Toshiba RAV-SM1403AT-E1 service manual Operation of diagnostic function Judgment and measures

Page 47

Error mode detected by remote controller or central controller (TCC-LINK)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation of diagnostic function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Judgment and measures

 

 

 

Check code

 

Cause of operation

Status of

Condition

 

 

 

 

 

 

 

 

 

 

 

air conditioner

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply error of remote controller, Indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EEPROM error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Check remote controller inter-unit wiring.

 

Not displayed at all

 

No communication with master indoor unit

 

 

2.

Check remote controller.

 

 

• Remote controller wiring is not correct.

 

 

 

 

 

(Operation on

 

Stop

3.

Check indoor power wiring.

 

remote controller is

 

• Power of indoor unit is not turned on.

4.

Check indoor P.C. board.

 

 

 

 

 

impossible.)

 

• Automatic address cannot be completed.

 

 

5.

Check indoor EEPROM.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(including socket insertion)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Automatic address repeating phenom-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

enon generates.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No communication with master indoor unit

Stop

 

Receiving error from remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Check remote controller inter-unit wiring.

 

 

 

 

 

 

E01

 

• Disconnection of inter-unit wire between

(Automatic reset)

Displayed when

 

 

 

 

 

 

 

2.

Check remote controller.

 

 

 

 

 

 

2

 

remote controller and master indoor unit

If center exists,

error is detected

 

 

 

 

 

 

 

3.

Check indoor power wiring.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Detected by remote controller side)

operation continues.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.

Check indoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop

 

Sending error of remote controller

 

 

 

 

 

 

E02

 

Signal send error to indoor unit

(Automatic reset)

Displayed when

1. Check sending circuit inside of remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Detected by remote controller side)

If center exists,

error is detected

 

controller.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation continues.

 

 

Replace remote controller.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop

 

1.

In 2-remote controllers (including wireless),

 

 

 

 

 

 

E09

 

There are multiple main remote controllers.

Displayed when

 

there are multiple main units.

 

 

 

 

 

 

 

(Detected by remote controller side)

(Sub unit

error is detected

 

Check that there are 1 main remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

continues operation.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

controller and other sub remote controllers.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L20

 

Duplicated indoor central addresses on

Stop

Displayed when

1.

Check setting of central control system

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

network address. (Network adapter SW01)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Central controller

 

communication of central control system

(Automatic reset)

error is detected

2.

Check network adapter P.C. board.

 

 

(Detected by indoor/central controller side)

 

 

 

 

 

 

 

 

L20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Check communication wire / miswiring

 

 

 

 

 

 

3

 

 

 

 

2.

Check communication (U3, U4 terminals)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Communication circuit error of central

Continues

Displayed when

3.

Check network adapter P.C. board.

 

Central controller

 

 

 

control system

4. Check central controller (such as central

 

 

 

 

 

(Send)

 

(By remote controller)

error is detected

 

 

 

 

 

 

(Detected by central controller side)

 

 

 

 

 

 

C05

 

 

 

 

control remote controller, etc.)

 

 

 

 

 

 

 

 

 

 

5.

Check terminal resistance. (TCC-LINK)

 

 

 

 

(Receive)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C06

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Gr sub unit error

Continuation/Stop

Displayed when

Check the check code of the corresponding

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(According

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Central controller

 

(Detected by central controller side)

error is detected

unit from remote controller.

 

 

to each case)

 

 

 

 

 

 

P30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 The check code cannot be displayed by the wired remote controller. (Usual operation of air conditioner becomes unavailable.)

For the wireless models, an error is notified with indication lamp.

3 This trouble is related to communication of remote controller (A, B), central system (TCC-LINK U3, U4), and [E01], [E02], [E03], [E09] or [E18] is displayed or no check display on the remote controller according to the contents.

