INSTALLATION

Magic-Pak: HW/HWC

6-12

See Table 6-3 and the Specifications section beginning on page 1-1 for correct wire ampacity for the cooling chassis required, and size the wire accordingly.

For HW (heating only units): When sizing wire, keep in mind that an air conditioning chassis may be added in the future.

TABLE 6-3

Minimum Circuit Ampacity

 

 

Clg. Chassis Model

Min. Circuit Ampacity

 

 

 

 

18A

16

 

 

 

 

24A

24

 

 

 

 

30A

27

 

 

 

 

181

13.3

 

 

 

 

241

21

 

 

 

 

301

23.6

 

 

122, 123

8.3

 

 

182, 183

13.6 Rotary/15.4 Scroll

 

 

242, 243

18.6

 

 

302, 303

22.4

 

 

 

Thermostat

Install the thermostat according to the directions furnished with it. The thermostat must be located on an inside wall where it will not be affected by drafts, sunlight or any other heat producing appliances. Connect the thermostat wires to the low voltage leads on top of the unit following the wiring diagram attached to the unit. The heat anticipator setting is 0.50 Amp.

Supply and Return Ducts

Provide ducts sized sufficiently to handle the larger of the air volumes for heating or cooling provided by the unit.

Connect the supply duct to the top of the unit using canvas connections or other flexible connections to prevent noise transmission into the duct system.

The supply duct should have a removable access panel. The opening should be accessible when the furnace is installed and should be large enough and located such that the heat exchanger can be inspected for leaks. The cover must be attached in such a manner as to prevent air leaks.

To connect the return duct to the system, use a straight piece of duct 22"

 

wide by 6" deep. Insert the duct into the return opening in the bottom of

SRM-

the unit and flange the duct over the existing flanges around the opening

 

HW/HWC

8/99

Page 119