INSTALLATION MANUAL Remote sensor

To Personnel Charged in Installation (Electric) Work and Service

MODEL : TCB-TC21LE

 

 

Accessory parts

 

Fix it with the spacer, but not so strongly. If the remote

 

 

 

 

Part Name

Q’ty

Part Name

Q’ty

sensor does not fit closely to the wall, adjust it by

cutting off the spacer.

 

Remote sensor

 

Spacer

 

 

 

2

3. Connect the remote sensor cable (2 cores) to the

 

1

 

(200mm-cable

 

 

terminal numbers of the indoor unit.

 

 

 

attached)

 

Wire joint

 

(Applying AC 220/230/240V breaks the unit.)

Small screw

 

2

 

 

4. Install the remote sensor body by matching to hooks

 

 

 

M4 x 25

2

 

 

on the rear case and putting into the hooks.

 

Cable clamper

 

 

 

1

 

 

 

 

 

 

 

Wood screw

 

Installation Manual

 

How to perform cabling of the remote sensor

 

2

1

 

 

 

 

 

 

 

 

 

In case of using the remote sensor as a concealed type

Requirement to install the remote sensor

Installation place

• Install the remote sensor at a position with height 1 to

1.5m from the floor, where the average temperature in

the room can be felt.

• Do not install the remote sensor at a place exposed to

the direct sunlight or direct outside air, such as a side of

window, etc.

• Do not install the remote sensor at a place behind

something or rear side of something, where air flow is

poor in the room.

• Connection diagram

 

 

 

Approx. 200mm

Terminal block

A

W

Remote

for remote

 

controller cable

B

B

sensor

in indoor unit

 

 

 

 

W : White

Remote sensor cable

Connecting

Cable from

B : Black

(Procured locally)

section

remote sensor body

Non polarity, 2 core cable is used..

Use 0.5mm² to 2 mm² cable.

Do not install the remote controller near the freezing

 

box or refrigerator because water proof or drop-proof is

 

not applied to this remote controller.

Be sure to set the remote sensor vertically on the wall

 

surface, etc.

How to install the remote sensor

NOTE 1 : Avoid to twist the remote sensor cable with the power supply cable, etc. or to store them in the same metal pipe, otherwise it causes a malfunction.

Attached wire joint (White, 2 pcs.)

Remote sensor cable

 

Cable from

Wire joint, CE-1

remote sensor body

(Nichiatsu)

1)Peel the sheath of the cable to be connected by approx. 14mm.

2)Twist two cables and pressure-connect them using a wire joint.

3)When an exclusive pressure-connecting tool is not used or soldering connection is used, apply insulation process with an insulation tape.

NOTE 2 : Install the remote sensor apart from the generation source of noise.

NOTE 3 : When noise is induced to the power source of the indoor unit, some measures such as mounting the noise filter is necessary.

• In case of using the remote sensor as a concealed type

Rear case Spacer

Remote sensor body

Wall

Small screws

M4 x 25 (2 pcs.)

1.Inserting a minus screwdriver, etc. into the groove at the lower side of the remote sensor body, force open the rear case to remove it.

2.Using the attached M4 screws (2 pcs.), fix the rear case of the remote sensor. Before installation, press to open the screw hole with a screwdriver, etc.

Requirement for using the remote sensor

together with the remote controller

How to install

For the above control, install the remote sensor in the following procedure.

1.Set the remote controller as the master remote controller.

2.Do not change the remote sensor switch in the master remote controller for correct temperature control by remote sensor.

Basic cabling diagram

1.Connect cables without miswiring. (Miswiring breaks the unit.)

2.In a case to operate an indoor unit from the remote sensors and the remote controller.

