York B1HH018 Additional Static Pressure Resistance, RESISTANCE, IWG Description CFM, Clearances

Page 13

66297-YIM-C-0205

TABLE 21 - ADDITIONAL STATIC PRESSURE RESISTANCE

 

 

 

 

 

 

 

RESISTANCE, IWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DESCRIPTION

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

600

700

800

900

1,000

1,100

1,200

1,300

1,400

1,500

1,600

1,700

1,800

1,900

2,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wet Indoor coil

0.01

0.01

0.01

0.02

0.01

0.02

0.03

0.04

0.04

0.03

0.04

0.04

0.05

0.05

0.06

0.07

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Economizer

0.00

0.00

0.00

0.01

0.01

0.01

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.07

0.08

0.08

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Filter/Frame Kit

0.01

0.02

0.02

0.02

0.02

0.02

0.03

0.03

0.03

0.03

0.04

0.05

0.05

0.06

0.06

0.07

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electric Heat

0.02

0.03

0.03

0.03

0.04

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.01

0.11

0.11

0.12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: 1. Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.

2.The pressure thru the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air duct system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.

CLEARANCES

(Minimum)

Front

12"

Back

0"

Left Side (Filter Access)

24"

Right Side

24"

Below Unit

0"

Above Unit￿

36" (For CondenserAir Discharge)

Units may be installed on combustible floors made from wood or class A, ￿B or C roof covering material.

Units must be installed outdoors. Overhanging structures or shrubs should not obstruct outdoor air discharge outlet.

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

NOTE: FOR UNITS APPLIED WITH A ROOF

 

CURB, THE MINIMUM CLEARANCE MAY BE

￿￿

TERIAL AND THE SUPPLY DUCT.

￿￿￿￿￿￿￿￿￿￿￿￿￿￿

REDUCED FROM 1 INCH TO 1/2 INCH BE-

 

TWEEN COMBUSTIBLE ROOF CURB MA-

 

FIG. 3 - CLEARANCES

Unitary Products Group

13

Image 13
Contents General Replacement PartsInspection ReferenceLocation LimitationsRigging or Handling Power and Control Wiring Service AccessClearances Duct WorkUnit Terminal Strip ThermostatPhysical Data Motor Ampacity Electrical Data Basic UnitSize Factor MIN MAX RLA LRAAmps Size Electrical Data 12 Seer Heat Pump / Electric Heat Model BHHElectrical Data 12 Seer Heat Pump / Electric Heat Indoor DB Outdoor TEMPERATURE, F Temperature Outdoor Indoor WB TEMPERATURE, F Temperature10.8 15.8 19.6 22.0 24.4 26.8 29.2 31.6 21.2 230/460/575 volts Side and Bottom Supply AIR Blower PerformanceVolts RESISTANCE, IWG Description CFM Additional Static Pressure ResistanceClearances Front Unit Size DimensionWith Power to Unit and Thermostat in Heating Mode With Power to Unit and Thermostat in Cooling ModeCooling Operation Thermostat Signals Single Phase Units Secure Owners Approval When the system isThermostat Signals Three Phase Units Normal MaintenanceCompressor and Outdoor FAN Instant on Elementary Diagram TroubleshootingYIM-C-0205$ Typical Wiring Diagram Notes See12356 Factory Typical Wiring Diagram BHH060 460-3-60 Power Supply Unit Caut Typical Wiring Diagram Legend SeeTypical Wiring Diagram 208/230-1-60 Power Supply Typical Wiring Diagram 230-3-60 Power Supply Typical Wiring Diagram 460-3-60 & 575-3-60 Power Supply Typical Wiring Diagram Notes See page 24, 25 Typical Wiring Diagram Legend See page 24, 25