York FL8V*DH, PV8*DH, FC8V*DH, LC8V*DH, LL8V*DH Troubleshooting, Furnace Control Diagnostics

Page 7

271015-UUM-A-0407

Continuous Blower Operation

The blower will run continuously whenever the wall thermostat fan switch is in the "ON" position. The furnace blower will run at the speed selected on the "FAN SPEED" jumpers on the main control board (HI COOL, LO COOL, HI HEAT or LO HEAT). When the jumper is in the "VS G" position, the blower will run at 50% of the high cool speed.

Delay Tap Selection

The set of jumper pins on the control board labelled "DELAY" are used to set the delay profiles for the furnace. These can be chosen so as to maximize the comfort and sound levels for various regions of the coun- try.

Tap A is the default profile. It provides a 15-second ramp-up from zero airflow to full capacity and a 15-second ramp-down from full capacity back to zero airflow. Whenever there is a change in airflow mode, such as from low heat to high heat, the motor will take 15 seconds to ramp from one speed to the other.

Tap B is the humid profile. This profile is best-suited for installations where the humidity is frequently very high during cooling season, such as in the southern part of the country. On a call for cooling, the blower will ramp up to 50% of full capacity and will stay there for two minutes, then will ramp up to 82% of full capacity and will stay there for five min- utes, and then will ramp up to full capacity, where it will stay until the wall thermostat is satisfied. In every case, it will take the motor 15 sec- onds to ramp from one speed to another.

Tap C is the dry profile. This profile is best suited to parts of the country where excessive humidity is not generally a problem, where the sum- mer months are usually dry. On a call for cooling the motor will ramp up to full capacity and will stay there until the thermostat is satisfied. At the end of the cooling cycle, the blower will ramp down to 50% of full capac- ity where it will stay for 60 seconds. Then it will ramp down to zero. Any ramp up to a higher speed will take 30 seconds and any ramp down to a lower speed (or off) will take 60 seconds.

Tap D is the normal profile, best suited for most of the country, where neither excessive humidity nor extremely dry conditions are the norm. On a call for cooling, the motor will ramp up to 63% of full capacity and will stay there for 90 seconds, then will ramp up to full capacity. At the end of the cooling cycle, the motor will ramp down to 63% of full capac- ity and will stay there for 30 seconds, then will ramp down to zero. In every case, it will take the motor 15 seconds to ramp from one speed to another.

Humidistat

When a humidistat is installed in the system, the “Humidistat Installed?” jumper on the CFM board should be moved to the “YES” position. The cooling CFM will then be reduced by 15% whenever the humidistat indi- cates high humidity.

Hot Surface Ignition System

HOT SURFACE IGNITION SYSTEM

Do not attempt to light this furnace by hand (with a match or any other means). There may be a potential shock hazard from the components of the hot surface ignition system. The furnace can only be lit automatically by its hot surface ignition system.

TROUBLESHOOTING

The following visual checks should be made before troubleshooting:

1.Check to see that the power to the furnace and the ignition control module is ON.

2.The manual shut-off valves in the gas line to the furnace must be open.

3.Make sure all wiring connections are secure.

4.Review the sequence of operation. Start the system by setting the thermostat above the room temperature. Observe the system’s response. Then use the troubleshooting section in this manual to check the system’s operation.

Never bypass any safety control to allow furnace opera- tion. To do so will allow furnace to operate under poten- tially hazardous conditions.

Do not try to repair controls. Replace defective controls with UPG Source 1 Parts.

Never adjust pressure switch to allow furnace operation.

FURNACE CONTROL DIAGNOSTICS

The furnace has built-in, self-diagnostic capability. If a system problem occurs, a blinking LED shows a fault code. The LED can flash red, green or amber to indicate various conditions. It is located behind a clear view port in the blower compartment door.

The control continuously monitors its own operation and the operation of the system. If a failure occurs, the LED will indicate the failure code. If the failure is internal to the control, the light will stay on continuously. In this case, the entire control should be replaced, as the control is not field repairable.

Flash sequence codes 1 through 10 are as follows: LED will turn “on” for 1/4 second and “off” for 1/4 second. This pattern will be repeated the number of times equal to the code. For example, six “on” flashes equals a number 6 fault code. All flash code sequences are broken by a 2 sec- ond “off” period.

