ECOi Mini | ECOi 2 Way - features at a glance |
|
|
| |||
|
|
|
|
|
|
|
|
SANYO’s policy of product development continues with the expansion of the ECOi Mini, the 2 pipe heat pump small VRF system specifically designed for the European market.
Offering between 11kW and 16kW cooling capacity in 3 sizes and up to 9 indoor units connected, the ECOi Mini sets new standards of performance and flexibility.
Utilising R410A and DC inverter technology, SANYO offers VRF to a new and growing market.
Forming a new key part of the SANYO VRF line up, the ECOi Mini is compatible with the same indoor units and controls of the electric and gas powered VRF range.
Features at a glance
•Single phase or three phase power supply
•One AMP start current
•DC inverter technology combined with R410A for excellent efficiency
•COP of up to 4.34
•Diversity ratio
•150m pipe runs
•Cooling operation to
•Full range of indoor units and control options
•Compact outdoor unit 1230x940x340mm
Highest COPs - lowest running costs
HP | 4 | 5 | 6 |
EER Cooling | 4.06 | 3.66 | 3.39 |
COP Heating | 4.34 | 4.10 | 3.84 |
|
|
|
|
Wide operating range
The operating range for heating operation is to
ECOi 2 Way is a
•Heat pump systems offer heating or cooling
•Single footprint size for all unit capacities
•DC inverter technology combined with R410A for excellent efficiency
•System configuration from 8HP to 48HP
•Diversity ratio
•Industry low outdoor unit sound levels: from 54.5dB(A)
•Quiet mode offers a further 3dB(A) reduction
•Extended pipe runs of up to 150m
•COPs up to 4.10
•Heating capacity to
•Connectability of 40 indoor units from 24HP upwards
•Units available from
Extended compressor life
The compressor running time is monitored and optimised by a microcomputer to ensure that there is no imbalance in the operation times of compressors on the same refrigerant circuit.
Longer piping means greater installation area
Reducing the refrigerant volume by reducing piping size has extended the piping actual length to 150m (175m equivalent piping length).
Save on piping cost
HP |
| 4 | 5 |
| 6 | |
Model name |
| |||||
Power supply |
|
| 230V, 1 phase, 50/60Hz/400, 3 phase, 50/60Hz |
| ||
Cooling capacity | kW | 11.20 | 14.00 |
| 15.50 | |
Heating capacity | kW | 12.50 | 16.00 |
| 17.60 | |
EER Cooling |
| 4.06 | 3.66 |
| 3.39 |
R410A with low pressure loss enables smaller pipe sizes. This means reduced piping space, improved workability at the site and reduced piping material costs.
Extended operating range - better output at lower temperatures
System difference of elevation: 50m *1
COP Heating |
|
| 4.34 | 4.10 | 3.84 | |
|
| Running | A | 14.1/4.34 | 19.6/6.02 | 23.4/7.18 |
| Cooling | amperes | ||||
Electric rating |
| Power input | kW | 2.76 | 3.83 | 4.57 |
| Running | A | 14.7/4.52 | 19.9/6.13 | 23.4/7.19 | |
|
| |||||
| Heating | amperes | ||||
|
| Power input | kW | 2.88 | 3.90 | 4.58 |
Recommended fuse size (motor | 1ph 3ph |
| 25/16 |
| 32/16 | |
rated) |
|
| ||||
|
|
|
|
| ||
Dimensions (H/W/D) | mm |
|
| 1,230x940x340 |
| |
Net weight | kg |
|
| 104 |
|
The operating range for heating has been extended to |
|
| |
operation has also been extended from 16°C to 30°C. | Difference in elevation |
|
between indoor units: 15m
Actual length: 150m*2 (Equivalent length: 175m)
Air circulation |
| m3/min |
|
| 100 |
| |
Refrigerant amount at shipment |
| kg |
|
| 3.5 |
| |
|
| Gas | Inches |
| 5/8 (15.88) | 3/4 (19.05) | |
Piping connection |
| (mm) |
| ||||
| Liquid | Inches |
| 3/8 (9.52) |
| ||
|
|
|
| ||||
|
| (mm) |
|
| |||
Operating sound normal mode |
| dB(A) |
|
| 51.0 | 52.0 | |
Operating sound quiet mode |
|
|
| 48.0 | 49.0 | ||
|
|
|
| ||||
Ambient temperature operating |
| Cooling |
|
|
|
| |
range |
| Heating |
|
|
|
| |
Maximum number of indoor units |
|
|
| 6 |
| 8 | 9 |
*Condenser actual pipe connections may vary from above pipe connections shown, please refer to technical manuals for full details.
*Please refer to tube sizing charts for pipe selections and pipe length parameters.
5 | UK Conditions: Cooling Indoor 23˚C DB 50% RH Outdoor 30˚C Heating Indoor 20˚C Outdoor 0˚C |
Rating Conditions: Cooling Indoor 27˚C DB 19˚C WB Outdoor 35˚C DB 24˚C WB Heating Indoor 20˚C DB Outdoor 7˚C DB 6˚C WB |
*1: 40m if the outdoor unit is below the indoor unit.
*2: Total length of pipe: no more than 300m
Higher COPs - lower running costs
HP | 8 | 10 | 12 | 14 | 16 | 18 | 20 | 22 |
| 24 | 26 | 28 | 30 | 32 | 34 | 36 | 38 | 40 | 42 | 44 | 46 | 48 |
EER Cooling | 3.74 | 3.54 | 3.50 | 3.45 | 3.38 | 3.63 | 3.54 | 3.51 |
| 3.49 | 3.44 | 3.43 | 3.41 | 3.38 | 3.50 | 3.47 | 3.47 | 3.45 | 3.42 | 3.43 | 3.40 | 3.38 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
COP Heating | 4.10 | 4.10 | 3.91 | 3.91 | 3.79 | 4.06 | 4.06 | 3.97 |
| 3.96 | 3.88 | 3.84 | 3.85 | 3.79 | 4.00 | 3.94 | 3.89 | 3.91 | 3.86 | 3.83 | 3.83 | 3.79 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
UK Conditions: Cooling Indoor 23˚C DB 50% RH Outdoor 30˚C Heating Indoor 20˚C Outdoor 0˚C |
|
|
|
|
|
|
|
|
|
|
|
| 6 | |||||||||
Rating Conditions: Cooling Indoor 27˚C DB 19˚C WB Outdoor 35˚C DB 24˚C WB Heating Indoor 20˚C DB Outdoor 7˚C DB 6˚C WB |
|
|
|
|
|
|
|
|