– 47 –

Image 47
Contents RAV-SM1103AT-E1 RAV-SM1403AT-E1 Contents Original instruction Indication Explanation Explanation of indicationsExplanation of illustrated marks Work undertaken Protective gear wornDescription Confirmation of warning label on the main unitPrecaution for Safety Undertake the work Refrigerant used by this air conditioner is the R410A Properly DI series Explanations given to userRelocation Model names with a rating of 12 kW and below outdoor unitsFlare nut Safety Caution Concerned to New RefrigerantPipe Materials Copper pipe PipingGeneral tools Conventional tools can be used ToolsDigital Inverter Outdoor UnitCooling Heating Operation Characteristic CurveCapacity variation ratio according to temperature Operation Characteristic Curve Digital InverterRAV-SM1103AT-E1, RAV-SM1403AT-E1 Construction Views External ViewsModel RBC RBC-TWP30E2, RBC-TWP50E2 Simultaneous TwinOutdoor unit RAV-SM1103AT-E1 Wiring Diagram Specifications of Electric Parts Copper Pipes Safety During Installation/ServicingRefrigerant Piping Installation Piping Materials and Joints UsedProcessing of Piping Materials Flare Processing Procedures and PrecautionsJoints R410A R22 R410A, R22 Clutch type Wing nut type 3 Dimensions related to flare processing for R410A / R22Flare and flare nut dimensions for R410A Flare and flare nut dimensions for R22Wrenches available on the market Flare Connecting Procedures and PrecautionsNm kgfm Required Tools Recharging of RefrigerantMaterials for Brazing Silver brazing filler Low temperature brazing fillerFlux Reason why flux is necessary Brazing of PipesBrazing Characteristics required for fluxTypes of flux Piping materials for brazing and used brazing filler/fluxBranching Pipe for Simultaneous Operation System Instructions for Re-use Piping of R22 or R407CBasic Conditions Needed to Reuse the Existing Pipe Restricted Items to Use the Existing PipesYES Final Installation ChecksReference outside diameter Wall thickness Handling of Existing PipeCN806 Outline of Main Controls Pulse Modulating Valve PMV control Discharge temperature release controlAllocations of fan tap revolutions rpm Current release controlOutdoor fan control Cooling fan controlDefective to sensor Coil heating controlHeating fan control Normal timeCurrent release control value Current release value shift controlDefrost control Start of heating operation High-pressure switchAt normal to At error to Zone Control of compressor case thermoWired remote controller type Summary of TroubleshootingBefore troubleshooting Troubleshooting procedureTrouble Confirmation of lamp display Wireless remote controller typeOutline of judgment TroubleshootingLamp indication Check code Cause of trouble occurrence Others Other than Check CodePushing Test button returns the status to the usual display ContentsIndication Check Code List OutdoorCentral control indication Remote controller TCJ Error mode detected by indoor unitAfter Error mode detected by outdoor unitAfter Series Operation of diagnostic function Judgment and measures Contents Error Display Display of the latest error Diagnostic Procedure for Each Check Code Outdoor UnitYES Case thermostat operation E04F06 Heat exchanger temp. sensor TE errorF15 Miswiring of heat exchanger sensor TE, TS F12 Suction temp. sensor TS errorF13 Heat sink temp. sensor TH error H02 Compressor lock H01 Compressor break downL10 P03 Discharge temp. errorPower supply error Vdc, High pressure protective operation High pressure SW system errorP15 Gas leak detection P07 Heat sink overheat errorWay valve reversal error Check Code P19 Outdoor Check and troubleshooting LED displayOpen valve fully Single operation check for outdoor fan MethodPosition detection circuit error TA, TC, TCJ, TE, TS, to sensors Temperature sensorTA, TC, TCJ, TE, TS, to sensors Representative value TD, TL sensors Representative valuePosition Parts name Checking procedureTable Inspection of outdoor unit main parts Resistance valueGroup Control Operation Calling of Error HistoryContents ProcedureUsual regular Communication „ Indoor unit power-ON sequenceBy feed unit Automatic address judgment Initial communicationOutdoor Unit Service switch SW800, SW801 operationsRefrigerant recovery control Service switch setting Case to return the setting to one at shipment from factory LED display switching Display switching list Error display ON, OFF, Slow flashing Once/second Open PMV Electronic expansion valve fully Applicable Control of Outdoor unit Address Setup Procedure Address SetupTerminology Address Setup & Group ControlSystem Configuration Only turning on source power supply Automatic completion Automatic Address Example from Unset Address No miswiringStandard One outdoor unit Single Twin Single system Simultaneous twin system Remote Controller WiringWiring diagram Address Setup Manual setting from remote controllerButton Confirmation of Indoor Unit No. PositionTo know the position of indoor unit body by address Maintenance/Check listRemoving the P.C. board Setting the jumper wiresInstalling the P.C. board Exchange of Compressor Exchanging Procedure of Compressor OutlineDetachments Discharge port Part name Procedure Remarks Perform works of 1 of c, 2 of f Propeller fan When reconnecting the lead wires to Pulse Modulating Product Exploded Views and Parts List RAV Inverter assembly Toshiba Carrier Corporation

RAV-SM1403AT-E1 specifications

The Toshiba RAV-SM1403AT-E1 is a state-of-the-art air conditioning system designed for residential and commercial applications. Its advanced features and cutting-edge technology ensure optimal cooling and heating performance, making it a popular choice among consumers and businesses alike.

One of the standout characteristics of the RAV-SM1403AT-E1 is its energy efficiency. This model is equipped with a highly efficient inverter compressor that adjusts its output based on the cooling load required, which results in significant energy savings compared to traditional air conditioning systems. Its impressive Seasonal Energy Efficiency Ratio (SEER) ratings highlight its ability to provide effective climate control while minimizing electricity consumption.

The RAV-SM1403AT-E1 utilizes Toshiba’s innovative DC inverter technology, which allows for smoother and quieter operation. This means that users can enjoy a comfortable indoor environment without the disruptive noise often associated with conventional models. In addition to its quiet operation, this air conditioner also features an advanced air filtration system that helps to maintain indoor air quality by removing dust, allergens, and other pollutants.

Another major feature of this system is its versatility in installation. The RAV-SM1403AT-E1 can be installed in various configurations, allowing it to adapt to different spaces and design requirements. It supports multiple indoor units that can be connected to a single outdoor unit, providing flexibility for cooling or heating multiple areas simultaneously.

Smart technology is also integrated into the RAV-SM1403AT-E1. Users can take advantage of remote control options, including Wi-Fi capabilities that allow for convenient management of the air conditioning system via smartphones or tablets. This level of control ensures that users can adjust settings even when they are not present, increasing comfort and efficiency.

The build quality of the Toshiba RAV-SM1403AT-E1 reflects its durability and reliability. Designed to withstand varying environmental conditions, it includes corrosion-resistant features that extend the lifespan of the unit, making it a practical investment for both home and commercial use.

In summary, the Toshiba RAV-SM1403AT-E1 combines energy efficiency, advanced technology, and flexible installation options, making it an excellent choice for those seeking a high-performance air conditioning solution. With its innovative features and commitment to sustainability, this model stands out in the competitive HVAC market.