036-21502-002-A-0303

TABLE 24: PHYSICAL DATA

 

MODELS

 

 

DM

 

 

 

 

 

 

 

 

 

036

048

 

060

072

 

 

 

 

 

 

 

EVAPORATOR

Centrifugal Blower (Dia. x Wd. in.)

12 X 10

12 X 10

 

12 X 10

12 X 11

 

 

 

 

 

 

Fan Motor HP (Direct Drive)

1/2

3/4

 

1

1

BLOWER

 

 

 

 

 

 

 

 

Fan Motor HP (Belt Drive)

1 1/2

1 1/2

 

1 1/2

1 1/2

 

 

 

 

 

 

 

EVAPORATOR

Rows Deep

3

3

 

3

4

 

 

 

 

 

 

Fins Per Inch

13

13

 

13

13

COIL

 

 

 

 

 

 

 

Face Area (Sq. Ft.)

3.6

4.3

 

5.1

5.1

 

 

 

 

 

 

 

 

 

CONDENSER

Propeller Dia. (in.)

24

24

 

24

24

 

 

 

 

 

 

Fan Motor Hp

1/4

1/4

 

1/4

1/4

FANS

 

 

 

 

 

 

 

Nom. CFM

3400

3400

 

3400

3400

 

 

 

 

 

 

 

 

 

CONDENSER

Rows Deep

1

1

 

1

2

 

 

 

 

 

 

Fins Per Inch

16

16

 

22

16

COILS

 

 

 

 

 

 

 

Face Area (Sq. Ft.)

17.1

17.1

 

17.1

16.7

 

 

 

 

 

 

 

 

 

COMPRESSOR

Scroll Type

1

1

 

1

1

(Qty. Per Unit)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR

Quantity Per Unit (15” X 20” X 1” or 2“)

2

2

 

2

2

 

 

 

 

 

 

Quantity Per Unit (14” X 25” X 1” or 2“)

1

1

 

1

1

FILTERS

 

 

 

 

 

 

 

 

Total Face Area (sq. ft.)

6.3

6.3

 

6.3

6.3

 

 

 

 

 

 

 

CHARGE

Refrigerant 22

5/8

6/8

 

6/8

10/0

(lbs./oz.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 25: ELECTRIC HEAT CORRECTION FACTORS

NOMINAL VOLTAGE

VOLTAGE

kW CAP. MULTI-

PLIER

 

 

 

 

 

208

208

1.00

 

 

 

240

230

0.92

 

 

 

480

460

0.92

 

 

 

600

575

0.92

 

 

 

TABLE 26: VOLTAGE LIMITATIONS1

POWER SUPPLY

 

VOLTAGE

 

 

 

 

MIN.

 

MAX.

 

 

 

 

208/230-3-60

187

 

253

 

 

 

 

460-3-60

414

 

506

 

 

 

 

575-3-60

518

 

506

 

 

 

 

1.Utilization Range “A” in accordance with ARI Standard 110.

30

Unitary Products Group

Image 30
Contents Simplicity DescriptionTable of Contents Ton Sunline Model Number Nomenclature 048 N04 Product NomenclatureProduct Nomenclature Panels Johnson UNT Controller, DFS, APS & Phase Monitor Technicoat Condenser Coil & Dirty Filter Switch Features SimplicityFACTORY-INSTALLED Options Unit CutawayFIELD-INSTALLED Accessories Sound Power RATING1 Capacity Ratings ARI 210/2401GAS Heat RATINGS1 DM036 Cooling Capacities 3 TON DM048 Cooling Capacities 4 TON DM060 Cooling Capacities 5 TON DM072 Cooling Capacities 6 TON 036-21502-002-A-0303 036-21502-002-A-0303 036-21502-002-A-0303 036-21502-002-A-0303 Belt Drive Blower Motor and Drive Data MEDStatic Resistances Electric Heater CFM LimitationsRLA LRA FLA RLA LRA 036-21502-002-A-0303 036-21502-002-A-0303 036-21502-002-A-0303 036-21502-002-A-0303 036-21502-002-A-0303 036-21502-002-A-0303 Physical Data Voltage LIMITATIONS1Typical Power Wiring Typical Control WiringUnit Dimensions 3 6 TON COOLING/GAS Heat Front View Unit with Economizer Rainhood Unit Dimensions Rear View Minimum ClearancesTypical Applications DM 6 Point Loads Weight Distribution Center of GravityOperating Weights LBS Roof Curb DimensionsGuide Specifications GeneralDescription Unit Controls Manual Outdoor AIR Damper