1 of 4
PROJECT:
TAG:
Gross Cooling Capacity [Btuh]: | 244,000* |
Design CFM: | 8,000 |
Energy Efficiency Ratio: | 10.10 EER** |
Net Cooling Capacity [Btuh]: | 236,000** |
Net Cooling CFM: | 6,800 |
|
|
Evaporator Fan No./Type: | 2/CENTRIFUGAL |
Diameter x Width [in]: | 15x15 |
Drive: | Adjustable Belt |
Motor HP : | 5.0 / 7.5 |
[Standard/Oversized] |
|
|
|
Condenser Fan No./Type: | 2/CENTRIFUGAL |
Diameter x Width [in]: | 18x13 |
Drive: | Adjustable Belt |
Motor HP : | 7.5 |
[Standard] |
|
|
|
Evaporator Coil Face Area: | 19.00 [sq ft] |
Rows/FPI : | 4/10 |
Refrigerant Control: | TX Valve |
|
|
Condenser Coil Face Area: | 20.55 [sq ft] |
Rows/FPI: | 4/14 |
|
|
Compressor No./Type: | 2/Scroll |
Refrigerant Circuits: | 2 / Independent |
|
|
Refrigerant: | R22 |
Charge: | 18.35 Lbs./ circuit |
|
|
Filters - Qty./Size: | 6/20x25x2 |
|
|
Operating Weight [lbs.]: | 1720 |
Shipping Weight [lbs.]: | 1805 |
|
|
Condensate Connection: | 3 / 4 NPT |
|
|
*Cooling performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F wet bulb and CFM listed. Gross capacity does not include the effect of fan motor heat.
**Rated in accordance with ARI Standard
EVAPORATOR FAN PERFORMANCE
MODEL | SUPPLY |
|
|
|
|
|
| EXTERNAL STATICPRESSURE - Inches W.C. |
|
|
|
|
|
| |||||||||
0.2 | 0.4 | 0.6 |
| 0.8 |
| 1.0 | 1.2 | 1.4 | 1.6 | 1.8 | 2.0 | ||||||||||||
# | CFM | RPM | BHP | RPM | BHP | RPM | BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM | BHP | RPM | BHP | RPM | BHP | ||||||
| 7200 | 657 | 1.89 | 717 | 2.19 | 774 | 2.51 | 829 |
| 2.84 | 875 |
| 3.18 | 933 | 3.53 | 972 | 3.89 | 1024 | 4.26 | 1072 | 4.63 | 1113 | 5.02 |
DPV240 | 8000 | 717 | 2.51 | 772 | 2.84 | 825 | 3.20 | 875 |
| 3.55 | 924 |
| 3.92 | 976 | 4.31 | 1022 | 4.72 | 1062 | 5.15 | 1105 | 5.60 | 1145 | 6.07 |
| 8800 | 778 | 3.27 | 830 | 3.64 | 878 | 4.01 | 925 |
| 4.40 | 970 |
| 4.79 | 1015 | 5.20 | 1067 | 5.63 | 1102 | 6.08 | 1140 | 6.54 | 1183 | 7.03 |
NOTE:
1.At high evaporator air flows, and wet bulb conditions, condensate
2.Values include pressure drop from wet coil and clean filters.
3.Shaded areas indicate oversize motors.
CONDENSER FAN PERFORMANCE
|
|
|
| EXTERNAL STATIC | PRESSURE - Inches W.C. |
|
|
| |||||
MODEL | OUTDOOR | 0.2 | 0.4 | 0.6 | 0.8 | 1.0 | 1.2 | ||||||
# | CFM | RPM | BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM | BHP | ||||
DPV240 | 10200 | 656 | 3.72 | 700 | 4.12 | 741 | 4.50 | 781 | 4.91 | 820 | 5.32 | 857 | 5.73 |
ELECTRICAL DATA – STANDARD MOTOR
MODEL | VOLTAGE |
| COMPRESSOR | EVAPORATOR FAN | CONDENSER FAN | MIN. CCT. | MAX FUSE / | ||||
# |
| QTY |
| RLA | LRA | HP | FLA | HP | FLA | AMPACITY | CCT. BKR. AMP |
DPV240 | 2 | @ | 33.6 | 225.0 | 5.00 | 13.7 | 7.50 | 22.2 | 111.50 | 125 | |
DPV240 | 460/3/60 | 2 | @ | 17.3 | 114.0 | 5.00 | 6.6 | 7.50 | 10.8 | 56.33 | 70 |
DPV240 | 575/3/60 | 2 | @ | 13.5 | 80.0 | 5.00 | 5.3 | 7.50 | 8.2 | 43.88 | 50 |
ELECTRICAL DATA – OVERSIZED MOTOR
MODEL | VOLTAGE |
| COMPRESSOR | EVAPORATOR FAN | CONDENSER FAN | MIN. CCT. | MAX FUSE / | ||||
# |
| QTY |
| RLA | LRA | HP | FLA | HP | FLA | AMPACITY | CCT. BKR. AMP |
DPV240 | 2 | @ | 33.6 | 225.0 | 7.50 | 22.2 | 7.50 | 22.2 | 120.00 | 150 | |
DPV240 | 460/3/60 | 2 | @ | 17.3 | 114.0 | 7.50 | 10.8 | 7.50 | 10.8 | 60.53 | 70 |
DPV240 | 575/3/60 | 2 | @ | 13.5 | 80.0 | 7.50 | 8.4 | 7.50 | 8.4 | 47.18 | 60 |
Johnson Controls maintains a continuous product improvement policy, therefore specifications are subject to change without notice.
DESCRIPTION:
DPV240 VERTICAL UNIT
SELF-CONTAINED AIR-COOLED
Form YK145.12-PA8 (308)
DATE:
March 2008
Page 18