Service Reference Manual
8.When the call for heat is satisfied, the circuit be- tween R and W is interrupted,
9.With W
10.The blower control board starts a
FLAME SENSE
1.During a call for heat, the spark terminal is ener- gized and the gas valve is opened to light the burners.
2.The ignition control energizes the spark terminal and the gas valve for approximately six seconds. If a flame is not sensed in this time period, the igni- tion control
3.Since the
4.The induced draft blower continues to run for approximately 30 seconds, then another trial for ignition begins.
5.The ignition control runs three trials for ignition. If a flame is not sensed during these three trials, the ignition control will lockout.
6.The circulating air blower continues to run until the
7.The ignition control remains in lockout until
LIMIT OPENS
If the limit switch opens for any reason during a call for heat, the following happens:
1.If the limit switch senses that the temperature in the unit is too high, the contacts between terminals C and NC on the limit switch open and the con- tacts between C and NO close. This interrupts the
2.When the limit switch senses that the tempera- tures in the unit are normal, the contacts between terminals C and NO open, the contacts between terminals C and NC close and the operation of the unit returns to normal.
SEQUENCE OF OPERATIONS
PRESSURE SWITCH OPENS (BLOCKED FLUE)
1.If blockage of the flue occurs, negative pressure in the induced draft blower is reduced. At the set point of the pressure switch, the contacts open.
This interrupts the
2.Terminal W on the blower control board stays energized and the circulating air blower contin- ues to run. If negative pressure is restored, the pressure switch closes and sends a
ROLLOUT SWITCH ACTIVATED
1.If conditions in the burner compartment cause the rollout switch to trip, the contacts on the switch open, interrupting the
2.The reason the rollout switch was tripped must be determined before any corrective action is taken.
3.The signal to terminal P.SW can only be restored if the rollout switch is reset, which can only be done manually. The W terminal on the blower control board remains energized and the circulating air blower continues to operate. Once the rollout switch is reset, the operation of the unit returns to normal.