INSTALLATION INSTRUCTIONS |
| ||
|
|
|
|
|
|
|
|
Figure 19 |
| Comfort Alertt Diagnostics (some models) |
|
Miswired Module Indication |
| Troubleshooting Information |
|
Green LED is not on, module | Determine if both R and C module terminals are connected. Verify voltage is |
| |
does not power up | present at module's R and C terminals. |
| |
|
|
| |
Green LED intermittent, mod‐ | Determine if R and Y terminals are wired in reverse. Verify module's R and C |
| |
ule powers up only when com‐ | terminals have a constant source. |
| |
pressor runs |
|
|
|
|
|
| |
TRIP LED is on but system | Verify Y terminal is wired properly per OEM wiring diagram. Verify voltage at |
| |
and compressor check OK | contactor coil falls below 0.5VAC when off. Verify 24VAC is present across Y and |
| |
| C when thermostat demand signal is present. If not, R and C are reverse wired. |
| |
|
|
| |
TRIP LED and ALERT LED | Verify R and C terminals are supplied with |
| |
flashing together |
|
|
|
|
|
| |
ALERT Flash Code 3 | Verify Y terminal is connected to 24VAC at contactor coil. Verify voltage at |
| |
(Compressor short cycling) | contactor coil falls below 0.5VAC when off. |
| |
displayed incorrectly |
|
|
|
ALERT Flash Code 5 or 6 | Check that compressor T1 and T3 wires are through module's current sensing |
| |
(Open Circuit, Missing Phase) | holes. Verify Y terminal is connected to 24VAC at contactor coil. Verify voltage at |
| |
displayed incorrectly | contactor coil falls below 0.5VAC when off. |
| |
|
|
| |
ALERT Flash Code 8 | Determine if module's Y terminal is connected. Verify Y terminal is connected to |
| |
(Welded Contactor) displayed | 24VAC at contactor coil. Verify 24VAC is present across Y and C when |
| |
incorrectly | thermostat demand signal is present. If not, R and C are reversed wired. Verify |
| |
| voltage at contactor coil falls below 0.5VAC when off. Review. |
|
16 | International Comfort Products, LLC | 506 01 5001 00 | |