York CU060 - 300 manual HOT Water & Steam Heating Coils Performance Data

Page 25

271846-YTG-B-0208

Steam Coil Performance @ 2 PSIG

Unit Model

CFM

Entering Air Dry Bulb Temperature

 

 

 

 

10

30

50

70

 

 

 

 

 

 

 

 

 

1800

140

126.6

113.1

99.7

CU060

2000

147.1

133

118.8

104.7

 

2200

153.6

138.9

124.1

109.3

 

3000

258.3

233.4

208.6

183.8

CU096

3200

266.6

241

215.3

189.7

 

3400

274.5

248.1

221.8

195.4

 

3600

282.1

255

227.9

200.8

CU120

4000

296.3

267.9

239.4

210.9

 

4400

309.5

279.8

250.1

220.3

 

5400

425.8

384.9

344

303.1

CU180

6000

447.4

404.4

361.4

318.4

 

6600

467.3

422.4

377.5

332.6

 

7200

569.6

514.9

460.2

405.5

CU240

8000

598.5

541

483.5

426

 

8800

625.3

565.2

505.1

445.1

 

9000

645.8

583.7

521.7

459.6

CU300

10000

677.1

612.1

547

481.9

 

11000

706.1

638.2

570.4

502.6

Steam Heating Coils are tube-in-tube ‘steam distributing’ type to eliminate risk of con- densate freezing.

Coils are constructed of 5/8 inch diameter outer copper tubes, with 3/8 inch diameter inner tubes. The outer tube is mechanically bonded to rippled aluminum plate fins. Coil casing is fabricated of heavy gauge galvanized sheet. Copper headers are complete with MPT connections.

All coils are 1 row, 8 fins per inch.

Hot Water Coil Performance

Unit Model

GPM

CFM

 

Temperature Difference*

 

 

 

 

 

 

 

70

 

90

110

 

130

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1800

62.4

 

80.8

99.3

 

117.8

CU060

10

 

 

 

 

 

 

 

2000

66.2

 

85.9

105.5

 

125.3

 

 

2200

69.9

 

90.6

111.4

 

132.3

 

 

 

 

 

 

 

 

 

 

 

3000

111.6

 

144.3

177.1

 

209.9

CU096

15

 

 

 

 

 

 

 

3200

116

 

150.1

184.1

 

218.3

 

 

3400

120.2

 

155.5

190.9

 

226.3

 

 

 

 

 

 

 

 

 

 

 

3600

124.3

 

160.8

197.3

 

234

CU120

15

 

 

 

 

 

 

 

4000

131.9

 

170.7

209.6

 

248.6

 

 

4400

138.9

 

179.9

220.9

 

262

 

 

 

 

 

 

 

 

 

 

 

5400

183.5

 

237.3

291.2

 

345.2

CU180

20

 

 

 

 

 

 

 

6000

194.6

 

251.7

308.9

 

366.2

 

 

6600

204.8

 

265

325.3

 

385.7

 

 

 

 

 

 

 

 

 

 

 

7200

257.6

 

332.7

407.9

 

483.2

CU240

35

 

 

 

 

 

 

 

8000

274.2

 

354.2

434.3

 

514.6

 

 

8800

289.6

 

374.3

459

 

543.9

 

 

 

 

 

 

 

 

 

 

 

9000

313.2

 

404.3

495.5

 

586.8

CU300

50

 

 

 

 

 

 

 

10000

333.6

 

430.7

527.9

 

625.3

 

 

11000

352.5

 

455.3

558.2

 

661.2

 

 

 

 

 

 

 

 

 

* Temperature difference between entering water and entering air temperature.

Hot Water Heating Coils are constructed of 1/2 inch diameter copper tubes, mechanically bonded to rippled aluminum plate fins. Coil casing is fabricated of heavy gauge galvanized sheet. Copper tube headers are complete with MPT connections.

All coils are 2 row, 8 fins per inch.

CU240 - 300

CU060 - 180

FIGURE 10 - HOT WATER & STEAM HEATING COILS PERFORMANCE DATA

Johnson Controls Unitary Products

25

Image 25 Contents
Single Package AIR Conditioning Water Cooled Table of Contents General DescriptionOversized Evaporator FAN Motors ANTI-SHORT Cycle TimerCorrosion Resistant Coatings Stainless Steel Drain PANCondenser-Type General Data CH060-120 5-10 TON Horizontal ModelsGeneral Data CU 5-25 TON Vertical Models RPM BHP CU060 Supply AIR Blower Performance CU300, 25 TON Vertical ModelWaterside Pressure Drop CU Models Water Pressure Drop Data CH Models EDB Cooling Performance Data CH 5-10 TON Horizontal ModelsCooling Performance Data CU 5-20 TON Vertical Models PD PSI Cooling Performance Data CU 25 TON Vertical ModelsEWT F Total Sensible Standard Motors CU 5-25 TON ModelsStandard Motors CH 5-10 TON Models Oversized Motors CU 5-25 TON ModelsOversized Motors CH 8-10 TON Models Dimensional Data CH 5 TON Horizontal Model Dimensional Data CH 8 & 10 TON Horizontal Models Filter Frame Water Side View Electrical Connections Supply AIR Dimensional Data CU 15 TON Vertical Model Dimensional Data CU 20 TON Vertical Model Dimensional Data CU 25 TON Vertical Model Supply AIR/RETURN AIR Configuration HOT Water & Steam Heating Coils Dimensional Data HOT Water & Steam Heating Coils Performance Data Typical WATER-SIDE Economizer Physical Configuration Typical WATER-SIDE Economizer Piping Schematic Johnson Controls Unitary Products York Drive Norman, OK