SPX Cooling Technologies 800 user manual Troubleshooting, Trouble Cause Remedy

Page 22

Troubleshooting

Trouble

Cause

Remedy

 

 

 

Motor Will Not Start

Power not available at motor terminals

1. Check power at starter. Correct any bad connections be-

 

 

tween the control apparatus and the motor.

 

 

2. Check starter contacts and control circuit. Reset overloads,

 

 

close contacts, reset tripped switches, or replace failed

 

 

control switches.

 

 

3. If power is not on all leads at starter make sure overload and

 

 

short circuit devices are in proper condition.

 

 

 

 

Wrong connections

Check motor and control connections against wiring diagrams.

 

 

 

 

Low voltage

Check nameplate voltage against power supply. Check voltage

 

 

at motor terminals.

 

 

 

 

Open circuit in motor winding

Check stator windings for open circuits.

 

 

 

 

Motor or fan drive stuck

Disconnect motor from load and check motor and Geareducer

 

 

for cause of problem.

 

 

 

 

Rotor defective

Look for broken bars or rings.

 

 

 

Unusual Motor Noise

Motor running single-phase

Stop motor and attempt to start it. Motor will not start if single-

 

 

phased. Check wiring, controls, and motor.

 

 

 

 

Motor leads connected incorrectly

Check motor connections against wiring diagram on motor.

 

 

 

 

Ball bearings

Check lubrication. Replace bad bearings.

 

 

 

 

Electrical unbalance

Check voltages and currents of all three lines. Correct if re-

 

 

quired.

 

 

 

 

Air gap not uniform

Check and correct bracket fits or bearing.

 

 

 

 

Rotor unbalance

Rebalance.

 

 

 

 

Cooling fan hitting guard

Reinstall or replace fan.

 

 

 

Motor Runs Hot

Wrong voltage or unbalanced voltage

Check voltage and current of all three lines against nameplate

 

 

values.

 

 

 

 

Overload

Check fan blade pitch. See Fan Service Manual. Check for

 

 

drag in fan drive train as from damaged bearings.

 

 

 

 

Wrong motor RPM

Check nameplate against power supply. Check RPM of motor

 

 

and gear ratio.

 

 

 

 

Bearings over-greased

Remove grease reliefs. Run motor up to speed to purge exces-

 

 

sive grease.

 

 

 

 

Rotor rubs stator bore

If not poor machining, replace worn bearing.

 

 

 

 

Wrong lubricant in bearings

Change to proper lubricant. See motor manufacturer’s instruc-

 

 

tions.

 

 

 

 

One phase open

Stop motor and attempt to start it. Motor will not start if single-

 

 

phased. Check wiring, controls, and motor.

 

 

 

 

Poor ventilation

Clean motor and check ventilation openings. Allow ample venti-

 

 

lation around motor.

 

 

 

 

Winding fault

Check with Ohmmeter

 

 

 

 

Bent motor shaft

Straighten or replace shaft.

 

 

 

 

Insufficient grease

Remove plugs and re-grease bearings.

 

 

 

 

Deterioration of or foreign material in

Flush bearings and relubricate.

 

grease

 

 

 

 

 

Bearings damaged

Replace bearings.

 

 

 

Motor Does Not Come Up

Incorrect fan blade pitch

See Fan Service Manual for blade pitching instructions.

 

 

 

To Speed

Voltage too low at motor terminals be-

Check transformer and setting of taps. Use higher voltage on

 

cause of line drop

transformer terminals or reduce loads. Increase wire size or

 

 

reduce inertia.

 

 

 

 

Broken rotor bars

Look for cracks near the rings. A new rotor may be required.

 

 

Have motor service man check motor.

22

Image 22
Contents Marley Class 800 Mechanical Draft Cooling Tower Page Contents General Before Start-up SafetyCleaning InspectionOperate Water System Initial Starting Procedure Routine Starting Procedure Tower Performance OperationFan Drive Drift Eliminators Hot Water Distribution SystemFill Cold Water Collection BasinFreezing Weather Operation DeicingIntermittent Operation Maximizing Tower Performance Temperature Control and Energy ManagementMinimizing Tower Energy Use Temperature Control and Energy Management Maintenance AccessTower Framework Cleaning Blowdown Water TreatmentChemical Treatment Scaling FoamingMechanical Equipment Seasonal Shutdown InstructionsTower Electric MotorsAccessories Spare Parts and AccessoriesSpare Parts Troubleshooting Trouble Cause RemedyManual Safety Inspection and Maintenance Schedule General RecommendationsInspection Checklist GPMRPM Cooling Technologies

800 specifications

SPX Cooling Technologies 800 is a highly advanced cooling tower designed for commercial and industrial applications. This state-of-the-art equipment is recognized for its efficiency, reliability, and robust construction. The 800 model is engineered to meet the demanding needs of modern cooling processes, ensuring optimal performance in various settings.

One of the main features of the SPX Cooling Technologies 800 is its innovative design which contributes to superior heat transfer capabilities. The large surface area of the cooling fill maximizes the interaction between air and water, enhancing cooling efficiency while reducing operational costs. This design also supports effective thermal performance with lower water consumption, making it an environmentally friendly option for businesses.

The unit's fan technology is another standout characteristic. The SPX Cooling Technologies 800 employs low-noise, high-efficiency axial fans that optimize airflow while minimizing sound levels. This consideration for noise reduction makes it ideal for installation in noise-sensitive environments without compromising on performance.

Moreover, the 800 model incorporates a corrosion-resistant casing, fabricated from high-quality materials like fiberglass-reinforced plastic. This durability ensures a long service life and reduces the need for frequent maintenance, which in turn lowers operating costs. The design also allows for easy access to internal components, streamlining servicing and inspection processes.

SPX Cooling Technologies has also integrated advanced automation features into the 800 unit. With intelligent control systems, operators can easily monitor and adjust performance parameters remotely. This capability enhances operational efficiency and allows for predictive maintenance, ultimately extending the equipment's lifespan.

This model is suitable for a variety of applications, including industrial manufacturing, commercial HVAC systems, and process cooling. The flexible design options and customizable configurations allow it to meet specific site requirements, ensuring compatibility with existing infrastructure.

In summary, the SPX Cooling Technologies 800 stands out in the market for its combination of high performance, durability, and efficiency. With features such as advanced fan technology, corrosion-resistant materials, and intelligent automation, it offers a comprehensive solution for modern cooling needs, catering to a diverse range of industries while promoting sustainability and cost-effectiveness.