Toshiba Understanding RAV Error Codes and Panasonic P05 Fault Troubleshooting

Page 45

Error mode detected by outdoor unit

The indoor unit check code has been ramified from 4 series and after.

The ramified check code is displayed only when combined with 4-series indoor unit. (Ex. Combination of RAV-SM1404UT-E with RAV-SM1403AT-E1)

When the indoor unit is 3 series and before, the conventional check code is displayed. (Ex. Combination of RAV-SM1402CT-E and RAV-SM1403AT-E1)

 

 

Operation of diagnostic function

 

 

 

 

 

 

 

 

 

Checkcode

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

Cause of operation

Status of

Condition

 

Judgment and measures

 

 

air conditioner

 

 

before

after

 

 

 

 

 

 

 

 

 

3 series

4 series

 

 

 

 

 

 

 

 

 

 

 

 

F04

F04

Disconnection, short of discharge

Stop

Displayed when

1.

Check discharge temp. sensor (TD).

temp. sensor (TD)

error is detected

2.

Check outdoor P.C. board

 

 

 

 

 

 

 

 

 

 

 

F06

Disconnection, short of outdoor temp.

Stop

Displayed when

1.

Check temp. sensor (TE).

 

sensor (TE)

error is detected

2.

Check outdoor P.C. board .

 

 

 

 

 

 

 

 

 

 

 

F07

Disconnection, short of outdoor temp.

Stop

Displayed when

1.

Check temp. sensor (TL).

 

sensor (TL)

error is detected

2.

Check outdoor P.C. board .

 

 

 

F06

 

 

 

 

 

 

F12

Disconnection, short of suction temp.

Stop

Displayed when

1.

Check suction temp. sensor (TS).

 

 

sensor (TS)

error is detected

2.

Check outdoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

F15

Miss-mounting of outdoor temp.

Stop

Displayed when

1.

Check temp. sensor (TE, TS).

 

sensor (TE, TS)

error is detected

2.

Check outdoor P.C. board.

 

 

 

 

 

 

 

 

 

 

F08

F08

Disconnection, short of outside temp.

Continue

Displayed when

1.

Check outside temp. sensor (TO).

sensor (TO)

error is detected

2.

Check outdoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

F13

Disconnection, short of heat sink

Stop

Displayed when

1.

Check outdoor P.C. board

 

temp. sensor (TH)

error is detected

 

(IC200 is incorporated in TH sensor.)

 

 

 

 

 

 

 

 

 

 

 

 

F31

Outdoor P.C. EEPROM error

Stop

Displayed when

1.

Check outdoor P.C. board.

 

error is detected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L10

Unset jumper of service P.C. board

Stop

Displayed when

1.

Outdoor service P.C. board.

 

error is detected

 

Check model type setting jumper wire.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat sink overheat error

 

Displayed when

1.

Check screw tightening between P.C.Board and heat

 

P07

Heat sink temp. sensor detected

Stop

 

sink and check radiator grease.

L29

error is detected

 

 

over specified temperature.

 

2.

Check heat sink blast path.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Check gas leak, recharge

 

 

Detection of gas leak

 

 

2.

Check full open of service valve.

 

P15

Discharge temp. sensor (TD),

Stop

Displayed when

3.

Check PMV (Pulse Motor Valve).

 

Suction temp. sensor (TS) detected

error is detected

4.

Check broken pipe.

 

 

 

 

 

temperature over specified temp.

 

 

 

 

 

 

5.

Check discharge temp. sensor (TD), suction temp.

 

 

 

 

 

 

 

 

 

 

 

sensor (TS).

 

 

 

 

 

 

 

 

 

4-way valve inverse error

 

 

1.

Check operation of 4-way valve.

 

 

After heating operation has started,

 

 

2.

Check outdoor heat exchanger (TE), suction temp.

 

 

indoor heat exchanger temp. lowers

 

Displayed when

 

sensor (TS).

 

P19

under the specified temp.

Stop

 

 

 

error is detected

3.

Check indoor heat exchanger sensor (TC).

