Service Reference Manual

UNIT COMPONENTS

 

 

5-9

 

 

 

Diagnostics (Fenwal Triton 2461D)

 

 

 

 

 

 

 

 

 

 

 

1. Diagnostic LED flash rate is 1/4 second “ON”, 1/4 second “OFF”

 

 

 

followed by up to four seconds “OFF” before repeating the code.

 

 

 

2. Only one code is displayed at a time.

 

 

 

3. During a “STEADY ON” code, the LED may blink off momentarily.

 

 

 

4. Diagnostic codes may be reset by removing the power from the

 

 

 

control for three seconds, then reapplying power. (Cycle thermostat

 

 

 

“OFF” for three seconds, then back “ON”.)

 

 

 

The following ignition control board LED codes indicate normal or

 

 

 

abnormal operations:

 

TABLE 5-1

Triton 2461D Diagnostic Flash Code

 

 

 

 

 

 

This code is used for up to four seconds at startup each time the control is powered to

 

 

STEADY ON

indicate that the control is performing a self diagnostic check. If a problem is detected, the

 

 

 

self diagnosis will repeat for a total of five times which equals twenty seconds. If LED is on

 

 

 

steady for 20 seconds, this indicates a control failure.

 

 

 

 

 

 

 

Indicates an air flow fault. Used only on models with a pressure switch input (PSW). This

 

 

 

code is active only if the PSW input is in the improper state after a predetermined time delay.

 

 

 

For example: If the PSW input was powered when the call for heat begins (closed contacts),

 

 

ONE FLASH

the control will allow a fixed time for the PSW input to go off otherwise the LED flash will

 

 

 

commence. Conversely, if he PSW input is not powered within a fixed delay time after the

 

 

 

inducer motor is energized, the LED flash will commence. If the PSW input is removed

 

 

 

during a heating cycle, power will be removed from the gas valve immediately. If the PSW

 

 

 

power input is not reapplied within a fixed time, the LED flash will commence.

 

 

 

 

 

 

 

Indicates a flame detected out of sequence or with no call for heat. LED will flash twice as

 

 

TWO

soon as flame is detected out of sequence and continue as long as the flame is present.

 

 

FLASHES

Controls with an inducer control circuit will also power the inducer circuit when flame is

 

 

 

detected out of sequence.

 

 

 

 

 

 

THREE

Indicates ignition lockout after all ignition tries have been completed. This code will continue

 

 

as long as the call for heat remains. On models equipped with one hour automatic reset, the

 

 

 

 

FLASHES

 

 

code will stop when a new ignition attempt begins.

 

 

 

 

 

 

 

 

 

 

 

 

 

SRM-HW/HWC 2/99