HP Extech 380976 manual Specifications

Page 17

Specifications

General Specifications

 

Display

Dual Display; 4-digit, 10,000 count (0 to 9999) LCD

Jaw Opening

1.6” (42mm)

Max. Input limit

Max. voltage between any terminal and ground: 600Vrms

Sampling rate

2.5 times per second (Digital Display); Once every 6

 

seconds (KW, KVA, and KVAR)

Auto Sleep

After approx. 30 minutes (feature can be defeated)

Low battery indication

Battery symbol appears on the LCD

Power supply

9V Battery

Battery life

Approx. 32 hours with alkaline battery

Operating Temperature

32 to 122oF (0 to 50oC)

Operating Humidity

< 80% RH

Operating Altitude

7000 ft. (2000 meters) maximum.

Storage Temperature

14 to 140oF (-10 to 60oC)

Storage Humidity

< 70% RH

Temperature coefficient

0.1 x (specified accuracy) / oC at < 64oF (18oC), > 82oF

 

(28oC)

Dimensions

9.0 x 3.0 x 1.5" (228 x 76 x 39mm)

Weight

Approx. 1.0 lb. (465g)

Approvals

CE, UL

Safety

This meter is intended for indoor use and protected, against

 

the users, by double insulation per EN61010-1 and

 

IEC61010-1 2nd Edition (2001) to CAT III 600V; Pollution

 

Degree 2. The meter also meets UL 61010A-1, First Edition

UL Listed

The UL mark does not indicate that this product has been

 

evaluated for the accuracy of its readings.

PER IEC1010 OVERVOLTAGE INSTALLATION CATEGORY

OVERVOLTAGE CATEGORY I

Equipment of OVERVOLTAGE CATEGORY I is equipment for connection to circuits in which measures are taken to limit the transient overvoltages to an appropriate low level. Note – Examples include protected electronic circuits.

OVERVOLTAGE CATEGORY II

Equipment of OVERVOLTAGE CATEGORY II is energy-consuming equipment to be supplied from the fixed installation.

Note – Examples include household, office, and laboratory appliances.

OVERVOLTAGE CATEGORY III

Equipment of OVERVOLTAGE CATEGORY III is equipment in fixed installations. Note – Examples include switches in the fixed installation and some equipment for industrial use with permanent connection to the fixed installation.

OVERVOLTAGE CATEGORY IV

Equipment of OVERVOLTAGE CATEGORY IV is for use at the origin of the installation. Note – Examples include electricity meters and primary over-current protection equipment

17

380976

V3.1

6/08

Image 17
Contents 1Φ/3Φ 1000 Amp True RMS Power Clamp-On Model Introduction Table of ContentsWhen servicing, use only specified replacement parts WarrantySafety Information Meter Description AC Current Measurements MeasurementsAC + DC Voltage Measurements 380976 V3.1 380976 V3.1 KVA 3φ 3W KW+PF Power Factor, KW+KVAR, KVA+θPhase Angle or A+V380976 V3.1 380976 V3.1 380976 V3.1 380976 V3.1 Resistance and Audible Continuity Measurements KVA 3φ 4WCapacitance Measurements Temperature MeasurementsDiode Tests AC and DC µA MeasurementsRange Key Meter Control KeysHold MX/MN Key Battery Replacement Automatic Sleep Mode and Battery ReplacementAuto Sleep Disable Specifications AC Current 50Hz to 400Hz True RMS Measurement SpecificationsΜA True RMS AC+DC AC Voltage 50Hz to 400Hz True RMS1Φ/3Φ True Power PF 0.5 or 60o 50/60Hz Temperature K-Type thermocouple1Φ/3Φ Horse Power HP PF 0.5 or 60o 50/60Hz 1Φ/3Φ Reactive Power Kvar PF 0.5 or 60o 50/60Hz1Φ/3Φ Apparent Power KVA Calibration and Repair ServicesPhase Angle 50/60Hz Frequency