York LL8V*DH, PV8*DH, FC8V*DH, FL8V*DH, LC8V*DH Safety Section, Furnace Maintenance Section

Page 4

271015-UUM-A-0407

Every time the filters are changed the following items should be visually inspected:

Check vent pipe for blockage or leakage.

Check all components to be sure they are in good condition and that there are no obvious signs of deterioration.

Check for dirt or lint on any surfaces or on components. Do not try to clean any of the surfaces or components. Cleaning of the fur- nace and its components must be done by a qualified service pro- fessional.

If, during the inspection of your furnace, you find any of the following conditions:

Excessive amounts of dust and lint on components.

Damaged or deteriorated components or surfaces.

Leaks or blockage in the vent pipe passages.

Water on any surface inside or outside of the furnace.

Do not operate the furnace, call a certified dealer / servicing contractor to check and / or clean your furnace, or for more information if you have questions about the operation of your furnace.

If all components appear to be in good operating condition, replace the front panels. Turn ON the gas and electrical power supplies to the fur- nace, and set thermostat to the desired temperature.

Air Filters

Dirty filters greatly restrict the flow of air and may cause damage to the moving parts of the furnace. If the filters become clogged the heat exchangers and blower motor could overheat resulting in a potentially dangerous situation.The filters should be checked every 3 months. On new construction, check the filters every week for the first four weeks and every three weeks after that, especially if the indoor fan is running continuously. When replacing the filter(s) you must use filters that are the same size as those recommended in Table 1. use the following pro- cedure to determine the filter size. Never operate your furnace without a suitable air filter.

Removing Filters

Externally Mounted Air Filters

Some installations may have the air filter in a rack attached to the cas- ing of the furnace or placed in the return air duct. You can gain access to the filter by pulling on the door or unscrewing the retaining screw, then slide the filter(s) out of its channel. Replace throw away filter(s) with the same size new filter(s). Throw away filter(s) may be replaced with cleanable filter(s) at this time. Cleanable filter(s) may be cleaned as described in the manufacturer instructions or as described below and then re-installed.

To replace the filter after cleaning you must do the following:

1.Slide filter into place.

2.Snap the door on or place the door in position and tighten the retaining screws, if provided.

3.Make sure the door is secure to the end of the filter rack.

TABLE 1: Filter Sizes

Cabinet Size

Top Return (in)

Top Return (cm)

A

(2) 14 x 20

(2) 35.6 x 50.8

B

(2) 14 x 20

(2) 35.6 x 50.8

C

(2) 14 x 20

(2) 35.6 x 50.8

How to Clean your Filter

High-velocity filters may be cleaned with a vacuum cleaner or washed with a garden hose. Be sure to shake off excess water and allow filter to completely dry before re-installing the filter.

Blower Care

Even with good filters properly in place, blower wheels and motors will become dust laden after long months of operation. The entire blower assembly should be inspected annually. If the motor and wheel are heavily coated with dust, they can be brushed and cleaned with a vac- uum cleaner. If the blower cannot be properly cleaned without removing it from the furnace, then this service must be performed by a qualified service agency.

Make sure you DO NOT move the clip on weight on the indoor fan wheel when cleaning the wheel. This weight is used to balance the wheel. Moving the weight will cause the fan wheel to vibrate.

Motor Lubrication

The motors in these furnaces are permanently lubricated, and do not require periodic oiling.

SECTION II: SERVICE AND MAINTENANCE MANUAL

SAFETY SECTION

The following safety rules must be followed when servicing the furnace.

ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD

Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage.

Improper servicing could result in dangerous operation, serious injury, and death or property damage.

Before servicing, disconnect all electrical power to the fur- nace.

When servicing controls, label all wires prior to disconnect- ing. Reconnect wires correctly.

Verify proper operation after servicing.

FURNACE MAINTENANCE SECTION

The furnace should be cleaned and adjusted by a certified dealer or qualified service contractor once a year or before the start of every heating season. The following items must be cleaned and serviced or replaced if there are signs of deterioration.

1.The vent terminal screen (if applicable).

2.The furnace vent and combustion air intake passageways. Should it be necessary to service the vent/air intake system, the manufac- turer recommends this service be conducted by a qualified service agency. The operation of this appliance requires the reassembly and resealing of the vent/air intake system.

3.The furnace burners, ignitor and flame sensor.

4

Unitary Products Group

Image 4
Contents Table of Contents SafetyContact Information What to do if YOU Smell GASInstructions for Examining the Furnace Installation Fire or Explosion HazardFurnace User Maintenance HOW Your GAS Furnace WorksSTART-UP and Shutdown Instructions Operating InstructionsSafety Section Furnace Maintenance SectionFurnace Cleaning Section Burner Removal/CleaningCleaning the Heat Exchanger Sequence of OperationAdjustment of FAN Control Settings Heating Indoor Fan Off DelayControl Board Heating AirflowTroubleshooting Furnace Control DiagnosticsDiagnostic Fault Code Storage and Retrieval Ignition ControlFurnace Control Event Schedule Section III Replacement Parts List AIR Moving Replacement Part Contact Information Model no Description Used withSection IV Wiring Diagram UUM-A-0407 UUM-A-0407 Unitary Products Group Unitary 5005 Norman Products York Group Drive 73069 Exclusions80%

LL8V*DH, LC8V*DH, FL8V*DH, FC8V*DH, PV8*DH specifications

The York FL8V*DH, LC8V*DH, PV8*DH, LL8V*DH, and FC8V*DH series represent a range of advanced heating and cooling solutions tailored to meet the needs of both residential and commercial applications. These units are engineered with cutting-edge technologies that enhance energy efficiency, performance, and user comfort, making them a top choice for HVAC needs.

One of the standout features of these systems is their high-efficiency design, which often exceeds industry standards. The FL8V*DH, for example, boasts an impressive SEER (Seasonal Energy Efficiency Ratio) rating, allowing users to save on energy costs while ensuring optimal heating and cooling comfort. The innovative design minimizes energy consumption without compromising performance, which is critical in today’s eco-conscious market.

Another hallmark of these series is their use of advanced refrigerant technology. Utilizing environmentally friendly refrigerants, such as R-410A, these units deliver excellent heat transfer while reducing the overall carbon footprint. This focus on sustainability ensures that customers can feel good about their choice, contributing positively to the environment.

The technology behind these models extends to their variable-speed blower motors, which provide precise airflow and temperature control. This flexibility allows adjustments based on real-time demand, enhancing comfort and reducing energy usage. The use of smart thermostats with these systems enables users to program schedules, monitor usage, and optimize settings remotely, further improving efficiency.

In terms of durability and reliability, the York series is built from high-quality materials designed to withstand the test of time. Robust construction minimizes maintenance needs, resulting in lower long-term ownership costs. Additionally, many units feature quiet operation technologies, ensuring minimal noise disturbance, which is particularly important in residential settings.

Moreover, installation and servicing of the York FL8V*DH, LC8V*DH, PV8*DH, LL8V*DH, and FC8V*DH systems are made simpler through their user-friendly designs. Easy access points for maintenance staff help to reduce downtime and enhance system longevity.

Overall, the York FL8V*DH, LC8V*DH, PV8*DH, LL8V*DH, and FC8V*DH units stand out due to their efficiency, innovative technology, durability, and user-friendly design, marking them as exceptional choices in the HVAC market. These systems not only provide comfort but also align with energy-saving initiatives, making them a wise investment for the future.