York 359583-YTG-B-0208 manual 100 400 000

Page 6

359583-YTG-B-0208

TABLE 4: RP 012 @400 CFM NOMINAL AIRFLOW VERTICAL AND HORIZONTAL MODELS

EWT

GPM

WPD

 

 

Cooling

 

 

(ºF)

(PSI)

EAT

TC

SC

KW

THR

 

(db/wb)

(MBH)

(MBH)

(MBH)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75/62

13.2

10.0

0.80

15.9

 

1.8

2.1

80/67

14.4

9.9

0.83

17.2

50

 

 

85/72

15.4

9.6

0.89

18.4

 

 

75/62

13.4

10.1

0.76

15.9

 

 

 

 

3.0

5.3

80/67

14.7

10.0

0.78

17.3

 

 

 

 

 

 

 

 

 

 

 

85/72

16.0

9.8

0.80

18.7

 

 

 

 

 

 

 

 

 

 

 

75/62

12.7

9.8

0.88

15.7

 

1.8

2.0

80/67

13.8

9.7

0.90

16.8

60

 

 

85/72

14.9

9.4

0.96

18.1

 

 

75/62

13.0

9.9

0.85

15.9

 

 

 

 

3.0

5.1

80/67

13.9

9.8

0.88

16.9

 

 

 

 

 

 

 

 

 

 

 

85/72

15.5

9.6

0.92

18.6

 

 

 

 

 

 

 

 

 

 

 

75/62

12.3

9.6

0.96

15.5

 

1.8

1.9

80/67

13.4

9.5

1.00

16.8

70

 

 

85/72

14.4

9.3

1.04

17.9

 

 

75/62

12.5

9.7

0.91

15.6

 

 

 

 

3.0

4.8

80/67

13.7

9.6

0.95

16.9

 

 

 

 

 

 

 

 

 

 

 

85/72

14.9

9.4

0.98

18.2

 

 

 

 

 

 

 

 

 

 

 

75/62

11.5

9.3

1.08

15.1

 

1.8

1.8

80/67

12.6

9.2

1.11

16.3

85

 

 

85/72

13.6

9.0

1.16

17.5

 

 

75/62

11.8

9.4

1.03

15.3

 

 

 

 

3.0

4.6

80/67

13.0

9.3

1.06

16.6

 

 

 

 

 

 

 

 

 

 

 

85/72

14.1

9.2

1.11

17.8

 

 

 

 

 

 

 

 

 

 

 

75/62

10.8

9.0

1.20

14.8

 

1.8

1.7

80/67

11.8

8.9

1.25

16.0

100

 

 

85/72

12.7

8.7

1.31

17.1

 

 

75/62

11.1

9.1

1.16

15.0

 

 

 

 

3.0

4.4

80/67

12.1

9.0

1.21

16.2

 

 

 

 

 

 

 

 

 

 

 

85/72

13.2

8.8

1.26

17.5

 

 

 

 

 

 

 

 

EWT(ºF)

GPM

 

Heating

 

EAT

HC

KW

H Absrp.

 

 

(db)

(MBH)

(MBH)

 

 

 

 

 

 

 

 

 

 

 

60

11.7

0.87

8.7

 

1.8

70

11.6

0.93

8.4

50

 

80

11.4

0.98

8.1

 

60

12.4

0.90

9.4

 

 

 

3.0

70

12.3

0.96

9.0

 

 

 

 

 

 

 

 

80

12.1

1.01

8.7

 

 

 

 

 

 

 

 

60

13.1

0.92

10.0

 

1.8

70

12.9

0.98

9.6

60

 

80

12.8

1.03

9.3

 

60

13.8

0.94

10.6

 

 

 

3.0

70

13.6

1.01

10.2

 

 

 

 

 

 

 

 

80

13.5

1.07

9.8

 

 

 

 

 

 

 

 

60

15.2

1.00

11.8

 

1.8

70

14.9

1.07

11.3

70

 

80

14.8

1.13

10.9

 

60

15.9

1.02

12.4

 

 

 

3.0

70

15.6

1.09

11.9

 

 

 

 

 

 

 

 

80

15.4

1.15

11.5

 

 

 

 

 

 

 

 

60

16.9

1.05

13.3

 

1.8

70

16.6

1.13

12.8

80

 

80

16.4

1.20

12.3

 

60

17.4

1.07

13.7

 

 

 

3.0

70

17.1

1.15

13.2

 

 

 

 

 

 

 

 

80

16.9

1.22

12.7

 

 

 

 

 

 

NOTE: All capacity data shown is NET - includes motor power/heat at design CFM and HI fan speed. Tabulated kW values do not include allowance for external pumping power.

TC = TOTAL COOLING CAPACITY

SC = SENSIBLE COOLING CAPACITY

THR = TOTAL HEAT REJECTION

HC = TOTAL HEATING CAPACITY

WPD = WATER PRESSURE DROP

AIR FLOW CORRECTION FACTORS

AIRFLOW

 

 

HEATING

 

 

 

COOLING

 

% OF

 

CFM

HC

Input

Heat

TC

SC

 

Input

THR

Nominal

 

Power

Absrp.

 

Power

 

 

 

 

 

 

 

80

 

320

0.986

1.058

0.969

0.966

0.893

 

0.992

0.971

 

 

 

 

 

 

 

 

 

 

 

90

 

360

0.993

1.029

0.985

0.983

0.947

 

0.996

0.986

 

 

 

 

 

 

 

 

 

 

 

100

 

400

1.000

1.000

1.000

1.000

1.000

 

1.000

1.000

110

 

440

1.007

0.977

1.014

1.011

1.049

 

1.004

1.011

 

 

 

 

 

 

 

 

 

 

 

115

 

460

1.010

0.965

1.021

1.017

1.074

 

1.006

1.016

 

 

 

 

 

 

 

 

 

 

 

6

Johnson Controls Unitary Products

Image 6
Contents Technical Guide Product Nomenclature General Data AIR Flow Correction Factors 100 300 000 100 400 000 100 600 000 100 800 000 100 1000 100 1200 000 100 1600 000 100 2000 Blower Performance Horizontal Dimensional Data Vertical Dimensional Data Johnson Controls Unitary Products York Drive Norman, OK