Service Reference Manual

TROUBLESHOOTING

9-9

Performance

Performance Checkout

HW/HWC chassis come with a pre-charged chassis assembly. The chassis assembly is designed in a way that the unit may be run indepen- dently of the HWC unit. When the chassis is run on a floor or bench, the performance measurements will be affected due to the change in static pressures, recirculated air, excessive temperatures and equal ambient temperatures from indoor to outdoor.

Two sets of tables are provided in this section to address these issues. Tables 9-1 to 9-4 are to be used when the chassis is still installed in the complete unit. Tables 9-5 and 9-6 are to be used when the chassis is run independently outside of the unit.

Note: Pressures may vary +/– 10 psi. Temperatures may vary =/– 2-3°F.

Performance Tests (Chassis Installed in Unit)

TABLE 9-1

HWC122 Performance Test (Chassis Installed)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Air Temperature Entering Outdoor Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85°

 

 

95°

 

 

105°

 

 

115°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter.

Total

Suction

Suction

Liquid

Suction

Suction

Liquid

Suction

Suction

Liquid

Suction

Suction

Liquid

Air Vol.

DB/WB

Pressure

Temp.

Temp.

Pressure

Temp.

Temp.

Pressure

Temp.

Temp.

Pressure

Temp.

Temp.

 

 

(CFM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

81

49

87

82

49

97

84

50

107

85

51

117

75°/63°

 

450

83

54

87

84

50

97

86

51

107

87

52

117

 

 

500

85

60

87

86

52

97

88

52

107

89

53

117

 

 

400

87

63

87

88

53

97

89

53

107

91

54

117

80°/67°

 

450

88

68

88

90

58

97

91

54

107

93

55

117

 

 

500

90

73

88

92

63

97

93

57

107

95

56

117

85°/71°

 

400

92

74

88

93

64

97

94

56

108

96

57

117

 

 

450

94

79

88

95

71

97

96

62

108

98

58

117

 

 

500

96

84

88

97

74

97

98

65

108

100

59

117

Based on a normally installed cooling chassis

 

 

 

 

 

 

 

 

TABLE 9-2

HWC182 Performance Test (Chassis Installed)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Air Temperature Entering Outdoor Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85°

 

 

95°

 

 

105°

 

 

115°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter.

Total

Suction

Suction

Liquid

Suction

Suction

Liquid

Suction

Suction

Liquid

Suction

Suction

Liquid

Air Vol.

DB/WB

Pressure

Temp.

Temp.

Pressure

Temp.

Temp.

Pressure

Temp.

Temp.

Pressure

Temp.

Temp.

 

 

(CFM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

550

80

49

96

81

48

106

84

50

114

86

51

123

75°/63°

 

600

82

54

96

83

50

106

86

51

114

88

52

123

 

 

650

84

59

96

85

52

106

88

52

114

90

54

124

 

 

550

86

62

98

88

53

106

90

54

115

92

55

124

80°/67°

 

600

87

67

98

89

58

107

91

54

116

94

56

125

 

 

650

99

72

98

91

62

107

93

57

116

95

56

125

85°/71°

 

550

91

73

99

93

64

107

95

56

116

97

58

125

 

 

600

93

78

99

95

70

108

97

63

117

99

59

126

 

 

650

95

83

99

97

74

108

99

66

117

101

60

126

Based on a normally installed cooling chassis

Page 194
Image 194
Armstrong World Industries 242 HWC122 Performance Test Chassis Installed, HWC182 Performance Test Chassis Installed