TABLE 21 - ADDITIONAL STATIC PRESSURE RESISTANCE
|
|
|
|
|
|
| RESISTANCE, IWG |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
DESCRIPTION |
|
|
|
|
|
|
| CFM |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 500 | 600 | 700 | 800 | 900 | 1,000 | 1,100 | 1,200 | 1,300 | 1,400 | 1,500 | 1,600 | 1,700 | 1,800 | 1,900 | 2,000 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Wet Indoor coil | 0.01 | 0.01 | 0.01 | 0.02 | 0.01 | 0.02 | 0.03 | 0.04 | 0.04 | 0.03 | 0.04 | 0.04 | 0.05 | 0.05 | 0.06 | 0.07 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Economizer | 0.00 | 0.00 | 0.00 | 0.01 | 0.01 | 0.01 | 0.01 | 0.02 | 0.03 | 0.04 | 0.05 | 0.06 | 0.07 | 0.07 | 0.08 | 0.08 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Filter/Frame Kit | 0.01 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.03 | 0.03 | 0.03 | 0.03 | 0.04 | 0.05 | 0.05 | 0.06 | 0.06 | 0.07 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Electric Heat | 0.02 | 0.03 | 0.03 | 0.03 | 0.04 | 0.04 | 0.05 | 0.06 | 0.07 | 0.08 | 0.09 | 0.10 | 0.01 | 0.11 | 0.11 | 0.12 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
NOTE: 1. Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
2.The pressure thru the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air duct system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.
CLEARANCES
(Minimum)
Front | 12" |
Back | 0" |
Left Side (Filter Access) | 24" |
Right Side | 24" |
Below Unit | 0" |
Above Unit | 36" (For CondenserAir Discharge) |
Units may be installed on combustible floors made from wood or class A, B or C roof covering material.
Units must be installed outdoors. Overhanging structures or shrubs should not obstruct outdoor air discharge outlet.
NOTE: FOR UNITS APPLIED WITH A ROOF |
| |
CURB, THE MINIMUM CLEARANCE MAY BE | ||
TERIAL AND THE SUPPLY DUCT. | ||
REDUCED FROM 1 INCH TO 1/2 INCH BE- |
| |
TWEEN COMBUSTIBLE ROOF CURB MA- |
|
FIG. 3 - CLEARANCES
Unitary Products Group | 13 |