Service Reference Manual

UNIT COMPONENTS

5-7

Heatcraft Model IBC-H4C401

Blower Control Board Specifications Manufacturer: United Technologies Model: 1010-611

Armstrong P/N 39029B002 Operating Voltage: 18-30VAC 60 Hz 60 Hz Power Requirement: 4 VA max. Operating Temperature: – 40°F to +170°F

Wiring Connections: All Male .250" x .032" Quick Connect Tabs

Performance Specifications (all timings +/– 1 second):

Heating: On Delay Timing - 60 seconds

Off Delay Timing - 90 seconds

Cooling: On Delay Timing - 15 seconds

Off Delay Timing - 90 seconds

Heating and Cooling Output Rating:

12 F.L.A., 30 L.R.A. at 120VAC for 100,000 Cycles

10 F.L.A., 30 L.R.A. at 240VAC for 100,000 Cycles

Both heat and cool outputs cannot be energized simultaneously.

Cool Speed

L1 Power Out

Heat Speed

L1 Power Out

HEAT

 

L1 Line Voltage

 

COOL

M2

 

Dumb Terminal

L1

HEATCRAFT

(Park)

M1

 

W C R G

Dumb Terminal (Park)

24 VAC Heat Call

24 VAC (Fan On/Cooling Fan Auto)

 

24 VAC Common

24 VAC Power

 

FIGURE 5-5 Heatcraft Blower Control Board IBC-H4C401

SRM-HW/HWC 2/99

Page 70
Image 70
Armstrong World Industries 182, 243, 302, 242, 122 Heatcraft Model IBC-H4C401, 5 Heatcraft Blower Control Board IBC-H4C401