INSTALLATION MANUAL To Personnel Charged in Installation (Electric) Work and Service

Program Weekly Timer

MODEL : RBC-EXW21E

Accessory parts

Part Name

Q’ty

Program weekly timer

1

 

Connecting cable

1

(Length: 1.2m)

How to install the program weekly timer

NOTE 1 :

Avoid to twist the program weekly timer cable with the power supply cable, etc. or to store them in the same metal pipe, otherwise it causes a malfunction.

NOTE 2 :

Cabling

Connection diagram

(Be sure to use the attached connecting cable.)

Timer terminal Timer terminal

1

1

1

1

• System diagram

DC12V

Program

 

 

 

Remote

 

weekly

 

 

 

controller

 

timer

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

wires

 

 

 

 

: Terminal block

 

 

 

 

 

 

 

 

Indoor unit

: Connector

Outdoor unit

83

Screws

2

M4 x 25

 

Wood screws

2

 

Spacer

2

 

Owner’s Manual

1

 

Installation Manual

1

 

Requirement to install

the program weekly timer

Installing dimension for serial installation

When installing the program weekly timer (remote controller/system controller, etc.) to the wall surface, follow the installation procedure in (Fig. 1) and (Fig. 2).

 

92.5mm or more

125mm or more

 

from the wall

 

Spacer

 

Wall

90mm or more

125mm or more

 

from the wall

2.5mm (Gap size)

Pull-out port of lead wire

Fig. 1

*When installing the remote controller and the program weekly timer which are set in parallel at upper side and lower side, in consideration of maintenance, keep a clearance with 25mm or more.

Install the program weekly timer apart from the generation source of noise.

NOTE 3 :

When noise is induced to the power source of the indoor unit, measures such as mounting the noise filter is necessary.

Install the program weekly timer to the box (Procured locally) which has previously inserted in the wall.

Small screws

Spacer

M4 x 25 (2 pcs.)

 

or wood screws

 

Rear case

Program weekly

timer body

Cover

Fig. 2

1.Inserting a minus screwdriver, etc. into the groove at the lower side of the program weekly timer, which appears when opening lid of the program weekly timer body, force open the rear case to remove it.

2.Using the attached M4 screws or wood screws (2 pcs.), fix the rear case of the program weekly timer. Before installation, press to open the screw hole with a screwdriver, etc.

Fix it with the spacer, but not so strongly. If the program weekly timer does not fit closely to the wall, adjust it by cutting off the spacer.

3.Connect the attached connecting cable

(4 cores) to the program weekly timer body.

4.Install the program weekly timer body by matching to hooks on the rear case and putting into the hooks.

Program

2

2

 

 

2

2

Remote

weekly

3

3

 

 

 

3

3

controller

timer

 

 

 

4

4

4

4

 

Connecting cable (Accessory)

Arrangement

The program weekly timer and the remote controller can be arranged to either right or left side.

Cabling procedure

Perform cabling in the following procedure.

1.Connect the attached connecting cable to the timer terminal (4P connector) of the program weekly timer. (Fig. 3)

<Remote controller> <Program weekly timer>

To terminal block

To program

To remote controller

for indoor unit

Attached

Connector

remote controller

weekly timer

connecting cable

section

cabling

 

 

 

 

Fig. 3

2.Pull the attached cable out of lead wire pull- out port on the rear case of the program weekly timer and connect the cable to the timer terminal (4P connector) of the remote controller via inside of the wall. (Fig. 4)

Attached connecting cable

<Program weekly timer> <Remote controller>

Lead wire pull-out port

Fig. 4

Program weekly timer test run setup

After installation, check (OFF to ON) output status using the forced ON switch on the rear side of the program weekly timer P.C. board. Then check the normal operation and certainly turn OFF the forced ON switch.

ON OFF

ON OFF

Forced ON switch

Memory backup function for power failure compensation

This program weekly timer stores in memory the contents set by the operation button during a power failure. Pushing PROGRAM button resumes the operation with the contents before the power failure when the power failure has been reset.

How to use [BACKUP]

After the installation work, check [BACKUP] switch on the rear side of the program weekly timer P.C. board is turned to ON side.

ON OFF

ON OFF

BACKUP switch

Explanation to customers

After the installation work, hand “Owner’s Manual” and “Installation Manual” to the customers.

