Sanyo Electrical Data, Electrical Characteristics CM3212 / KMS0712⋅1, CM3212 / KMS1812⋅1

Page 17

6. ELECTRICAL DATA

Electrical Characteristics

CM3212 / KMS07121

Performance at

Indoor Unit

 

Outdoor Unit

 

Complete Unit

230/208V – 1ø – 60Hz

Fan Motor

Fan Motor

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

Rating Conditions

A

0.15

/ 0.14

0.62

/ 0.56

2.53

/ 2.80

3.3

/ 3.5

 

 

 

 

 

 

 

 

 

W

34

/ 28

140

/ 126

576

/ 566

750

/ 720

 

 

 

 

 

 

 

 

 

Locked-Rotor Amperes

A

0.19

/ 0.18

1.95

/ 1.77

22

 

 

 

 

 

 

 

 

Remarks: Rating conditions are: Outside air temperature 95°F DB/75°F WB

 

 

 

 

 

Indoor unit entering air temperature 80°F DB/67°F WB

 

 

CM3212 / KMS18121

Performance at

Indoor Unit

 

Outdoor Unit

 

Complete Unit

230/208V – 1ø – 60Hz

Fan Motor

Fan Motor

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

Rating Conditions

A

0.4

/ 0.4

1.45

/ 1.42

7.05

/ 7.68

8.9

/ 9.5

 

 

 

 

 

 

 

 

 

W

90

/ 80

330

/ 290

1,580

/ 1,580

2,000

/ 1,950

 

 

 

 

 

 

 

 

 

Locked-Rotor Amperes

A

0.45

/ 0.40

1.95

/ 1.77

54

 

 

 

 

 

 

 

 

Remarks: Rating conditions are: Outside air temperature 95°F DB/75°F WB

 

 

 

 

 

Indoor unit entering air temperature 80°F DB/67°F WB

 

 

CM3212 / KMS70122

Performance at

Indoor Units

 

Outdoor Unit

Complete Unit

230/208V – 1ø – 60Hz

Fan Motor

Fan Motor

Compressor

 

 

 

 

 

 

 

 

 

 

 

Rating Conditions

A

0.30

/ 0.28

1.45

/ 1.42

4.95 / 5.5

6.7

/ 7.2

 

 

 

 

 

 

 

 

W

68

/ 56

330

/ 290

1,142 / 1,144

1,540

/ 1,490

 

 

 

 

 

 

 

 

Locked-Rotor Amperes

A

(0.19 / 0.18) 2

1.95

/ 1.77

22 2

 

 

 

 

 

 

 

 

 

Remarks: Rating conditions are: Outside air temperature 95°F DB/75°F WB

Indoor unit entering air temperature 80°F DB/67°F WB

12WM – 700699

Image 17
Contents Split System AIR Conditioner Page CM3212 / KMS0712⋅2+KMS1812 Basic Information …In a Ceiling or Wall For safe installation and trouble-free operation, you must…In a Room …In Moist or Uneven LocationsTable of Contents CM3212 / KMS0712⋅2+KMS1812 Operating RangeUnit Specifications SpecificationsApplicable Indoor Unit KMS1812 Wall-mounted Cooling 18,000 / 17,600 440 Outdoor Unit CM3212 Dimensional DataIndoor Unit KMS1812 Indoor Unit KMS0712230V CM3622 / KMS0712⋅1 Cooling Capacity208V CM3622 / KMS0712⋅1 230V CM3622 / KMS1812 208V CM3622 / KMS1812 Outdoor Unit Refrigerant Flow DiagramElectrical Data Electrical Characteristics CM3212 / KMS0712⋅1CM3212 / KMS1812⋅1 CM3212 / KMS7012⋅2CM3212 / KMS7012⋅2+KMS1812 CM3212 / KMS0712+KMS1812To avoid electrical shock hazard, be sure to Controller From Outdoor Unit H406/12M