Armstrong World Industries 123, 243 5-13, United Technologies Model 1097-400-1 cont, Heat Mode

Models: 183 182 203 123 122 242 302 243

1 196
Download 196 pages 63.09 Kb
Page 76
Image 76

Service Reference Manual

UNIT COMPONENTS

 

 

5-13

United Technologies Model 1097-400-1 (cont.)

 

 

Heat Mode

 

 

 

Pre-purge

30 seconds

Inter-purge

30 seconds

Post-purge

5 seconds

Trial Time

10 seconds

# of Trials

3

 

 

Board to reset from lockout after 60 minutes.

Fan On Delay

 

Cool

5 seconds (fixed)

Heat

30 seconds (fixed)

Fan Off Delay

 

Cool

90 seconds (fixed)

Heat

120 seconds (fixed)