9-3. Outdoor Unit

Various displays and various operations are enabled by push buttons (service) switches and LED on the outdoor control P.C. board.

Service switch (SW800, SW801) operations

LED display

4 patterns are provided for LED display.

: ON, : OFF, : Rapid flashing (5 times/second), : Slow flashing (Once/second)

In the initial status of LED display, D805 is ON as the right figure.

When the initial status does not appear (in case of flashing of D805), LED display can be returned to the initial status by pushing and holding the service switches SW800 and SW801 for 5 seconds or more simultaneously.

D800

D801

D802

D803

D804

D805

LED display: Initial status

LED

(Yellow) OFF or rapid flashing

(Yellow) OFF or rapid flashing

(Yellow) OFF or rapid flashing

(Yellow) OFF or rapid flashing (Yellow) OFF or rapid flashing (Green) ON

9-3-1. Refrigerant recovery control

HFC refrigerant is “Ozone layer destructive coefficient = 0”. However the discharge regulation is established for HFC refrigerant as it is greenhouse gas.

For this Model, a switch is mounted for refrigerant recovery operation (pump down) by the outdoor unit so that this Model can easily react to the environment when it will be reinstalled or scrapped.

[Operating method]

1)Set fan operation to the indoor unit.

2)Check LED display is the initial status. If it is not so, set the initial status.

3)Push and hold SW800 for 5 seconds or more and then check D804 flashes slowly.

4)Push SW800 several times and then stop it at the point where LED display (D800 to D804) is indicated as the following table.

D800

D801

D802

D803

D804

 

 

 

 

 

: ON, : OFF, : Rapid flashing (5 times/second)

5)Push SW801 so that D805 flashes rapidly.

6)Push and hold SW801 for 5 seconds or more. The forced cooling operation starts if D804 flashes slowly and D805 is turned on. (Max. 10 minutes)

7)After operation for 3 minutes or more, close the valve at liquid side.

8)After recovery of refrigerant, close the valve at gas side.

9)Push and hold SW800 and SW801 for 5 seconds or more simultaneously. The LED returns to the initial status, the cooling operation stops and the indoor fan operation stops.

10)Turn off the power supply.

*If an unknown point generated on the way of the operation, push and hold SW800 and SW801 for 5 seconds or more simultaneously. You can return to the item 2).