 

 

After heating operation has started,

 

 

 

 

 

4.

Check 4-way valve coil.

 

 

outdoor heat exchanger / suction

 

 

 

 

 

 

5.

Check PMV (Pulse Motor Valve).

 

 

temp. rises over the specified temp.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor break down

 

 

1.

Check power supply voltage. (AC198 to 264V)

H01

H01

Although operation has started,

Stop

Displayed when

2.

Overload operation of refrigerating cycle

operation frequency decreases and

error is detected

 

 

 

 

 

 

 

 

 

operation stops.

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor lock

 

Displayed when

1.

Trouble of compressor (Lock, etc.): Replace compres-

H02

H02

* Over-current detection after

Stop

 

sor.

error is detected

 

 

 

compressor start-up

 

2.

Wiring error of compressor (Open phase)

 

 

 

 

 

 

 

 

 

 

 

– 45 –

Image 45
Contents RAV-SM1103AT-E1 RAV-SM1403AT-E1 Contents Original instruction Explanation of illustrated marks Explanation of indicationsWork undertaken Protective gear worn Indication ExplanationDescription Confirmation of warning label on the main unitPrecaution for Safety Undertake the work Refrigerant used by this air conditioner is the R410A Properly Relocation Explanations given to userModel names with a rating of 12 kW and below outdoor units DI seriesPipe Materials Safety Caution Concerned to New RefrigerantCopper pipe Piping Flare nutGeneral tools Conventional tools can be used ToolsDigital Inverter Outdoor UnitCapacity variation ratio according to temperature Operation Characteristic CurveOperation Characteristic Curve Digital Inverter Cooling HeatingRAV-SM1103AT-E1, RAV-SM1403AT-E1 Construction Views External ViewsModel RBC RBC-TWP30E2, RBC-TWP50E2 Simultaneous TwinOutdoor unit RAV-SM1103AT-E1 Wiring Diagram Specifications of Electric Parts Refrigerant Piping Installation Safety During Installation/ServicingPiping Materials and Joints Used Copper PipesFlare Processing Procedures and Precautions JointsProcessing of Piping Materials Flare and flare nut dimensions for R410A 3 Dimensions related to flare processing for R410A / R22Flare and flare nut dimensions for R22 R410A R22 R410A, R22 Clutch type Wing nut typeFlare Connecting Procedures and Precautions Nm kgfmWrenches available on the market Required Tools Recharging of RefrigerantFlux Reason why flux is necessary Low temperature brazing fillerBrazing of Pipes Materials for Brazing Silver brazing fillerTypes of flux Characteristics required for fluxPiping materials for brazing and used brazing filler/flux BrazingBasic Conditions Needed to Reuse the Existing Pipe Instructions for Re-use Piping of R22 or R407CRestricted Items to Use the Existing Pipes Branching Pipe for Simultaneous Operation SystemYES Final Installation ChecksReference outside diameter Wall thickness Handling of Existing PipeCN806 Outline of Main Controls Pulse Modulating Valve PMV control Discharge temperature release controlOutdoor fan control Current release controlCooling fan control Allocations of fan tap revolutions rpmHeating fan control Coil heating controlNormal time Defective to sensorCurrent release value shift control Defrost controlCurrent release control value At normal to At error to Zone High-pressure switchControl of compressor case thermo Start of heating operationBefore troubleshooting Summary of TroubleshootingTroubleshooting procedure Wired remote controller typeTrouble Confirmation of lamp display Wireless remote controller typeOutline of judgment TroubleshootingLamp indication Check code Cause of trouble occurrence Others Other than Check CodePushing Test button returns the status to the usual display ContentsIndication Check Code List OutdoorCentral control indication Remote controller TCJ Error mode detected by indoor unitAfter Error mode detected by outdoor unitAfter Series Operation of diagnostic function Judgment and measures Contents Error Display Display of the latest error Diagnostic Procedure for Each Check Code Outdoor UnitYES Case thermostat operation E04F06 Heat exchanger temp. sensor TE errorF12 Suction temp. sensor TS error F13 Heat sink temp. sensor TH errorF15 Miswiring of heat exchanger sensor TE, TS H02 Compressor lock H01 Compressor break downL10 P03 Discharge temp. errorPower supply error Vdc, High pressure protective operation High pressure SW system errorP15 Gas leak detection P07 Heat sink overheat errorWay valve reversal error Check Code P19 Outdoor Check and troubleshooting LED displayOpen valve fully Single operation check for outdoor fan MethodPosition detection circuit error TA, TC, TCJ, TE, TS, to sensors Representative value Temperature sensorTD, TL sensors Representative value TA, TC, TCJ, TE, TS, to sensorsTable Inspection of outdoor unit main parts Parts name Checking procedureResistance value PositionContents Calling of Error HistoryProcedure Group Control OperationBy feed unit Automatic address judgment „ Indoor unit power-ON sequenceInitial communication Usual regular CommunicationService switch SW800, SW801 operations Refrigerant recovery controlOutdoor Unit Service switch setting Case to return the setting to one at shipment from factory LED display switching Display switching list Error display ON, OFF, Slow flashing Once/second Open PMV Electronic expansion valve fully Applicable Control of Outdoor unit Address Setup Procedure Address SetupAddress Setup & Group Control System ConfigurationTerminology Only turning on source power supply Automatic completion Automatic Address Example from Unset Address No miswiringStandard One outdoor unit Single Twin Wiring diagram Remote Controller WiringAddress Setup Manual setting from remote controller Single system Simultaneous twin systemButton Confirmation of Indoor Unit No. PositionTo know the position of indoor unit body by address Maintenance/Check listSetting the jumper wires Installing the P.C. boardRemoving the P.C. board Exchange of Compressor Exchanging Procedure of Compressor OutlineDetachments Discharge port Part name Procedure Remarks Perform works of 1 of c, 2 of f Propeller fan When reconnecting the lead wires to Pulse Modulating Product Exploded Views and Parts List RAV Inverter assembly Toshiba Carrier Corporation

