INSTALLATION INSTRUCTIONS
! CAUTION
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product damage.
Indoor coil and outdoor unit must be listed as a certified combination (match) in the ARI Unitary Directory of Certified Products.
Indoor coil must have
When installing a hard
A typical hard
Figure 3 | Typical TXV Installation |
|
|
INDOOR
COIL
EQUALIZER
TUBE
SENSING | SUCTION | |
TUBE | ||
BULB | ||
|
LIQUID
TUBE
HARD
TXV
SENSING BULB
(EITHER SIDE) | STRAP |
| |
| SUCTION |
| TUBE |
8 O'CLOCK | 4 O'CLOCK |
B. REFRIGERANT LINE SETS
The refrigerant line set must be properly sized to assure maximum efficiency and proper oil circulation. Select line set tube diameters as specified in Figure 4.
NOTE: If the line set actual length is to exceed 80 feet, or if there is more than 20 feet vertical separation between outdoor and indoor units, refer to the Long Line Application Guidline document for additional instructions.
NOTE: Line set actual length must not exceed 200 feet.
NOTE: A crankcase heater must be used when the refrigerant line length exceeds 80 feet.
If it is necessary to add refrigerant line in the field, use dehydrated or dry, sealed, deoxidized, copper refrigeration tubing. Do not use copper water pipe.
Do not remove rubber plugs or caps from copper tubing until connections are ready to be made.
Be extra careful when bending refrigeration tubing. Tubing can “kink” easily, and if this occurs, the entire length of tubing must be replaced.
! WARNING
PERSONAL INJURY HAZARD
Failure to follow this warning could result in per‐ sonal injury and/or death.
Relieve pressure and recover all refrigerant before servicing existing equipment, and before final unit disposal. Use all service ports and open all
!CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in improp‐ er product operation.
Do not leave system open to atmosphere any lon‐ ger than absolutely required for installation. Inter‐ nal system components - especially refrigerant oils - are extremely susceptible to moisture con‐ tamination. Keep ends of tubing sealed during installation until the last possible moment.
Figure 4 |
|
| |||
|
|
|
|
| |
| Service Valve Fittings | Line Set < 80 feet long | Line Set 80 - 200 feet long | ||
|
|
|
|
|
|
Model Size | Liquid |
| Suction | Suction Line Diameter | Suction Line Diameter |
36 (3 ton) | a” |
| w” | w” | d” |
|
|
|
|
|
|
42 (32 ton), 48 (4 ton) | a” |
| d” | d” | !8” |
|
|
|
|
|
|
60 (5 ton) | a” |
| d” | !8” | !8” |
NOTE: If the line set actual length is to exceed 80 feet, or if there is more than 20 feet vertical separation between outdoor and indoor units, refer to the Long Line Application Guideline document for additional instruc‐ tions.
506 01 5001 00 | 5 |