1 of 4
PROJECT:
TAG:
Gross Cooling Capacity [Btuh]: | 122,000* |
Design CFM: | 4,000 |
Energy Efficiency Ratio: | 10.60 EER** |
Net Cooling Capacity [Btuh]: | 117,000** |
Net Cooling CFM: | 3,600 |
|
|
Evaporator Fan No./Type: | 1/CENTRIFUGAL |
Diameter x Width [in]: | 12x15 |
Drive: | Adjustable Belt |
Motor HP : | 2.0 / 3.0 |
[Standard/Oversized] |
|
|
|
Condenser Fan No./Type: | 2/CENTRIFUGAL |
Diameter x Width [in]: | 12x11 |
Drive: | Adjustable Belt |
Motor HP : | 3.0 |
[Standard] |
|
|
|
Evaporator Coil Face Area: | 8.67 [sq ft] |
Rows/FPI : | 4/10 |
Refrigerant Control: | TX Valve |
|
|
Condenser Coil Face Area: | 12.28 [sq ft] |
Rows/FPI: | 4/14 |
|
|
Compressor No./Type: | 2/Scroll |
Refrigerant Circuits: | 2 / Independent |
|
|
Refrigerant: | R22 |
Charge: | 9.5 Lbs./ circuit |
|
|
Filters - Qty./Size: | 4/14x25x2 |
|
|
Operating Weight [lbs.]: | 1065 |
Shipping Weight [lbs.]: | 1110 |
|
|
Condensate Connection: | 3 / 4 NPT |
|
|
*Cooling performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F wet bulb and CFM listed. Gross capacity does not include the effect of fan motor heat.
**Rated in accordance with ARI Standard
EVAPORATOR FAN PERFORMANCE
MODEL | SUPPLY |
|
|
|
|
|
| EXTERNAL STATIC PRESSURE - Inches W.C. |
|
|
|
|
|
| |||||||
0.2 | 0.4 | 0.6 | 0.8 | 1.0 | 1.2 | 1.4 | 1.6 | 1.8 | 2.0 | ||||||||||||
# | CFM | RPM | BHP | RPM | BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM | BHP | RPM | BHP | RPM | BHP | |||||
DPV120 | 3600 | 800 | 1.13 | 867 | 1.28 | 931 | 1.43 | 993 | 1.59 | 1052 | 1.74 | 1100 | 1.88 | 1158 | 2.11 | 1225 | 2.25 | 1245 | 2.50 | 1335 | 2.66 |
4000 | 876 | 1.52 | 937 | 1.68 | 996 | 1.85 | 1052 | 2.01 | 1100 | 2.23 | 1154 | 2.31 | 1200 | 2.55 | 1263 | 2.72 | 1304 | 2.93 | 1367 | 3.12 | |
| 4400 | 951 | 1.98 | 1007 | 2.16 | 1062 | 2.35 | 1120 | 2.52 | 1178 | 2.76 | 1204 | 2.92 | 1263 | 3.15 | - | - | - | - | - | - |
NOTE:
1.At high evaporator air flows, and wet bulb conditions, condensate
2.Values include pressure drop from wet coil and clean filters.
3.Shaded areas indicate oversize motors.
CONDENSER FAN PERFORMANCE
|
|
|
| EXTERNAL STATIC | PRESSURE - Inches W.C. |
|
|
| |||||
MODEL | OUTDOOR | 0.2 | 0.4 | 0.6 | 0.8 | 1.0 | 1.2 | ||||||
# | CFM | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM BHP | RPM | BHP | |
DPV120 | 5500 | 804 | 1.71 | 873 | 1.94 | 941 | 2.19 | 1008 | 2.46 | 1073 | 2.75 | 1136 | 3.06 |
ELECTRICAL DATA – STANDARD MOTOR
MODEL | VOLTAGE |
| COMPRESSOR | EVAPORATOR FAN | CONDENSER FAN | MIN. CCT. | MAX FUSE / | ||||
# |
| QTY |
| RLA | LRA | HP | FLA | HP | FLA | AMPACITY | CCT. BKR. AMP |
DPV120 | 2 | @ | 19.3 | 123.0 | 2.00 | 5.9 | 3.00 | 8.7 | 58.03 | 70 | |
DPV120 | 460/3/60 | 2 | @ | 7.5 | 49.5 | 2.00 | 2.8 | 3.00 | 4.0 | 23.68 | 30 |
DPV120 | 575/3/60 | 2 | @ | 6.4 | 40.0 | 2.00 | 2.2 | 3.00 | 3.2 | 19.80 | 25 |
ELECTRICAL DATA – OVERSIZED MOTOR
MODEL | VOLTAGE |
| COMPRESSOR | EVAPORATOR FAN | CONDENSER FAN | MIN. CCT. | MAX FUSE / | ||||
# |
| QTY |
| RLA | LRA | HP | FLA | HP | FLA | AMPACITY | CCT. BKR. AMP |
DPV120 | 2 | @ | 19.3 | 123.0 | 3.00 | 8.7 | 3.00 | 8.7 | 60.83 | 80 | |
DPV120 | 460/3/60 | 2 | @ | 7.5 | 49.5 | 3.00 | 4.0 | 3.00 | 4.0 | 24.88 | 30 |
DPV120 | 575/3/60 | 2 | @ | 6.4 | 40.0 | 3.00 | 3.2 | 3.00 | 3.2 | 20.80 | 25 |
Johnson Controls maintains a continuous product improvement policy, therefore specifications are subject to change without notice.
DESCRIPTION:
DPV120 VERTICAL UNIT AIR-COOLED SELF-CONTAINED
Form YK145.12-PA5 (308)
DATE:
March 2008