– 65 –

Image 65
Contents RAV-SM1103AT-E1 RAV-SM1403AT-E1 Contents Original instruction Explanation of illustrated marks Explanation of indicationsWork undertaken Protective gear worn Indication ExplanationDescription Confirmation of warning label on the main unitPrecaution for Safety Undertake the work Refrigerant used by this air conditioner is the R410A Properly Relocation Explanations given to userModel names with a rating of 12 kW and below outdoor units DI seriesPipe Materials Safety Caution Concerned to New RefrigerantCopper pipe Piping Flare nutGeneral tools Conventional tools can be used ToolsDigital Inverter Outdoor UnitCapacity variation ratio according to temperature Operation Characteristic CurveOperation Characteristic Curve Digital Inverter Cooling HeatingRAV-SM1103AT-E1, RAV-SM1403AT-E1 Construction Views External ViewsModel RBC RBC-TWP30E2, RBC-TWP50E2 Simultaneous TwinOutdoor unit RAV-SM1103AT-E1 Wiring Diagram Specifications of Electric Parts Refrigerant Piping Installation Safety During Installation/ServicingPiping Materials and Joints Used Copper PipesProcessing of Piping Materials Flare Processing Procedures and PrecautionsJoints Flare and flare nut dimensions for R410A 3 Dimensions related to flare processing for R410A / R22Flare and flare nut dimensions for R22 R410A R22 R410A, R22 Clutch type Wing nut typeWrenches available on the market Flare Connecting Procedures and PrecautionsNm kgfm Required Tools Recharging of RefrigerantFlux Reason why flux is necessary Low temperature brazing fillerBrazing of Pipes Materials for Brazing Silver brazing fillerTypes of flux Characteristics required for fluxPiping materials for brazing and used brazing filler/flux BrazingBasic Conditions Needed to Reuse the Existing Pipe Instructions for Re-use Piping of R22 or R407CRestricted Items to Use the Existing Pipes Branching Pipe for Simultaneous Operation SystemYES Final Installation ChecksReference outside diameter Wall thickness Handling of Existing PipeCN806 Outline of Main Controls Pulse Modulating Valve PMV control Discharge temperature release controlOutdoor fan control Current release controlCooling fan control Allocations of fan tap revolutions rpmHeating fan control Coil heating controlNormal time Defective to sensorCurrent release control value Current release value shift controlDefrost control At normal to At error to Zone High-pressure switchControl of compressor case thermo Start of heating operationBefore troubleshooting Summary of TroubleshootingTroubleshooting procedure Wired remote controller typeTrouble Confirmation of lamp display Wireless remote controller typeOutline of judgment TroubleshootingLamp indication Check code Cause of trouble occurrence Others Other than Check CodePushing Test button returns the status to the usual display ContentsIndication Check Code List OutdoorCentral control indication Remote controller TCJ Error mode detected by indoor unitAfter Error mode detected by outdoor unitAfter Series Operation of diagnostic function Judgment and measures Contents Error Display Display of the latest error Diagnostic Procedure for Each Check Code Outdoor UnitYES Case thermostat operation E04F06 Heat exchanger temp. sensor TE errorF15 Miswiring of heat exchanger sensor TE, TS F12 Suction temp. sensor TS errorF13 Heat sink temp. sensor TH error H02 Compressor lock H01 Compressor break downL10 P03 Discharge temp. errorPower supply error Vdc, High pressure protective operation High pressure SW system errorP15 Gas leak detection P07 Heat sink overheat errorWay valve reversal error Check Code P19 Outdoor Check and troubleshooting LED displayOpen valve fully Single operation check for outdoor fan MethodPosition detection circuit error TA, TC, TCJ, TE, TS, to sensors Representative value Temperature sensorTD, TL sensors Representative value TA, TC, TCJ, TE, TS, to sensorsTable Inspection of outdoor unit main parts Parts name Checking procedureResistance value PositionContents Calling of Error HistoryProcedure Group Control OperationBy feed unit Automatic address judgment „ Indoor unit power-ON sequenceInitial communication Usual regular CommunicationOutdoor Unit Service switch SW800, SW801 operationsRefrigerant recovery control Service switch setting Case to return the setting to one at shipment from factory LED display switching Display switching list Error display ON, OFF, Slow flashing Once/second Open PMV Electronic expansion valve fully Applicable Control of Outdoor unit Address Setup Procedure Address SetupTerminology Address Setup & Group ControlSystem Configuration Only turning on source power supply Automatic completion Automatic Address Example from Unset Address No miswiringStandard One outdoor unit Single Twin Wiring diagram Remote Controller WiringAddress Setup Manual setting from remote controller Single system Simultaneous twin systemButton Confirmation of Indoor Unit No. PositionTo know the position of indoor unit body by address Maintenance/Check listRemoving the P.C. board Setting the jumper wiresInstalling the P.C. board Exchange of Compressor Exchanging Procedure of Compressor OutlineDetachments Discharge port Part name Procedure Remarks Perform works of 1 of c, 2 of f Propeller fan When reconnecting the lead wires to Pulse Modulating Product Exploded Views and Parts List RAV Inverter assembly Toshiba Carrier Corporation

RAV-SM1403AT-E1 specifications

The Toshiba RAV-SM1403AT-E1 is a state-of-the-art air conditioning system designed for residential and commercial applications. Its advanced features and cutting-edge technology ensure optimal cooling and heating performance, making it a popular choice among consumers and businesses alike.

One of the standout characteristics of the RAV-SM1403AT-E1 is its energy efficiency. This model is equipped with a highly efficient inverter compressor that adjusts its output based on the cooling load required, which results in significant energy savings compared to traditional air conditioning systems. Its impressive Seasonal Energy Efficiency Ratio (SEER) ratings highlight its ability to provide effective climate control while minimizing electricity consumption.

The RAV-SM1403AT-E1 utilizes Toshiba’s innovative DC inverter technology, which allows for smoother and quieter operation. This means that users can enjoy a comfortable indoor environment without the disruptive noise often associated with conventional models. In addition to its quiet operation, this air conditioner also features an advanced air filtration system that helps to maintain indoor air quality by removing dust, allergens, and other pollutants.

Another major feature of this system is its versatility in installation. The RAV-SM1403AT-E1 can be installed in various configurations, allowing it to adapt to different spaces and design requirements. It supports multiple indoor units that can be connected to a single outdoor unit, providing flexibility for cooling or heating multiple areas simultaneously.

Smart technology is also integrated into the RAV-SM1403AT-E1. Users can take advantage of remote control options, including Wi-Fi capabilities that allow for convenient management of the air conditioning system via smartphones or tablets. This level of control ensures that users can adjust settings even when they are not present, increasing comfort and efficiency.

The build quality of the Toshiba RAV-SM1403AT-E1 reflects its durability and reliability. Designed to withstand varying environmental conditions, it includes corrosion-resistant features that extend the lifespan of the unit, making it a practical investment for both home and commercial use.

In summary, the Toshiba RAV-SM1403AT-E1 combines energy efficiency, advanced technology, and flexible installation options, making it an excellent choice for those seeking a high-performance air conditioning solution. With its innovative features and commitment to sustainability, this model stands out in the competitive HVAC market.