Explain use and maintenance methods to the customers according to “Owner’s Manual”.

85464359429000 (EN)

Image 83
Contents Split Type Adoption of NEW Refrigerant AccessoriesApplicable Controls Accessory parts and Parts to be procured locallyProgram Weekly Timer Type Concealed Duct TypeConnect the connecting cable correctly Precautions for SafetyNew Refrigerant Air Conditioner Installation To Disconnect the Appliance from Main Power SupplyInappropriate grounding may cause electric shock Before installation Accessory and RefrigerantSelection of Installation Accessory and Installation PartsObstacle at front side Upper side is free Installation PlaceNecessary Space for Installation Obstacle at rear side Upper side is freeInstallation of Outdoor Unit Selection of InstallationPiping connection Optional Installation Parts Local ProcureRefrigerant Piping Connection For ReferenceKnockout of Pipe Cover Knockout procedureHow to remove the front panel Projection margin in flaring B Unit mm Flaring Refrigerant PipingPipe Forming/End Positioning Flaring size a Unit mmOuter diam. of copper pipe Tightening torque Tightening of Connecting PartRefrigerant Piping RequirementVacuum pump EvacuatingAir Purge Charge port How to open the valveEvacuating Valve sizeElectrical Work SM560AT-E How to remove the valve coverHow to wire Stripping length power cord and connecting cableSelf-Diagnosis by LED Indication Final Installation ChecksCheck and Test Operation New tools for R410A Applicable to R22 model Changes Changes in the product and componentsNew tools for R410A Precautions for Safety RAV Length of refrigerant pipe Single unitIn installation Selection of Installation Liquid side Gas side Outer diameter Thickness Ø9.5 Ø15.9 Outer dia Projection margin in flaring B Unit mmOuter dia. of copper pipe R410A Outer dia. of copper pipe Tightening torque Valve at gas sideEvacuating How to close the valve Mm2 or more SM1100AT-E SM1400AT-E Power supply 220 240Single phase 50 Hz Useful Functions Final Installation Checks Remote controller Accessories Sold SeparatelyPrecautions for Safety RAV-SM561BT-E/RAV-SM801BT-E RAV-SM1101BT-E/RAV-SM1401BT-E Outdoor unit Parts NameIndoor unit Display section Parts Name of Remote ControllerOperation section Stop Turn on the main power switch and/or the leakage breakerCorrect Usage PreparationStart Mode select button ModeTemperature button When restarting the operation after stopClear of timer operation Timer OperationTimer operation Get uniform circulation of room air Hints for Economical OperationDo not open doors and windows more often than necessary Window curtainsChecks before operation MaintenanceCleaning of remote controller If you do not plan to use the unit for more than 1 monthAIR Conditioner Operations and Performance Be careful with noise or vibrations RE-INSTALLATIONDo not install the air conditioner in the following places Troubles and CausesInoperative Auto Part name ’ty Shape Part name ’ty Shape Standard wired remote ControllerSeparate sold parts Precautions for Safety Inappropriate grounding may cause electric shock Secure the space required to installation and servicing Selection of Installation PlaceInstallation space Selection of installation place AdviceInstallation procedure Installation of Indoor UnitRAV-SM1101, 1401BT Installation of Indoor UnitDimension External viewClamp mounting Removal of air filter Installation of remote controller Sold separatelyMounting of clamp Accessory Hanging down of indoor unitQuality of supplying grilles Restriction to installationInstallation clearance Ledge ceiling concealed duct typeAIR Ducting Work Static pressure characteristics of each modelRAV-SM1101BT Round duct AIR Ducting WorkConnecting method of the duct General cautions Points at installation workMounting of filter and canvas for suction port Mounting of remote controllerHanging of indoor unit Thermal-insulating process Drain Piping WorkPiping material Piping and cautionsAfter electric piping work Drain-upConnection of the drain hose Check of water drainTightening torque of flare pipe connections Permissible piping length and heatFlaring dia meter size a Unit mm Tightening connectionUse a vacuum pump Packed valve handling precautionsOpen valve fully Gas leak check801, 1101, 1401 type valve at gas side For 801, 1101, 1401AT modelElectrical Work Cabling Remote controller cablingCabling diagram Electrical WorkBefore test run How to execute a test runCase of wired remote controller Test RUNConfirmation and check TroubleshootingConfirmation of error history Procedure DescriptionAutomatic address Applicable ControlsNotification To incorporate a filter sold separately Setup of external static pressureWhen using wireless remote controller Applicable ControlsTo secure better effect of heating Change of lighting time of filter signClean the Return grilles with water INSTALLATION/SERVICING ToolsMaintenance Cleaning of Return grilleContents AccessoriesRBC-EXW21E FeaturesTurn on the power supply of the air conditioner How to check the program operation timeSetting error display Present time display Timer set buttonCancel button Holiday setting indication markHeating Operation procedureTurn on the power supply of the air conditioner Setup of the day of the weekNext set up the operation time to the program 2 When push SET Button,Set error When ON/OFF time is set as follows, Error is displayedClear of a part of the program Clearance of Holiday setupPush DAY button and put the operation To be checkedResuming of operation Matters to be memorized Power failureOperation of program weekly timer and air conditioner RBC-AS21E Start/Stop button Check button Used in servicing Temperature Setup buttonSelected mode displays Heat pump type Selected mode displays Cooling only typePush button Push button to select fan speed Power supplyPush either or set to Auto Recommended temperature Automatic Cool/HeatRequirement to install Remote controller Accessory partsHow to install remote controller Requirement for installation Multiple remote controllersHow to perform cabling of the remote controller Accessory partsRequirement for installation Multiple remote controllers Remote controller test run setupProgram weekly timer test run setup Accessory parts Part Name ’tyHow to install the program weekly timer Requirement to install Program weekly timerHow to install the remote sensor Accessory partsRequirement to install the remote sensor Maintenance of filter sold separately SpecificationsSafety Cautions Installation of filter sold separatelyHigh-Efficiency filter 65% Model TCB-UFM11BE Installation of high-efficiency filterSetup of fan when building in the high-efficiency filter High-Efficiency FilterAmmonium Filter Model TCB-DF11BE-AM Setup of fan when building in the filter sold separatelyDeodorant Filter, Ammonium Filter Deodorant Filter Model TCB-DF11BE

