 (Equivalent length: 175m)

Air circulation

 

m3/min

 

 

100

 

Refrigerant amount at shipment

 

kg

 

 

3.5

 

 

 

Gas

Inches

 

5/8 (15.88)

3/4 (19.05)

Piping connection

 

(mm)

 

 

Liquid

Inches

 

3/8 (9.52)

 

 

 

 

 

 

 

(mm)

 

 

Operating sound normal mode

 

dB(A)

 

 

51.0

52.0

Operating sound quiet mode

 

 

 

48.0

49.0

 

 

 

 

Ambient temperature operating

 

Cooling

 

 

 

-10°C DB +43°C DB

 

range

 

Heating

 

 

 

-20°C DB +15°C DB

 

Maximum number of indoor units

 

 

 

6

 

8

9

*Condenser actual pipe connections may vary from above pipe connections shown, please refer to technical manuals for full details.

*Please refer to tube sizing charts for pipe selections and pipe length parameters.

5

UK Conditions: Cooling Indoor 23˚C DB 50% RH Outdoor 30˚C Heating Indoor 20˚C Outdoor 0˚C

Rating Conditions: Cooling Indoor 27˚C DB 19˚C WB Outdoor 35˚C DB 24˚C WB Heating Indoor 20˚C DB Outdoor 7˚C DB 6˚C WB

*1: 40m if the outdoor unit is below the indoor unit.

*2: Total length of pipe: no more than 300m

Higher COPs - lower running costs

HP

8

10

12

14

16

18

20

22

 

24

26

28

30

32

34

36

38

40

42

44

46

48

EER Cooling

3.74

3.54

3.50

3.45

3.38

3.63

3.54

3.51

 

3.49

3.44

3.43

3.41

3.38

3.50

3.47

3.47

3.45

3.42

3.43

3.40

3.38

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COP Heating

4.10

4.10

3.91

3.91

3.79

4.06

4.06

3.97

 

3.96

3.88

3.84

3.85

3.79

4.00

3.94

3.89

3.91

3.86

3.83

3.83

3.79

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UK Conditions: Cooling Indoor 23˚C DB 50% RH Outdoor 30˚C Heating Indoor 20˚C Outdoor 0˚C

 

 

 

 

 

 

 

 

 

 

 

 

6

Rating Conditions: Cooling Indoor 27˚C DB 19˚C WB Outdoor 35˚C DB 24˚C WB Heating Indoor 20˚C DB Outdoor 7˚C DB 6˚C WB

 

 

 

 

 

 

 

 

Image 4
Contents Electric VRF Ease of installation Off-coil temperature controlSimple to design Easy to positionSANYO-Installation cost saving design Solenoid Valve Box SANYO-Comfort control Air Discharge Temperature ControlUnique Sanyo benefits New PAC2 System Design Software Reduces the running cost of the systemECOi 2 Way features at a glance ECOi 2 Way Heat Pump VRF Inverter Systems ECOi 3 Way features at a glance Solenoid Valve Kit Higher COPs lower running costsProblems ECOi 3 Way Heat Recovery VRF Inverter SystemsIndustry’s smallest changeover boxes fewer locating Wireless remote control VRF Indoor Unit Range for ECOi and GHPOperation system Individual control systems Timer operation Centralised control systemsModel Name GU Type Heat Exchanger CFR UnitsModel CFR/ CFR-PHE 110 175 220