TABLE 8: RP 036 @ 1200 CFM NOMINAL AIRFLOW VERTICAL AND HORIZONTAL MODELS
EWT | GPM | WPD |
|
| Cooling |
|
|
(ºF) | (PSI) | EAT | TC | SC | KW | THR | |
| (db/wb) | (MBH) | (MBH) | (MBH) | |||
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| 75/62 | 38.8 | 29.9 | 1.78 | 44.8 |
| 5.5 | 2.9 | 80/67 | 42.9 | 29.7 | 1.85 | 49.1 |
50 |
|
| 85/72 | 47.1 | 29.4 | 1.91 | 53.6 |
|
| 75/62 | 39.2 | 30.1 | 1.65 | 44.8 | |
|
|
| |||||
|
|
|
|
|
|
|
|
| 9.0 | 7.0 | 80/67 | 43.9 | 30.1 | 1.68 | 49.6 |
|
|
|
|
|
|
|
|
|
|
| 85/72 | 48.2 | 29.8 | 1.76 | 54.1 |
|
|
| 75/62 | 36.7 | 29.0 | 2.15 | 44.0 |
| 5.5 | 2.8 | 80/67 | 40.6 | 28.9 | 2.21 | 48.1 |
60 |
|
| 85/72 | 44.5 | 28.5 | 2.29 | 52.3 |
|
| 75/62 | 37.1 | 29.2 | 2.03 | 44.0 | |
|
|
| |||||
|
|
|
|
|
|
|
|
| 9.0 | 6.8 | 80/67 | 41.5 | 29.2 | 2.09 | 48.6 |
|
|
|
|
|
|
|
|
|
|
| 85/72 | 45.6 | 28.9 | 2.14 | 52.8 |
|
|
| 75/62 | 35.1 | 28.4 | 2.30 | 42.9 |
| 5.5 | 2.6 | 80/67 | 38.4 | 28.0 | 2.38 | 46.5 |
70 |
|
| 85/72 | 42.2 | 27.7 | 2.43 | 50.4 |
|
| 75/62 | 35.5 | 28.4 | 2.19 | 42.9 | |
|
|
| |||||
|
|
|
|
|
|
|
|
| 9.0 | 6.4 | 80/67 | 39.6 | 28.5 | 2.25 | 47.2 |
|
|
|
|
|
|
|
|
|
|
| 85/72 | 43.4 | 28.1 | 2.32 | 51.3 |
|
|
| 75/62 | 32.6 | 27.3 | 2.56 | 41.3 |
| 5.5 | 2.5 | 80/67 | 35.6 | 27.0 | 2.63 | 44.5 |
85 |
|
| 85/72 | 38.6 | 26.5 | 2.81 | 48.1 |
|
| 75/62 | 33.0 | 27.3 | 2.48 | 41.4 | |
|
|
| |||||
|
|
|
|
|
|
|
|
| 9.0 | 6.1 | 80/67 | 36.1 | 27.1 | 2.59 | 44.9 |
|
|
|
|
|
|
|
|
|
|
| 85/72 | 40.0 | 27.0 | 2.67 | 49.1 |
|
|
| 75/62 | 28.9 | 25.8 | 2.92 | 38.8 |
| 5.5 | 2.4 | 80/67 | 31.4 | 25.4 | 3.04 | 41.7 |
100 |
|
| 85/72 | 35.2 | 25.4 | 3.12 | 45.8 |
|
| 75/62 | 29.3 | 25.8 | 2.85 | 39.0 | |
|
|
| |||||
|
|
|
|
|
|
|
|
| 9.0 | 5.8 | 80/67 | 32.5 | 25.8 | 2.96 | 42.5 |
|
|
|
|
|
|
|
|
|
|
| 85/72 | 36.4 | 25.8 | 3.03 | 46.7 |
EWT | GPM |
| Heating |
| |
(ºF) |
| EAT | HC | KW | H Absrp. |
| (db) | (MBH) | (MBH) | ||
|
|
| |||
|
|
|
|
|
|
|
| 60 | 31.4 | 2.20 | 23.9 |
| 5.5 | 70 | 31.0 | 2.35 | 23.0 |
50 |
| 80 | 30.7 | 2.49 | 22.2 |
| 60 | 32.8 | 2.24 | 25.2 | |
|
| ||||
|
|
|
|
|
|
| 9.0 | 70 | 32.3 | 2.39 | 24.2 |
|
|
|
|
|
|
|
| 80 | 32.0 | 2.53 | 23.3 |
|
| 60 | 36.0 | 2.33 | 28.0 |
| 5.5 | 70 | 35.4 | 2.49 | 26.9 |
60 |
| 80 | 34.9 | 2.64 | 25.9 |
| 60 | 38.1 | 2.39 | 30.0 | |
|
| ||||
|
|
|
|
|
|
| 9.0 | 70 | 37.5 | 2.56 | 28.8 |
|
|
|
|
|
|
|
| 80 | 37.0 | 2.72 | 27.8 |
|
| 60 | 41.9 | 2.50 | 33.3 |
| 5.5 | 70 | 41.1 | 2.68 | 32.0 |
70 |
| 80 | 40.6 | 2.85 | 30.8 |
| 60 | 44.4 | 2.58 | 35.6 | |
|
| ||||
|
|
|
|
|
|
| 9.0 | 70 | 43.6 | 2.76 | 34.2 |
|
|
|
|
|
|
|
| 80 | 43.0 | 2.93 | 33.0 |
|
| 60 | 46.7 | 2.65 | 37.7 |
| 5.5 | 70 | 45.9 | 2.84 | 36.2 |
80 |
| 80 | 45.2 | 3.02 | 34.9 |
| 60 | 49.3 | 2.74 | 40.0 | |
|
| ||||
|
|
|
|
|
|
| 9.0 | 70 | 48.4 | 2.93 | 38.4 |
|
|
|
|
|
|
|
| 80 | 47.6 | 3.11 | 37.0 |
NOTE: All capacity data shown is NET - includes motor power/heat at design CFM and HI fan speed. Tabulated kW values do not include allowance for external pumping power.
TC = TOTAL COOLING CAPACITY
SC = SENSIBLE COOLING CAPACITY
THR = TOTAL HEAT REJECTION
HC = TOTAL HEATING CAPACITY
WPD = WATER PRESSURE DROP
AIR FLOW CORRECTION FACTORS
AIRFLOW |
|
| HEATING |
|
|
| COOLING |
| ||
% OF |
| CFM | HC | Input | Heat | TC | SC |
| Input | THR |
Nominal |
| Power | Absrp. |
| Power | |||||
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
80 |
| 960 | 0.986 | 1.058 | 0.969 | 0.966 | 0.893 |
| 0.992 | 0.971 |
90 |
| 1080 | 0.993 | 1.029 | 0.985 | 0.983 | 0.947 |
| 0.996 | 0.986 |
|
|
|
|
|
|
|
|
|
|
|
100 |
| 1200 | 1.000 | 1.000 | 1.000 | 1.000 | 1.000 |
| 1.000 | 1.000 |
110 |
| 1320 | 1.007 | 0.977 | 1.014 | 1.011 | 1.049 |
| 1.004 | 1.011 |
115 |
| 1380 | 1.010 | 0.965 | 1.021 | 1.017 | 1.074 |
| 1.006 | 1.016 |
|
|
|
|
|
|
|
|
|
|
|
10 | Johnson Controls Unitary Products |