R410A specifications

Toshiba R410A is a highly regarded refrigerant known for its efficiency and environmental benefits. This hydrofluorocarbon (HFC) mixture is widely used in various air conditioning and refrigeration applications due to its excellent thermodynamic properties. One of the standout features of R410A is its superior energy efficiency, which contributes to lower energy consumption and reduced CO2 emissions in HVAC systems.

One significant advantage of R410A over older refrigerants, such as R22, is its lower ozone depletion potential (ODP). R410A has an ODP of zero, making it a more environmentally friendly choice. This characteristic aligns with global initiatives aimed at protecting the ozone layer and promoting sustainable practices. The shift to R410A has been supported by government regulations in many countries, phasing out older, more harmful refrigerants.

Toshiba has incorporated advanced technologies in its R410A compatible products, enhancing performance and reliability. Among these technologies is the inverter technology that allows the compressor to operate at variable speeds. This functionality leads to improved temperature regulation, reduced noise levels, and further energy savings. Inverter systems provide precise control over the cooling and heating processes, allowing for a comfortable indoor environment while minimizing wastage of energy.

R410A also exhibits excellent heat transfer properties, which boosts cooling capacity. This feature makes it suitable for large-scale HVAC systems, including commercial and industrial applications. Its high-pressure characteristics enable the design of more compact and efficient components, allowing for smaller units and easier installation.

Furthermore, Toshiba's dedication to technological innovation is visible in its commitment to research and development. The company continuously strives to optimize systems that utilize R410A, focusing on reliability and longevity. This includes improved compressor designs, enhanced heat exchangers, and the integration of smart controls that adapt to the varying load conditions in real-time.

In terms of safety, R410A is classified as non-toxic and non-flammable under normal conditions, making it a safe choice for use in residential and commercial settings. However, it is important to note that R410A operates at higher pressures compared to traditional refrigerants, necessitating proper equipment design and handling procedures.

In conclusion, Toshiba R410A stands out in the market for its energy efficiency, environmental safety, and technological advancements. It is an ideal refrigerant for modern HVAC applications, contributing to both comfort and sustainability. As the industry continues to evolve, R410A remains a pivotal element in the quest for responsible and efficient refrigeration solutions.