York D2NA060 Normal Maintenance, Cleaning Flue Passages and Heating Elements, Structions

Page 12

035-18265-001-A-0202

MAINTENANCE

NORMAL MAINTENANCE

WARNING: Prior to any of the following maintenance proce- dures, shut off all power to the unit, to avoid per- sonal injury.

Periodic maintenance consists of changing or cleaning filters. Under some conditions, the main burners should be cleaned.

FILTERS - Inspect once a month. Replace Disposable or clean Permanent Type as necessary. DO NOT replace Permanent Type with Disposable.

MOTORS - Indoor and outdoor fan motors, along with the com- bustion blower are permanently lubricated and require no maintenance.

OUTDOOR COIL - Dirt should not be allowed to accumulate on the outdoor coil surface or other parts in the air circuit. Cleaning should be as often as necessary to keep the coil clean. Use a brush, vacuum cleaner attachment, or other suitable means. If water is used to clean the coil, be sure that the power to the unit is shut off prior to cleaning.

CAUTION: Exercise care when cleaning the coil so that the coil fins are not damaged.

Do not permit the hot condenser air discharge to be obstructed by overhanging structures or shrubs.

BURNER - At the beginning of each heating season, make a visual check of the main burner flame. If it is not possible to ad- just for the proper flame, the burners may need cleaning.

TO CLEAN BURNERS - Remove them from the furnace as ex- plained in “Burner Instructions”. Clean burners with hot water applied along top of the burner.

COMBUSTION AIR DISCHARGE - Visually inspect discharge outlet periodically to insure soot and dirt buildup is not exces- sive. If necessary, clean to maintain adequate combustion air discharge.

The manufacture recommends that the furnace system be in- spected once a year by a qualified service person.

CLEANING FLUE PASSAGES AND HEATING ELEMENTS

With proper combustion adjustment the heating element of a gas fired furnace will seldom need cleaning. If the element should become sooted, it can be cleaned as follows:

1.Remove the burner assembly as outlined in “BURNER IN-

STRUCTIONS”.

2.Remove the screws securing the restrictor plate to the tube sheet.

3.Using a wire brush on a flexible wand, brush out the inside of each heat exchanger from the burner inlet and flue outlet ends.

4.Brush out the inside of the restrictor plate to the tube sheet.

5.If soot build-up is particularly bad, remove the vent motor and clean the wheel and housing.

6.After brushing is complete, blow all brushed areas with air or nitrogen. Vacuum as needed.

7.Replace parts in the order they were removed in steps 1 thru 3.

12

Unitary Products Group

Image 12
Contents Installation Instruction Champion SeriesTable of Contents Installation Power and Control Wiring Service AccessRoof Curb FiltersCombustion Discharge GAS PipingGAS Connection Drip LEGFlue Vent Hood Physical DataUnit Weights Electrical DataFront RearSequence of Operation START-UPManifold GAS Pressure Adjustment T L E T Proper Flame AdjustmentBurner Instructions Adjustment of Temperature Rise Checking GAS InputSecure Owners Approval Maintenance Normal MaintenanceCleaning Flue Passages and Heating Elements StructionsUsing An inclined Manometer Determine Tity can esult in extensive system damageIndoor After Readings have De-energize Rator coil may vary greatly, measuringSuperheat Charging Table for Model D1NA018 Superheat Charging Table for Model D1NA024Superheat Charging Table for Model D1NA030 Superheat Charging Table for Model D1NA036Superheat Charging Table for Model D1NA042 Superheat Charging Table for Model D1NA048Superheat Charging Table for Model D2NA060 Troubleshooting StartInset HSI Terminals YESOptionalcchconfiguratioblkcch T1L1N Typical Wiring Diagram 460-3-60 Power Supply Wiring Diagram Detail B 460 & 575-3-60 Power Supply See035-18265-001-A-0202

D1NA018, D2NA060 specifications

The York D1NA018 and D2NA060 are advanced rooftop air conditioning units that combine efficiency, reliability, and innovative technologies to provide optimal climate control for commercial buildings. These units are designed to deliver robust performance while ensuring ease of installation and maintenance.

The D1NA018 is a compact model with a nominal cooling capacity of 1.5 tons, making it an ideal choice for smaller commercial spaces or applications where space is limited. In contrast, the D2NA060 offers a higher cooling capacity of 5 tons, catering to larger areas or environments that require more substantial cooling solutions. Both units are built with high-quality materials that enhance their durability and extend their operational life.

One of the key features of both models is their energy efficiency. They utilize advanced scroll compressor technology that ensures a quieter operation while optimizing energy consumption. The units are designed to achieve high Seasonal Energy Efficiency Ratios (SEER), which makes them compliant with modern energy regulations. This not only reduces operational costs but also minimizes the environmental impact.

Additionally, the York D1NA018 and D2NA060 come equipped with enhanced airflow technologies. They feature multi-speed blowers that can adapt to varying load conditions, ensuring consistent temperature control throughout the indoor space. The airflow systems are designed to provide even distribution, enhancing comfort for occupants.

These units are also equipped with user-friendly control options. The integrated digital controls allow for precise temperature management and programming, further increasing efficiency. Building managers can easily monitor and control the units, leading to improved operational convenience.

Another standout characteristic is their ease of installation. The compact design and lightweight construction of the D1NA018 simplify rooftop installations. The D2NA060, while larger, maintains a straightforward installation process, ensuring minimal disruption to building operations.

In terms of maintenance, the York D1NA018 and D2NA060 incorporate features that facilitate routine service and upkeep. Access panels are strategically placed, allowing technicians to reach components quickly and perform necessary maintenance checks with ease.

Overall, the York D1NA018 and D2NA060 represent a blend of efficiency, innovation, and practicality, making them suitable choices for a wide range of commercial applications. Their advanced technologies provide reliable climate control while reducing energy consumption, making them a preferred option for businesses seeking sustainable solutions.