York THRU 060, B1HH018 installation instructions Outdoor Indoor WB TEMPERATURE, F Temperature

Page 8

66297-YIM-C-0205

TABLE 6 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 600 CFM (B1HH018)

OUTDOOR

 

 

 

 

INDOOR WB TEMPERATURE, °F

 

 

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

 

 

 

 

 

55

57

59

61

 

63

65

67

 

69

71

73

75

°F

 

 

65

5.5

5.8

6.1

6.4

 

6.7

7.0

7.3

 

13.0

18.7

24.5

30.2

70

5.1

5.5

5.9

 

6.3

6.7

7.1

 

12.4

17.8

23.1

28.5

75

5.4

 

5.8

6.3

6.8

 

11.8

16.8

21.8

26.8

80

 

5.4

6.0

6.6

 

11.2

15.8

20.5

25.1

85

 

5.6

6.3

 

10.6

14.9

19.1

23.4

90

 

5.3

6.1

 

10.0

13.9

17.8

21.7

95

 

5.8

 

9.4

12.9

16.5

20.0

100

 

 

7.9

11.0

14.1

17.2

105

 

 

6.5

9.1

11.8

14.4

110

 

 

5.0

7.2

9.4

11.6

115

 

 

5.3

7.1

8.8

TABLE 7 - HEATING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 600 CFM (B1HH018)

INDOOR DB

 

 

 

OUTDOOR TEMPERATURE, °F

 

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

 

 

-10

0

10

 

20

30

 

40

50

60

°F

 

 

55

3.1

3.5

4.0

 

4.7

5.8

 

7.3

9.4

12.4

70

 

3.5

 

5.0

7.1

10.1

80

 

 

3.6

5.7

8.7

TABLE 8 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 800 CFM (B1HH024)

OUTDOOR

 

 

 

 

INDOOR WB TEMPERATURE, °F

 

 

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

 

 

 

 

 

55

57

59

61

 

63

65

67

 

69

71

73

75

°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

18.8

20.7

22.6

24.5

 

26.4

28.3

30.2

 

30.6

31.0

31.4

31.8

70

15.7

17.5

19.3

21.1

 

22.9

24.7

26.5

 

27.5

28.6

29.7

30.8

75

12.5

14.2

15.9

17.6

 

19.3

21.0

22.7

 

24.5

26.2

28.0

29.7

80

9.4

11.0

12.6

14.2

 

15.8

17.4

19.0

 

21.4

23.8

26.3

28.7

85

6.2

7.7

9.2

10.7

 

12.2

13.7

15.2

 

18.3

21.4

24.6

27.7

90

5.9

7.2

 

8.7

10.1

11.5

 

15.3

19.1

22.9

26.7

95

 

5.1

6.4

7.7

 

12.2

16.7

21.1

25.6

100

 

5.3

6.2

 

10.0

13.9

17.7

21.5

105

 

 

7.9

11.1

14.2

17.4

110

 

 

5.8

8.3

10.8

13.3

115

 

 

5.5

7.3

9.2

TABLE 9 - HEATING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 800 CFM (B1HH024)

INDOOR DB

 

 

HEATING SUPERHEAT AT COMPRESSOR SUCTION, °F

 

 

TEMPERATURE,

 

 

 

 

 

 

 

 

-10

0

10

20

30

40

50

60

°F

 

 

 

 

 

 

 

 

 

55

4.4

4.4

4.6

4.9

5.6

7.1

10.2

16.6

70

5.9

12.3

80

9.3

8

Unitary Products Group

Image 8
Contents Replacement Parts GeneralInspection ReferenceRigging or Handling LimitationsLocation Service Access Power and Control WiringClearances Duct WorkPhysical Data ThermostatUnit Terminal Strip Electrical Data Basic Unit Motor AmpacitySize Factor MIN MAX RLA LRAElectrical Data 12 Seer Heat Pump / Electric Heat Model BHH Amps SizeElectrical Data 12 Seer Heat Pump / Electric Heat Outdoor Indoor WB TEMPERATURE, F Temperature Indoor DB Outdoor TEMPERATURE, F Temperature10.8 15.8 19.6 22.0 24.4 26.8 29.2 31.6 21.2 Volts Side and Bottom Supply AIR Blower Performance230/460/575 volts Clearances Additional Static Pressure ResistanceRESISTANCE, IWG Description CFM Unit Size Dimension FrontCooling Operation With Power to Unit and Thermostat in Cooling ModeWith Power to Unit and Thermostat in Heating Mode Secure Owners Approval When the system is Thermostat Signals Single Phase UnitsCompressor and Outdoor FAN Instant on Normal MaintenanceThermostat Signals Three Phase Units Troubleshooting Elementary DiagramTypical Wiring Diagram Notes See YIM-C-0205$12356 Factory Typical Wiring Diagram BHH060 460-3-60 Power Supply Typical Wiring Diagram Legend See Unit CautTypical Wiring Diagram 208/230-1-60 Power Supply Typical Wiring Diagram 230-3-60 Power Supply Typical Wiring Diagram 460-3-60 & 575-3-60 Power Supply Typical Wiring Diagram Legend See page 24, 25 Typical Wiring Diagram Notes See page 24, 25