DESCRIPTION
These units are completely assembled, piped, wired, charged and tested at the factory and are shipped ready for immediate installation. Only the power supply wiring, the thermostat wir- ing, the condenser water piping, the condensate drain piping and the ductwork are required to complete the installation.
Units include a
APPLICATION FLEXIBILITY
These “cooling only” units can be applied with:
1.Cooling towers.
2.Well or surface water providing the temperature and the GPM of the water meet the application limitations of the unit.
3.Brackish or salt water and a secondary heat exchanger. They can be installed:
1.Within the conditioned space as “free standing” units without any ductwork. Supply air plenum and return air grille accessories are available for these freestanding applications.
2.In an equipment room with both supply and return air ductwork
GENERAL
Horizontal (CH) units are designed for suspended mounting. HWC models are shipped with
All models 5
CABINET
All cabinets are completely constructed of 18 Ga. corrosion resistant "Galvalume" coated steel. The entire unit interior (both evaporator and condensing section) is insulated with 1/2" thick, 2 lbs. density insulation. Service panels are equipped with lifting handles for ease of removal and han- dling. Duct flanges for return air intake and evaporator dis-
charge are provided with the unit, for field installation. Duct flange on CU240 & CU300 evaporator return is incorporated into the filter frame.
REFRIGERATION CIRCUITS
All models utilize "Scroll" type hermetic compressors. Com- pressors are mounted on rubber isolators to minimize vibra- tion transmission. Internal overload protection is provided.
External high pressure and low pressure cutout switches are included in each compressor control circuit. The 5 ton units have a single refrigeration circuit. The 8
The evaporator coils are constructed of internally enhanced copper tubes mechanically bonded to rippled aluminum plate fins. The evaporator coil is employed in a
The
INDOOR FANS
Forward curved, double inlet and double width centrifugal blowers are used for evaporator air movement. Large diame- ter wheels are employed to provide required airflow perfor- mance at minimum rpm and noise levels. Blower wheels are fabricated of galvanized steel. Blowers employ solid steel shafts, supported in permanently lubricated ball bearings. All blowers are belt driven.
ELECTRICAL/CONTROLS
All units are completely factory wired with all necessary con- trols. Manual reset protection is provided on evaporator blower motors. A manual reset circuit is also provided on each compressor control circuit in the event of high/low pres- sure cutout. A 24 volt control circuit, with oversize trans- former, is provided for field connection. Units are designed to operate with conventional thermostat control interface.
FILTERS
All models are shipped with 2 inch thick
Johnson Controls Unitary Products | 3 |