Remote

 

 

 

 

Remote

 

 

 

 

(Sold

 

 

 

 

controller

 

 

 

 

sensor

 

 

 

 

 

 

 

 

separately)

 

 

 

 

(Master)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller cable

 

 

 

 

 

 

 

 

(Procured locally)

Terminal block for remote controller cable

A B

Indoor unit

Earth

84

85464359427000 (EN)-

Image 84
Contents Split Type Accessories Adoption of NEW RefrigerantAccessory parts and Parts to be procured locally Program Weekly Timer TypeConcealed Duct Type Applicable ControlsPrecautions for Safety New Refrigerant Air Conditioner InstallationTo Disconnect the Appliance from Main Power Supply Connect the connecting cable correctlyInappropriate grounding may cause electric shock Accessory and Refrigerant Selection of InstallationAccessory and Installation Parts Before installationInstallation Place Necessary Space for InstallationObstacle at rear side Upper side is free Obstacle at front side Upper side is freeSelection of Installation Installation of Outdoor UnitOptional Installation Parts Local Procure Refrigerant Piping ConnectionFor Reference Piping connectionKnockout procedure How to remove the front panelKnockout of Pipe Cover Refrigerant Piping Pipe Forming/End PositioningFlaring size a Unit mm Projection margin in flaring B Unit mm FlaringTightening of Connecting Part Refrigerant PipingRequirement Outer diam. of copper pipe Tightening torqueEvacuating Air PurgeVacuum pump How to open the valve EvacuatingValve size Charge portSM560AT-E How to remove the valve cover How to wireStripping length power cord and connecting cable Electrical WorkFinal Installation Checks Check and Test OperationSelf-Diagnosis by LED Indication Changes in the product and components New tools for R410ANew tools for R410A Applicable to R22 model Changes Precautions for Safety RAV Length of refrigerant pipe Single unitIn installation Selection of Installation Liquid side Gas side Outer diameter Thickness Ø9.5 Ø15.9 Projection margin in flaring B Unit mm Outer dia. of copper pipe R410AOuter dia Valve at gas side Outer dia. of copper pipe Tightening torqueEvacuating How to close the valve SM1100AT-E SM1400AT-E Power supply 220 240 Single phase 50 HzMm2 or more Useful Functions Final Installation Checks Accessories Sold Separately Precautions for SafetyRemote controller RAV-SM561BT-E/RAV-SM801BT-E RAV-SM1101BT-E/RAV-SM1401BT-E Parts Name Indoor unitOutdoor unit Parts Name of Remote Controller Display sectionOperation section Turn on the main power switch and/or the leakage breaker Correct UsagePreparation StopMode select button Mode Temperature buttonWhen restarting the operation after stop StartTimer Operation Timer operationClear of timer operation Hints for Economical Operation Do not open doors and windows more often than necessaryWindow curtains Get uniform circulation of room airMaintenance Cleaning of remote controllerIf you do not plan to use the unit for more than 1 month Checks before operationAIR Conditioner Operations and Performance RE-INSTALLATION Do not install the air conditioner in the following placesTroubles and Causes Be careful with noise or vibrationsInoperative Auto Part name ’ty Shape Standard wired remote Controller Separate sold partsPart name ’ty Shape Precautions for Safety Inappropriate grounding may cause electric shock Selection of Installation Place Installation space Selection of installation placeAdvice Secure the space required to installation and servicingInstallation of Indoor Unit Installation procedureInstallation of Indoor Unit DimensionExternal view RAV-SM1101, 1401BTInstallation of remote controller Sold separately Mounting of clamp AccessoryHanging down of indoor unit Clamp mounting Removal of air filterRestriction to installation Installation clearanceLedge ceiling concealed duct type Quality of supplying grillesStatic pressure characteristics of each model AIR Ducting WorkAIR Ducting Work RAV-SM1101BT Round ductConnecting method of the duct Points at installation work General cautionsMounting of remote controller Hanging of indoor unitMounting of filter and canvas for suction port Drain Piping Work Piping materialPiping and cautions Thermal-insulating processDrain-up Connection of the drain hoseCheck of water drain After electric piping workPermissible piping length and heat Flaring dia meter size a Unit mmTightening connection Tightening torque of flare pipe connectionsPacked valve handling precautions Open valve fullyGas leak check Use a vacuum pumpFor 801, 1101, 1401AT model 801, 1101, 1401 type valve at gas sideElectrical Work Remote controller cabling Cabling diagramElectrical Work CablingHow to execute a test run Case of wired remote controllerTest RUN Before test runTroubleshooting Confirmation of error historyProcedure Description Confirmation and checkApplicable Controls NotificationAutomatic address Setup of external static pressure When using wireless remote controllerApplicable Controls To incorporate a filter sold separatelyChange of lighting time of filter sign To secure better effect of heatingINSTALLATION/SERVICING Tools MaintenanceCleaning of Return grille Clean the Return grilles with waterAccessories ContentsFeatures Turn on the power supply of the air conditionerHow to check the program operation time RBC-EXW21ETimer set button Cancel buttonHoliday setting indication mark Setting error display Present time displayOperation procedure Turn on the power supply of the air conditionerSetup of the day of the week HeatingWhen push SET Button, Set errorWhen ON/OFF time is set as follows, Error is displayed Next set up the operation time to the program 2Clearance of Holiday setup Push DAY button and put the operationTo be checked Clear of a part of the programMatters to be memorized Power failure Operation of program weekly timer and air conditionerResuming of operation RBC-AS21E Temperature Setup button Selected mode displays Heat pump typeSelected mode displays Cooling only type Start/Stop button Check button Used in servicingPower supply Push either or set to Auto Recommended temperatureAutomatic Cool/Heat Push button Push button to select fan speedAccessory parts How to install remote controllerRequirement for installation Multiple remote controllers Requirement to install Remote controllerAccessory parts Requirement for installation Multiple remote controllersRemote controller test run setup How to perform cabling of the remote controllerAccessory parts Part Name ’ty How to install the program weekly timerRequirement to install Program weekly timer Program weekly timer test run setupAccessory parts Requirement to install the remote sensorHow to install the remote sensor Specifications Safety CautionsInstallation of filter sold separately Maintenance of filter sold separatelyInstallation of high-efficiency filter Setup of fan when building in the high-efficiency filterHigh-Efficiency Filter High-Efficiency filter 65% Model TCB-UFM11BESetup of fan when building in the filter sold separately Deodorant Filter, Ammonium FilterDeodorant Filter Model TCB-DF11BE Ammonium Filter Model TCB-DF11BE-AM

