TABLE 3: SUPPLY AIR BLOWER PERFORMANCE
|
|
|
|
|
|
| EXTERNAL STATIC PRESSURE - Inches W.C. |
|
|
|
|
| |||||||
MODEL # | SUPPLY CFM | 0.2 | 0.4 | 0.6 | 0.8 | 1.0 | 1.2 | 1.4 | 1.6 | 1.8 | |||||||||
|
| RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP |
| 1800 | 846 | 0.41 | 936 | 0.48 | 1024 | 0.56 | 1107 | 0.64 | 1195 | 0.74 | 1259 | 0.82 | 1325 | 0.90 | 1400 | 0.99 | - | - |
CH060 | 2000 | 917 | 0.54 | 999 | 0.62 | 1079 | 0.71 | 1157 | 0.79 | 1233 | 0.89 | 1305 | 0.98 | - | - | - | - | - | - |
| 2200 | 994 | 0.70 | 1069 | 0.79 | 1142 | 0.88 | 1214 | 0.98 | - | - | - | - | - | - | - | - | - | - |
| 3000 | 810 | 0.65 | 900 | 0.78 | 986 | 0.91 | 1066 | 1.04 | 1143 | 1.17 | 1221 | 1.32 | 1294 | 1.48 | 1363 | 1.63 | 1433 | 1.79 |
CH096 | 3200 | 851 | 0.78 | 938 | 0.91 | 1018 | 1.04 | 1095 | 1.18 | 1170 | 1.32 | 1236 | 1.42 | 1305 | 1.56 | 1380 | 1.74 | 1447 | 1.90 |
| 3400 | 892 | 0.91 | 974 | 1.05 | 1051 | 1.19 | 1125 | 1.33 | 1196 | 1.48 | 1266 | 1.64 | 1320 | 1.81 | 1390 | 1.90 | - | - |
| 3600 | 927 | 1.05 | 1006 | 1.20 | 1081 | 1.34 | 1152 | 1.50 | 1220 | 1.65 | 1287 | 1.81 | 1353 | 1.98 | 1405 | 2.07 | 1472 | 2.17 |
CH120 | 4000 | 1012 | 1.40 | 1085 | 1.56 | 1153 | 1.73 | 1220 | 1.89 | 1283 | 2.06 | 1345 | 2.23 | 1405 | 2.41 | 1464 | 2.59 | 1522 | 2.78 |
| 4400 | 1100 | 1.83 | 1166 | 2.00 | 1230 | 2.18 | 1292 | 2.37 | 1351 | 2.55 | 1410 | 2.74 | 1466 | 2.92 | - | - | - | - |
NOTE:
1.At higher evaporator airflows, and wet bulb conditions condensate
2.Values include pressure drop from wet coil and clean filters.
3.Shaded areas indicate oversize motors.
Johnson Controls Unitary Products | 7 |