INSTALLATION INSTRUCTIONS |
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Figure 16 |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
| Temperature (°F) - Cooling Mode |
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| Rating Plate (required) |
|
| Rating Plate (required) |
|
| |||||||||
Measured Liquid | Subcooling Temperature (°F) | Measured Liquid | Subcooling Temperature (°F) |
| ||||||||||||
5 |
| 10 |
| 15 |
| 20 | 5 |
| 10 |
| 15 |
| 20 |
| ||
Pressure (psig) |
|
|
| Pressure (psig) |
|
|
|
| ||||||||
134 | 71 |
| 66 |
| 61 |
| 56 | 233 | 107 |
| 102 |
| 97 |
| 92 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
141 | 74 |
| 69 |
| 64 |
| 59 | 243 | 110 |
| 105 |
| 100 |
| 95 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
148 | 77 |
| 72 |
| 67 |
| 62 | 253 | 113 |
| 108 |
| 103 |
| 98 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
156 | 80 |
| 75 |
| 70 |
| 65 | 264 | 116 |
| 111 |
| 106 |
| 101 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
163 | 83 |
| 78 |
| 73 |
| 68 | 274 | 119 |
| 114 |
| 109 |
| 104 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
171 | 86 |
| 81 |
| 76 |
| 71 | 285 | 122 |
| 117 |
| 112 |
| 107 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
179 | 89 |
| 84 |
| 79 |
| 74 | 297 | 125 |
| 120 |
| 115 |
| 110 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
187 | 92 |
| 87 |
| 82 |
| 77 | 309 | 128 |
| 123 |
| 118 |
| 113 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
196 | 95 |
| 90 |
| 85 |
| 80 | 321 | 131 |
| 126 |
| 121 |
| 116 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
205 | 98 |
| 93 |
| 88 |
| 83 | 331 | 134 |
| 129 |
| 124 |
| 119 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
214 | 101 |
| 96 |
| 91 |
| 86 | 346 | 137 |
| 132 |
| 127 |
| 122 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
223 | 104 |
| 99 |
| 94 |
| 89 | 359 | 140 |
| 135 |
| 130 |
| 125 |
|
SEQUENCE OF OPERATION
A. COOLING MODE | B. HEATING MODE |
On a call for cooling, the thermostat makes circuits
When thermostat is satisfied, its contacts open,
NOTE: If indoor unit is equipped with a
NOTE: Low ambient cooling feature allows unit to operate safely in cooling mode down to 0° F outdoor ambient.
On a call for heating, the thermostat makes circuits
When the thermostat is satisfied, its contacts open,
506 01 5001 00 | 13 |