Sanyo SPW-FTR124EH56 Electrical Wiring, General Precautions on Wiring, Outdoor unit Power supply

Page 8
Max. 130 m
2.5 mm2

4. ELECTRICAL WIRING

4-1. General Precautions on Wiring

(1)Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram.

(2)Provide a power outlet to be used exclusively for each unit, and a power supply disconnect and cir- cuit breaker for overcurrent protection should be provided in the exclusive line.

(3)To prevent possible hazards from insulation fail- ure, the unit must be grounded.

(4)Each wiring connection must be done in accor- dance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged.

(5)Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.

(6)Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.

(7)Regulations on wire diameters differ from locality to locality. For field wiring rules, please refer to your LOCAL ELECTRICAL CODES before begin- ning.

You must ensure that installation complies with all relevant rules and regulations.

(8)To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows:

The remote control wiring and the inter-unit control wiring should be wired apart from the inter-unit power wiring.

Use shielded wires for inter-unit control wiring between units and ground the shield on both sides.

(9)If the power supply cord of this appliance is dam- aged, it must be replaced by a repair shop appointed by the manufacture, because special purpose tools are required.

4-2. Recommended Wire Length and Wire Diameter for Power Supply System

Outdoor unit

 

(A) Power supply

Time delay fuse or

 

Wire size

Max. length

circuit capacity

SPW-CR254GV(H)56-C

4 mm2

24 m

25 A

SPW-CR364GV(H)56-C

4 mm2

22 m

25 A

SPW-CR484GV(H)56-C

6 mm 2

30 m

35 A

Indoor unit

(B) Power supply Time delay fuse or circuit capacity

10

Control wiring

(C) Inter-unit (between outdoor and

(D) Remote control wiring

(E) Control wiring for group control

indoor units) control wiring

 

 

 

 

 

0.75 mm2 (AWG #18)

0.75 mm2 (AWG #18)

0.75 mm2 (AWG #18)

Use shielded wiring*

Use shielded wiring

Use shielded wiring

Max. 1,000 m

Max. 500 m

Max. 500 m (Total)

 

 

 

NOTE

* With ring-type wire terminal.

8

Image 8
Contents SPW-FTR124EH56 SPW-FTR164EH56 SPW-FTR184EH56 Outdoor UnitsOptional Controllers Sanyo Airconditioners Europe S.r.lSpecial Precautions Check of Density Limit Contents GeneralDimensions mm HOW to Install the Unit Floor installationWall installation Under ceiling installation10 mm Electrical Wiring General Precautions on WiringOutdoor unit Power supply Wire size Max. length Circuit capacityWiring System Diagrams 7P terminal boardOutdoor unit Indoor unit How to connect wiring to the terminal For stranded wiring Driver. FigHOW to Process Tubing Connecting the Refrigerant Tubing Use of the Flaring MethodFlaring Procedure with a Flare Tool DeburringTube diameter Tightening torque Tube thickness Approximate · cm 140 180 kgf Φ9.52 3/8Precautions for Packed Valve Operation Insulating the Refrigerant Tubing Tubing InsulationInsulation material After a tube has been insu Lated, never try to bend itFinishing the Installation Taping the TubesInstalling the Control Unit AccessoriesSpecial Remarks Qty PartsCare and Cleaning Filter CleaningAIR Clean Filter Accessory Supplied on Request How to install the Air clean filterTroubleshooting Should the power fail while the unit is runningTips for Energy Saving Trouble Possible Cause RemedyFiltre AIR a Haute Efficacite Accessoire SUR Demande Application de laccessoireEntretien et nettoyage Nettoyage DU FiltreGuide de dépannage Conseils pour économiser l’énergiePanne Cause possible Remède RemarquePflege und Reinigung Herausnehmen des FiltersFilterreinigung Luftfilter MIT GROßER Leistungsfähigkeit AUF AnfrageFehlersuche Nützliche Hinweise für EnergieeinsparungStörung Mögliche Ursache Abhilfe Bei einem Stromausfall während des Betriebs des GerätsCome applicare laccessorio Cura e manutenzioneLato presa d’aria e uscita d’aria unità interna Pulizia FiltroProblema Causa probabile Rimedio Prima di chiamare il tecnicoSuggerimenti per risparmiare energia Mancanza di corrente durante il funzionamento dell’unitàCuidados e limpeza Lado de entrada e saída de ar unidade interiorPrecaução Limpeza do FiltroResolução de problemas Sugestões para poupar energiaAvaria Causa possível Solução Se ocorrer uma falha de energia com a unidade a funcionarEnergoá Αντιµετώπιση προβληµάτων Cuidados y limpieza Lados de entrada y salida de aire Unidad interiorLimpieza DEL Filtro Cómo se aplica el accesorioAvería Causa posible Remedio Localización de averíasSugerencias para ahorrar energía

SPW-FTR124EH56 specifications

The Sanyo SPW-FTR124EH56 is a cutting-edge air conditioning unit that combines energy efficiency with advanced technology, making it ideal for both residential and commercial applications. As a part of Sanyo's renowned product line, this model stands out for its sleek design and innovative features, aimed at providing optimal comfort throughout the year.

One of the key attributes of the SPW-FTR124EH56 is its inverter technology. This feature allows the compressor to adjust its speed dynamically, ensuring that the unit operates at the most efficient level for the given conditions. Consequently, this results in significant energy savings, with reduced power consumption compared to traditional air conditioning systems. The inverter technology also contributes to quieter operation, making it a perfect choice for living spaces, offices, and other environments where noise can be a concern.

The SPW-FTR124EH56 boasts a high cooling and heating capacity, making it versatile for varying climates. It is equipped with a powerful rotary compressor that ensures rapid temperature adjustment, providing relief during hot summer days and warmth during chilly winters. The unit's continuous heating capability allows it to maintain comfortable indoor temperatures even in extreme outdoor conditions.

Another notable feature is its advanced filtration system. The air conditioning unit comes with a built-in air purifying filter that effectively removes dust, allergens, and other airborne particles. This not only enhances indoor air quality but also contributes to the longevity of the unit by reducing the accumulation of dirt and debris.

The SPW-FTR124EH56 offers a user-friendly interface, with an intuitive remote control that allows for easy temperature adjustments and mode selections. Additionally, it features a programmable timer, enabling users to set the unit to operate at specific times, ensuring the space is always at a comfortable temperature without wasting energy when it’s unnecessary.

Moreover, the compact design of the Sanyo SPW-FTR124EH56 makes installation straightforward, allowing it to fit seamlessly into various settings. Its high energy efficiency rating highlights its environmental friendliness, appealing to eco-conscious consumers seeking sustainable climate control solutions.

In summary, the Sanyo SPW-FTR124EH56 is a highly efficient air conditioning unit that combines powerful performance with modern technology. With features like inverter technology, effective air filtration, and user-friendly controls, it is designed to provide year-round comfort while being mindful of energy consumption and environmental impact. Whether for home or office use, it represents an excellent choice for those seeking reliability and efficiency in climate control.