York B1HH018, THRU 060 Normal Maintenance, Thermostat Signals Three Phase Units

Page 17

66297-YIM-C-0205

TABLE 23 - THERMOSTAT SIGNALS (THREE PHASE UNITS)

SIGNAL

STATE

BOARD FUNCTION

 

 

 

 

 

 

“G”

ON

FAN INSTANT ON

 

 

OFF

FAN INSTANT OFF

 

 

 

 

 

 

FAN INSTANT ON

 

ON

COMPRESSOR AND OUTDOOR FAN INSTANT ON (AFTER ANTI-SHORT CYCLE DELAY)

 

REVERSING VALVE ENERGIZED

“G” & “Y” & “O”

 

 

SYSTEM OPERATES IN COOLING

 

 

 

 

OFF

COMPRESSOR AND OUTDOOR FAN INSTANT OFF

 

FAN 60 SEC. DELAY OFF

 

 

 

 

 

 

 

FAN INSTANT ON

 

ON

COMPRESSOR AND OUTDOOR FAN INSTANT ON (AFTER ANTI-SHORT CYCLE DELAY)

“G” & “Y”

 

SYSTEM OPERATES IN HEATING

 

 

 

OFF

COMPRESSOR AND OUTDOOR FAN INSTANT OFF

 

FAN 60 SEC. DELAY OFF

 

 

 

 

 

 

 

FAN INSTANT ON

 

ON

HEATER BANK 1, 2 & 3 ELEC. HEAT INSTANT ON

“G” & “W”

 

HEATER BANK 4, 5 & 6 ELEC. HEAT 10 SEC. DELAY ON

 

 

 

HEATER BANK 4, 5 & 6 ELEC. HEAT INSTANT OFF

 

 

 

OFF

HEATER BANK 1, 2 & 3 ELEC. HEAT ￿￿SEC. DELAY OFF

 

 

FAN 10 SEC. DELAY OFF

 

 

 

 

 

FAN INSTANT ON

 

 

COMPRESSOR AND OUTDOOR FAN INSTANT ON

 

ON

SYSTEM OPERATES IN HEATING

 

 

HEATER BANK 1, 2 & 3 ELEC. HEAT INSTANT ON

“G” & “Y” & “W”

 

HEATER BANK 4, 5 & 6 ELEC. HEAT 10 SEC. DELAY ON

 

 

 

 

COMPRESSOR AND OUTDOOR FAN INSTANT OFF

 

 

HEATER BANK 4, 5 & 6 ELEC. HEAT INSTANT OFF

 

OFF

HEATER BANK 1, 2 & 3 ELEC. HEAT ￿￿SEC. DELAY OFF

 

 

FAN 60 SEC. DELAY OFF

 

 

 

 

 

FAN INSTANT ON

 

ON

HEATER BANK 1, 2 & 3 ELEC. HEAT INSTANT ON

“W”

 

HEATER BANK 4, 5 & 6 ELEC. HEAT 10 SEC. DELAY ON

 

 

 

HEATER BANK 4, 5 & 6 ELEC. HEAT INSTANT OFF

 

 

 

OFF

HEATER BANK 1, 2 & 3 ELEC. HEAT ￿￿SEC. DELAY OFF

 

 

FAN 10 SEC. DELAY OFF

 

 

MAINTENANCE

NORMAL MAINTENANCE

 

WARNING: Prior to any of the following maintenance proce- dures, shut off all power to the unit, to avoid per- sonal injury.

Periodic maintenance consists of changing or cleaning filters and general cleaning of the outdoor coil.

FILTERS - Inspect once a month. Replace Disposable or clean Permanent Type as necessary. DO NOT replace Per- manent Type with Disposable.

MOTORS - Indoor and outdoor fan motors are permanently lubricated and require no maintenance.

OUTDOOR COIL - Dirt should not be allowed to accumulate on the outdoor coil surface or other parts in the air circuit. Cleaning should be as often as necessary to keep the coil clean. Use a brush, vacuum cleaner attachment, or other suitable means. If water is used to clean the coil, be sure that the power to the unit is shut off prior to cleaning.

CAUTION: Exercise care when cleaning the coil so that the coil fins are not damaged.

Do not permit the hot condenser air discharge to be obstructed by overhanging structures or shrubs.

Unitary Products Group

17

Image 17
Contents General Replacement PartsInspection ReferenceRigging or Handling LimitationsLocation Power and Control Wiring Service AccessClearances Duct WorkPhysical Data ThermostatUnit Terminal Strip Motor Ampacity Electrical Data Basic UnitSize Factor MIN MAX RLA LRAAmps Size Electrical Data 12 Seer Heat Pump / Electric Heat Model BHHElectrical Data 12 Seer Heat Pump / Electric Heat Indoor DB Outdoor TEMPERATURE, F Temperature Outdoor Indoor WB TEMPERATURE, F Temperature10.8 15.8 19.6 22.0 24.4 26.8 29.2 31.6 21.2 Volts Side and Bottom Supply AIR Blower Performance230/460/575 volts Clearances Additional Static Pressure ResistanceRESISTANCE, IWG Description CFM Front Unit Size DimensionCooling Operation With Power to Unit and Thermostat in Cooling ModeWith Power to Unit and Thermostat in Heating Mode Thermostat Signals Single Phase Units Secure Owners Approval When the system isCompressor and Outdoor FAN Instant on Normal MaintenanceThermostat Signals Three Phase Units Elementary Diagram TroubleshootingYIM-C-0205$ Typical Wiring Diagram Notes See12356 Factory Typical Wiring Diagram BHH060 460-3-60 Power Supply Unit Caut Typical Wiring Diagram Legend SeeTypical Wiring Diagram 208/230-1-60 Power Supply Typical Wiring Diagram 230-3-60 Power Supply Typical Wiring Diagram 460-3-60 & 575-3-60 Power Supply Typical Wiring Diagram Notes See page 24, 25 Typical Wiring Diagram Legend See page 24, 25