R410A specifications

Toshiba R410A is a highly regarded refrigerant known for its efficiency and environmental benefits. This hydrofluorocarbon (HFC) mixture is widely used in various air conditioning and refrigeration applications due to its excellent thermodynamic properties. One of the standout features of R410A is its superior energy efficiency, which contributes to lower energy consumption and reduced CO2 emissions in HVAC systems.

One significant advantage of R410A over older refrigerants, such as R22, is its lower ozone depletion potential (ODP). R410A has an ODP of zero, making it a more environmentally friendly choice. This characteristic aligns with global initiatives aimed at protecting the ozone layer and promoting sustainable practices. The shift to R410A has been supported by government regulations in many countries, phasing out older, more harmful refrigerants.

Toshiba has incorporated advanced technologies in its R410A compatible products, enhancing performance and reliability. Among these technologies is the inverter technology that allows the compressor to operate at variable speeds. This functionality leads to improved temperature regulation, reduced noise levels, and further energy savings. Inverter systems provide precise control over the cooling and heating processes, allowing for a comfortable indoor environment while minimizing wastage of energy.

R410A also exhibits excellent heat transfer properties, which boosts cooling capacity. This feature makes it suitable for large-scale HVAC systems, including commercial and industrial applications. Its high-pressure characteristics enable the design of more compact and efficient components, allowing for smaller units and easier installation.

Furthermore, Toshiba's dedication to technological innovation is visible in its commitment to research and development. The company continuously strives to optimize systems that utilize R410A, focusing on reliability and longevity. This includes improved compressor designs, enhanced heat exchangers, and the integration of smart controls that adapt to the varying load conditions in real-time.

In terms of safety, R410A is classified as non-toxic and non-flammable under normal conditions, making it a safe choice for use in residential and commercial settings. However, it is important to note that R410A operates at higher pressures compared to traditional refrigerants, necessitating proper equipment design and handling procedures.

In conclusion, Toshiba R410A stands out in the market for its energy efficiency, environmental safety, and technological advancements. It is an ideal refrigerant for modern HVAC applications, contributing to both comfort and sustainability. As the industry continues to evolve, R410A remains a pivotal element in the quest for responsible and efficient refrigeration solutions.