1 of 4
PROJECT:
TAG:
Gross Cooling Capacity [Btuh]: | 186,000* |
Design CFM: | 6,000 |
Energy Efficiency Ratio: | 9.80 EER** |
Net Cooling Capacity [Btuh]: | 178,000** |
Net Cooling CFM: | 5,500 |
|
|
Evaporator Fan No./Type: | 2/CENTRIFUGAL |
Diameter x Width [in]: | 15x9 |
Drive: | Adjustable Belt |
Motor HP : | 5.0 / NA |
[Standard/Oversized] |
|
|
|
Condenser Fan No./Type: | 2/CENTRIFUGAL |
Diameter x Width [in]: | 15x15 |
Drive: | Adjustable Belt |
Motor HP : | 5.0 |
[Standard] |
|
|
|
Evaporator Coil Face Area: | 13.03 [sq ft] |
Rows/FPI : | 4/10 |
Refrigerant Control: | TX Valve |
|
|
Condenser Coil Face Area: | 15.82 [sq ft] |
Rows/FPI: | 4/14 |
|
|
Compressor No./Type: | 2/Scroll |
Refrigerant Circuits: | 2 / Independent |
|
|
Refrigerant: | R22 |
Charge: | 13.83 Lbs./ circuit |
|
|
Filters - Qty./Size: | 2/14x20x2 & 4/14x25x2 |
|
|
Operating Weight [lbs.]: | 1465 |
Shipping Weight [lbs.]: | 1525 |
|
|
Condensate Connection: | 3 / 4 NPT |
|
|
*Cooling performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F wet bulb and CFM listed. Gross capacity does not include the effect of fan motor heat.
**Rated in accordance with ARI Standard
EVAPORATOR FAN PERFORMANCE
MODEL | SUPPLY |
|
|
|
|
|
| EXTERNAL STATIC PRESSURE - Inches W.C. |
|
|
|
|
|
| |||||||
0.2 | 0.4 | 0.6 | 0.8 | 1.0 | 1.2 | 1.4 | 1.6 | 1.8 | 2.0 | ||||||||||||
# | CFM | RPM | BHP | RPM | BHP | RPM | BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM | BHP | RPM | BHP | RPM | BHP | ||||
| 5400 | 765 | 1.93 | 818 | 2.16 | 870 | 2.41 | 920 | 2.70 | 970 | 2.90 | 1010 | 3.20 | 1050 | 3.46 | 1100 | 3.70 | 1145 | 3.90 | 1180 | 4.30 |
DPV180 | 6000 | 824 | 2.52 | 873 | 2.77 | 920 | 3.03 | 967 | 3.30 | 1010 | 3.58 | 1052 | 3.90 | 1097 | 4.24 | 1137 | 4.59 | 1178 | 4.95 | 1220 | 5.33 |
| 6600 | 903 | 3.33 | 947 | 3.60 | 991 | 3.89 | 1034 | 4.19 | 1076 | 4.49 | 1110 | 4.80 | 1150 | 5.10 | - | - | - | - | - | - |
NOTE:
1.At high evaporator air flows, and wet bulb conditions, condensate
2.Values include pressure drop from wet coil and clean filters.
3.Shaded areas indicate oversize motors.
CONDENSER FAN PERFORMANCE
|
|
|
| EXTERNAL STATIC | PRESSURE - Inches W.C. |
|
|
|
| ||||||||
MODEL | OUTDOOR | 0.2 |
| 0.4 |
| 0.6 |
| 0.8 |
| 1.0 | 1.2 | ||||||
# | CFM | RPM | BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM | BHP | ||||||||
DPV180 | 7500 | 725 | 2.35 | 780 |
| 2.67 | 834 |
| 3.01 | 886 |
| 3.37 | 936 |
| 3.76 | 983 | 4.18 |
ELECTRICAL DATA – STANDARD MOTOR
MODEL | VOLTAGE |
| COMPRESSOR | EVAPORATOR FAN | CONDENSER FAN | MIN. CCT. | MAX FUSE / | ||||
# |
| QTY |
| RLA | LRA | HP | FLA | HP | FLA | AMPACITY | CCT. BKR. AMP |
DPV180 | 2 | @ | 28.6 | 196.0 | 5.00 | 13.7 | 5.00 | 13.7 | 91.75 | 110 | |
DPV180 | 460/3/60 | 2 | @ | 14.2 | 100.0 | 5.00 | 6.6 | 5.00 | 6.6 | 45.15 | 50 |
DPV180 | 575/3/60 | 2 | @ | 9.7 | 90.0 | 5.00 | 5.3 | 5.00 | 5.3 | 32.43 | 40 |
Johnson Controls maintains a continuous product improvement policy, therefore specifications are subject to change without notice.
DESCRIPTION:
DPV180 VERTICAL UNIT AIR-COOLED SELF-CONTAINED
Form YK145.12-PA7 (308)
DATE:
March 2008
Page 14