Water quality requirements
Water quality requirements and specifications
•
•The chilled water temperature to be supplied to the HP POD must be 12º to 24ºC (55º to 75ºF).
NOTE: Freezing water might cause a blockage and damage to the unit. In outside locations subject to freezing temperatures, an additive such as glycol might be necessary to lower the freezing point. However, since the heat transfer potential of water with glycol is lower, the HP POD must be derated accordingly.
NOTE: The water cycle must be drained completely, and then purged using compressed air when storing or transporting at or below freezing temperatures.
Acceptable water quality specifications
Water must be maintained per the following acceptable water quality standards.
Parameter | Range |
|
|
pH | |
|
|
Specific conductance at 25ºC | |
(77ºF) |
|
|
|
Alkalinity ("M" as CaCO3) | |
Sulfur (SO4) | |
Chloride (Cl) | |
|
|
Hardness (CaCO3) | |
Calcium hardness (CaCO3) | |
Magnesium hardness (CaCO3) | |
Copper (Cu) | < 0.20 ppm |
|
|
Iron (Fe) | < 3.0 ppm |
|
|
Aluminum (Al) | < 0.50 ppm |
|
|
Sodium (Na) | |
|
|
Silica (SiO2) | |
Zinc (Zn) | < 1.0 ppm |
|
|
Manganese (Mn) | < 0.1 ppm |
|
|
Phosphate Ortho- (PO4) | < 3 ppm |
Bacteria | < 1000 CFU/ml |
|
|
Suspended solids | < 10 ppm |
|
|
If your water is out of range, consult a water quality expert.
Water quality requirements 15