Sanyo CM3212, KMS1812 service manual 208V CM3622 / KMS0712⋅1

Page 13

208V

CM3622 / KMS07121

Rating Capacity: 7,000 BTU/H

 

 

Air Flow Rate: 210 CFM

 

Evaporator

 

 

 

Condenser

 

 

Ent. Temp.

°F/(°C)

 

 

Ambient Temp.

°F/(°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WB

 

DB

 

75

 

85

 

95

 

105

115

 

 

(23.9)

 

(29.4)

(35.0)

 

(40.6)

(46.1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

6,930

 

6,620

 

6,300

 

5,940

5,460

 

 

 

kW

0.47

 

0.51

 

0.56

 

0.60

0.66

59

 

72 (22.2)

SHC

5,220

 

5,070

 

4,920

 

4,750

4,520

(15.0)

 

76 (24.4)

SHC

5,940

 

5,780

 

5,630

 

5,460

5,240

 

 

80 (26.7)

SHC

6,690

 

6,530

 

6,300

 

5,940

5,460

 

 

84 (28.9)

SHC

6,930

 

6,620

 

6,300

 

5,940

5,460

 

 

88 (31.1)

SHC

6,930

 

6,620

 

6,300

 

5,940

5,460

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

7,170

 

6,940

 

6,670

 

6,310

5,810

 

 

 

kW

0.47

 

0.52

 

0.56

 

0.61

0.68

63

 

72 (22.2)

SHC

4,360

 

4,250

 

4,130

 

3,970

3,760

(17.2)

 

76 (24.4)

SHC

5,070

 

4,970

 

4,850

 

4,690

4,470

 

 

80 (26.7)

SHC

5,820

 

5,720

 

5,590

 

5,430

5,220

 

 

84 (28.9)

SHC

6,530

 

6,430

 

6,310

 

6,150

5,810

 

 

88 (31.1)

SHC

7,170

 

6,940

 

6,670

 

6,310

5,810

 

 

 

TC

7,360

 

7,250

*7,000

 

6,620

6,160

 

 

 

kW

0.48

 

0.52

 

0.57

 

0.62

0.69

67

 

72 (22.2)

SHC

3,460

 

3,410

 

3,310

 

3,160

2,970

(19.4)

 

76 (24.4)

SHC

4,170

 

4,130

 

4,030

 

3,870

3,690

 

 

80 (26.7)

SHC

4,920

 

4,870

 

4,770

 

4,620

4,400

 

 

84 (28.9)

SHC

5,640

 

5,590

 

5,490

 

5,330

5,150

 

 

88 (31.1)

SHC

6,350

 

6,300

 

6,200

 

6,050

5,860

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

7,600

 

7,470

 

7,280

 

6,950

6,550

 

 

 

kW

0.48

 

0.53

 

0.58

 

0.64

0.70

71

 

72 (22.2)

SHC

2,540

 

2,490

 

2,420

 

2,300

2,150

(21.7)

 

76 (24.4)

SHC

3,250

 

3,210

 

3,140

 

3,020

2,870

 

 

80 (26.7)

SHC

4,000

 

3,950

 

3,880

 

3,760

3,620

 

 

84 (28.9)

SHC

4,720

 

4,670

 

4,600

 

4,480

4,330

 

 

88 (31.1)

SHC

5,430

 

5,380

 

5,310

 

5,190

5,040

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

7,740

 

7,660

 

7,490

 

7,220

6,930

 

 

 

kW

0.49

 

0.54

 

0.59

 

0.65

0.72

75

 

76 (24.4)

SHC

2,340

 

2,310

 

2,260

 

2,170

2,070

(23.9)

 

80 (26.7)

SHC

3,090

 

3,060

 

3,000

 

2,910

2,820

 

 

84 (28.9)

SHC

3,800

 

3,770

 

3,720

 

3,630

3,530

 

 

88 (31.1)

SHC

4,520

 

4,490

 

4,430

 

4,340

4,250

 

 

 

 

 

 

 

 

 

 

 

 

TC: Total Cooling Capacity (BTU/H)

SHC: Sensible Heat Capacity (BTU/H)

kW: Compressor Input (kW)

Remarks: Rating conditions (* mark) are: Outside ambient temperature 95°F DB

Indoor unit entering air temperature 80°F DB/67°F WB

8WM – 700699

Image 13
Contents Split System AIR Conditioner Page CM3212 / KMS0712⋅2+KMS1812 Basic Information …In a Ceiling or Wall For safe installation and trouble-free operation, you must…In a Room …In Moist or Uneven LocationsTable of Contents CM3212 / KMS0712⋅2+KMS1812 Operating RangeUnit Specifications SpecificationsApplicable Indoor Unit KMS1812 Wall-mounted Cooling 18,000 / 17,600 440 Outdoor Unit CM3212 Dimensional DataIndoor Unit KMS1812 Indoor Unit KMS0712230V CM3622 / KMS0712⋅1 Cooling Capacity208V CM3622 / KMS0712⋅1 230V CM3622 / KMS1812 208V CM3622 / KMS1812 Outdoor Unit Refrigerant Flow DiagramElectrical Data Electrical Characteristics CM3212 / KMS0712⋅1CM3212 / KMS1812⋅1 CM3212 / KMS7012⋅2CM3212 / KMS7012⋅2+KMS1812 CM3212 / KMS0712+KMS1812To avoid electrical shock hazard, be sure to Controller From Outdoor Unit H406/12M