Toshiba LF232*F specifications External Connections, Wiring Precautions

Page 6

TIC-LF502A

External Connections

Terminal box

wire

5.5mm2 or more

Grounded with 100Ω or less ground resistance

Thick walled steel conduit

Detector

Signal cable

(2-wire shielded hard-rubber sheathed cable)

Excitation cable

(3-wire hard-rubber sheathed cable) Output cable (CVV-S)

Digital I/O cable (CVV-S)

Power supply (CVV)

Power supply

Current output (4 to 20mA)

Digital input 2 (opt.)

Digital input 1 (opt.) (20 to 30 Vdc)

Digital output 4 (opt.) Digital output 3 (opt.) Digital output 2 (opt.)

Digital output

Figure 6. LF502/LF232*F flowmeter Wiring Diagram

Wiring Precautions

(1)Be sure to use thick walled steel conduit (22 mm) for signal and excitation cable wiring between the detector and converter. The conduit screw is R (PT)1/2. Use flexible conduits at the cable outlets of the detector as needed.

(2)Make the grounding wire as short as possible. Do not use a common ground shared with other equipment where earth current may flow. An independent earth ground is recommended.

(3)The meter may affect its accuracy when the electric potential of measurement fluid is unstable condition.

Make the piping of the upstream side and downstream side the same material.

When the material of next pipes are conductive like metal, use a 5.5mm2 or larger core cable for grounding of detector and wire it at 2 places as follows.

Between Grounding terminal at detector body and Grounding ring at upstream side.

Between Grounding terminal at detector body and Grounding ring at downstream side.

non-conductive like plastic, use a 5.5mm2 or larger core cable for grounding of detector and wire 1 place as follows.

Between Grounding terminal at detector body and Grounding (100 ohm or less).

(4)DO1 to DO4 and DI1 to DI2 use the same common terminal (COM). This COM can not connect to other instruments that have their own ground terminal (Power supply for connecting to DI or DO, etc...). Need to wire separately.

• When the material of next pipes are

6

Image 6
Contents Measurement range Overall SpecificationsAccuracy ±2% FS when measurement range is standard Flowmeter from a remote placeModel LF502 Detector Model LF232*F converterPreset point output Rage switching outputHigh/low limit alarm output Converter error alarmAnsi 150 flange dimensions InstallationDimensions Separate type LF502 Meter size 6 JIS 10K flange dimensionsDimensions Installation methodWiring Precautions External ConnectionsAbout establishment environment Piping PrecautionsFlange connection Ordering InformationSpecification Code for LF502 detector Code explanation Standard Option