SLOW GREEN FLASH: Normal operation.

SLOW AMBER FLASH: Normal operation with call for heat.

RAPID RED FLASH: Twinning error, incorrect 24V phasing. Check twinning wiring.

RAPID AMBER FLASH: Flame sense current is below 1.5 microamps. Check and clean flame sensor. Check for proper gas flow.

4 AMBER FLASHES: The control board is recieving a “Y” signal from the thermostat without a “G” signal, indicating improper thermostat wir- ing.

1 RED FLASH: This indicates that flame was sensed when there was not a call for heat. With this fault code the control will turn on both the inducer motor and supply air blower. A gas valve that leaks through or is slow closing would typically cause this fault.

2 RED FLASHES: This indicates that the normally open pressure switch contacts are stuck in the closed position. The control confirms these contacts are open at the beginning of each heat cycle. This would indicate a faulty pressure switch or miswiring.

3 RED FLASHES: This indicates the normally open pressure switch contact did not close after the inducer was energized. This could be caused by a number of problems: faulty inducer, blocked vent pipe, bro- ken pressure switch hose or faulty pressure switch.

Unitary Products Group

7

Image 7
Contents What to do if YOU Smell GAS Table of ContentsSafety Contact InformationFire or Explosion Hazard Instructions for Examining the Furnace InstallationOperating Instructions Furnace User MaintenanceHOW Your GAS Furnace Works START-UP and Shutdown InstructionsFurnace Maintenance Section Safety SectionSequence of Operation Furnace Cleaning SectionBurner Removal/Cleaning Cleaning the Heat ExchangerHeating Airflow Adjustment of FAN Control SettingsHeating Indoor Fan Off Delay Control BoardFurnace Control Diagnostics TroubleshootingIgnition Control Diagnostic Fault Code Storage and RetrievalFurnace Control Event Schedule Section III Replacement Parts List AIR Moving Model no Description Used with Replacement Part Contact InformationSection IV Wiring Diagram UUM-A-0407 UUM-A-0407 Unitary Products Group Unitary 5005 Norman Products York Group Drive 73069 Exclusions80%

LL8V*DH, LC8V*DH, FL8V*DH, FC8V*DH, PV8*DH specifications

The York FL8V*DH, LC8V*DH, PV8*DH, LL8V*DH, and FC8V*DH series represent a range of advanced heating and cooling solutions tailored to meet the needs of both residential and commercial applications. These units are engineered with cutting-edge technologies that enhance energy efficiency, performance, and user comfort, making them a top choice for HVAC needs.

One of the standout features of these systems is their high-efficiency design, which often exceeds industry standards. The FL8V*DH, for example, boasts an impressive SEER (Seasonal Energy Efficiency Ratio) rating, allowing users to save on energy costs while ensuring optimal heating and cooling comfort. The innovative design minimizes energy consumption without compromising performance, which is critical in today’s eco-conscious market.

Another hallmark of these series is their use of advanced refrigerant technology. Utilizing environmentally friendly refrigerants, such as R-410A, these units deliver excellent heat transfer while reducing the overall carbon footprint. This focus on sustainability ensures that customers can feel good about their choice, contributing positively to the environment.

The technology behind these models extends to their variable-speed blower motors, which provide precise airflow and temperature control. This flexibility allows adjustments based on real-time demand, enhancing comfort and reducing energy usage. The use of smart thermostats with these systems enables users to program schedules, monitor usage, and optimize settings remotely, further improving efficiency.

In terms of durability and reliability, the York series is built from high-quality materials designed to withstand the test of time. Robust construction minimizes maintenance needs, resulting in lower long-term ownership costs. Additionally, many units feature quiet operation technologies, ensuring minimal noise disturbance, which is particularly important in residential settings.

Moreover, installation and servicing of the York FL8V*DH, LC8V*DH, PV8*DH, LL8V*DH, and FC8V*DH systems are made simpler through their user-friendly designs. Easy access points for maintenance staff help to reduce downtime and enhance system longevity.

Overall, the York FL8V*DH, LC8V*DH, PV8*DH, LL8V*DH, and FC8V*DH units stand out due to their efficiency, innovative technology, durability, and user-friendly design, marking them as exceptional choices in the HVAC market. These systems not only provide comfort but also align with energy-saving initiatives, making them a wise investment for the future.