UNIT COMPONENTS

 

Magic-Pak: HW/HWC

5-22

 

 

TABLE 5-4

Pressure Switches

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Armstrong

Vendor

Model Number

Switch Opens

Color

 

 

 

P/N

 

 

(inches W.C.)

Code

 

 

 

 

 

 

 

41862-001

Tridelta Industries

FS6080A-1889

.40

Red

 

 

 

 

 

 

 

41862-002

Tridelta Industries

FS6080A-1891

.27

Green

 

 

 

 

 

 

 

41862-003

Tridelta Industries

FS6080A-1890

.45

White

 

 

 

 

 

 

 

44819-001

Tridelta Industries

PPS10090-2614

.25 +/– .05

Purple

 

 

 

 

 

 

 

44819-002

Tridelta Industries

PPS10090-2615

.35 +/– .05

Blue

 

 

 

 

 

 

 

44819-003

Tridelta Industries

PPS10090-2616

.45 +/– .05

Pink

 

 

 

 

 

 

 

44819-004

Tridelta Industries

PPS10090-2617

.55 +/– .05

Red

 

 

 

 

 

 

 

44819-005

Tridelta Industries

PPS10090-2618

.60 +/– .06

Green

 

 

 

 

 

 

 

44819-006

Tridelta Industries

PPS10090-2619

.70 +/– .06

White

 

 

 

 

 

 

 

44819-007

Tridelta Industries

PPS10090-2620

.80 +/– .07

Gray

 

 

 

 

 

 

 

44819-008

Tridelta Industries

PPS10090-2621

.50+/– .05

Red

 

 

 

 

 

 

 

44819-009

Tridelta Industries

PPS10090-2622

.30 +/– .05

Orange

 

 

 

 

 

 

 

44819-010

Tridelta Industries

PPS10090-2623

.10 +/– .05

Yellow

 

 

 

 

 

 

 

44819-011

Tridelta Industries

PPS10090-2624

.40 +/– .05

Light Blue

 

 

 

 

 

 

 

44819-012

Tridelta Industries

PPS10090-2625

.65 +/– .05

Brown

 

 

 

 

 

 

 

 

Pressure Switch Problems

The negative pressure developed in the combustion chamber is directly related to airflow. During furnace operation, the switch will react to conditions that reduce airflow, such as: blocked or restricted intake (combustion air piping), blockage of vent (flue) piping, blockage of the condensate drain piping, plugged pressure tap ports, leaking hoses or a failure of the induced draft blower motor.

If the pressure switch has already been replaced and problems are still being experienced, follow the procedure, Checking Pressure Switch Operation (found on page 5-24).

If the measured static pressure reading does not meet the switch specifi- cations, check these items:

1.Pressure switch hose/tubing for cracks or loose connections

2.Induced draft blower wheel for corrosion or loose blades

3.Induced draft blower for tight bearings or loose inducer wheel

SRM-HW/HWC

2/99