RAV-SM1403AT-E1 specifications

The Toshiba RAV-SM1403AT-E1 is a state-of-the-art air conditioning system designed for residential and commercial applications. Its advanced features and cutting-edge technology ensure optimal cooling and heating performance, making it a popular choice among consumers and businesses alike.

One of the standout characteristics of the RAV-SM1403AT-E1 is its energy efficiency. This model is equipped with a highly efficient inverter compressor that adjusts its output based on the cooling load required, which results in significant energy savings compared to traditional air conditioning systems. Its impressive Seasonal Energy Efficiency Ratio (SEER) ratings highlight its ability to provide effective climate control while minimizing electricity consumption.

The RAV-SM1403AT-E1 utilizes Toshiba’s innovative DC inverter technology, which allows for smoother and quieter operation. This means that users can enjoy a comfortable indoor environment without the disruptive noise often associated with conventional models. In addition to its quiet operation, this air conditioner also features an advanced air filtration system that helps to maintain indoor air quality by removing dust, allergens, and other pollutants.

Another major feature of this system is its versatility in installation. The RAV-SM1403AT-E1 can be installed in various configurations, allowing it to adapt to different spaces and design requirements. It supports multiple indoor units that can be connected to a single outdoor unit, providing flexibility for cooling or heating multiple areas simultaneously.

Smart technology is also integrated into the RAV-SM1403AT-E1. Users can take advantage of remote control options, including Wi-Fi capabilities that allow for convenient management of the air conditioning system via smartphones or tablets. This level of control ensures that users can adjust settings even when they are not present, increasing comfort and efficiency.

The build quality of the Toshiba RAV-SM1403AT-E1 reflects its durability and reliability. Designed to withstand varying environmental conditions, it includes corrosion-resistant features that extend the lifespan of the unit, making it a practical investment for both home and commercial use.

In summary, the Toshiba RAV-SM1403AT-E1 combines energy efficiency, advanced technology, and flexible installation options, making it an excellent choice for those seeking a high-performance air conditioning solution. With its innovative features and commitment to sustainability, this model stands out in the competitive HVAC market.