York DM 060, DM072, DM 048, DM 036 warranty Static Resistances, Electric Heater CFM Limitations

Page 21

036-21502-002-A-0303

TABLE 14: STATIC RESISTANCES

 

 

 

 

 

 

RESISTANCE, IWG

 

 

 

 

DESCRIPTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

1200

1400

1600

1800

2000

2200

2400

2600

2800

3000

 

 

 

 

 

 

 

 

 

 

 

 

ECONOMIZER1 2

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

0.30

ELECTRIC

5-15KW

0.04

0.05

0.06

0.07

0.08

0.10

0.12

0.14

0.16

0.19

0.22

HEATERS3

 

 

 

 

 

 

 

 

 

 

 

 

20-30KW

0.06

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

BOTTOM DUCT CONNECTIONS1

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.14

0.16

0.19

0.22

COOLING ONLY2

0.08

0.10

0.12

0.14

0.16

0.18

0.20

0.23

0.26

0.29

0.32

1.Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.

2.The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

3.Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.

TABLE 15: ELECTRIC HEATER CFM LIMITATIONS

UNIT MODEL SIZE NOMINAL

 

 

 

MINIMUM SUPPLY AIR CFM

 

 

VOLTAGE

 

 

 

 

 

 

 

 

HEATER SIZE NOMINAL KW

 

 

TONS

 

 

 

 

 

 

 

 

 

 

 

 

 

5

7

10

15

20

30

 

208/230-1-60

1100

1100

1200

1200

1300

-

3

208/230-3-60

1100

1100

1200

1200

1300

-

460-3-60

-

1100

1200

1200

1300

-

 

 

 

 

 

 

 

 

 

 

575-3-60

-

-

1200

1200

1300

-

 

208/230-1-60

1300

1300

1300

1300

1300

-

4

208/230-3-60

1300

1300

1300

1300

1300

-

 

 

 

 

 

 

 

460-3-60

-

1300

1300

1300

1300

-

 

 

 

 

 

 

 

 

 

 

575-3-60

-

-

1300

1300

1400

-

 

 

 

 

 

 

 

 

 

208/230-1-60

1600

1600

1600

1600

1600

1600

 

 

 

 

 

 

 

 

5

208/230-3-60

1600

1600

1600

1600

1600

1600

 

 

 

 

 

 

 

460-3-60

-

1600

1600

1600

1600

1600

 

 

575-3-60

-

-

1600

1600

1600

1800

 

208/230-1-60

1800

1800

1800

1800

1800

1800

 

 

 

 

 

 

 

 

6

208/230-3-60

1800

1800

1800

1800

1800

1800

 

 

 

 

 

 

 

460-3-60

-

1800

1800

1800

1800

1800

 

 

575-3-60

-

-

1800

1800

1800

1800

Unitary Products Group

21

Image 21
Contents Description SimplicityTable of Contents Product Nomenclature Ton Sunline Model Number Nomenclature 048 N04Product Nomenclature Panels Johnson UNT Controller, DFS, APS & Phase Monitor Technicoat Condenser Coil & Dirty Filter Switch Simplicity FeaturesUnit Cutaway FACTORY-INSTALLED OptionsFIELD-INSTALLED Accessories Sound Power RATING1 Capacity Ratings ARI 210/2401GAS Heat RATINGS1 DM036 Cooling Capacities 3 TON DM048 Cooling Capacities 4 TON DM060 Cooling Capacities 5 TON DM072 Cooling Capacities 6 TON 036-21502-002-A-0303 036-21502-002-A-0303 036-21502-002-A-0303 036-21502-002-A-0303 MED Belt Drive Blower Motor and Drive DataElectric Heater CFM Limitations Static ResistancesRLA LRA FLA RLA LRA 036-21502-002-A-0303 036-21502-002-A-0303 036-21502-002-A-0303 036-21502-002-A-0303 036-21502-002-A-0303 036-21502-002-A-0303 Voltage LIMITATIONS1 Physical DataTypical Control Wiring Typical Power WiringUnit Dimensions 3 6 TON COOLING/GAS Heat Front View Unit with Economizer Rainhood Minimum Clearances Unit Dimensions Rear ViewTypical Applications Center of Gravity DM 6 Point Loads Weight DistributionRoof Curb Dimensions Operating Weights LBSGuide Specifications GeneralDescription Unit Controls Manual Outdoor AIR Damper