TABLE 7: RP 030 @ 1000 CFM NOMINAL AIRFLOW VERTICAL AND HORIZONTAL MODELS
EWT | GPM | WPD |
|
| Cooling |
|
|
(ºF) | (PSI) | EAT | TC | SC | KW | THR | |
| (db/wb) | (MBH) | (MBH) | (MBH) | |||
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| 75/62 | 32.8 | 25.0 | 1.71 | 38.6 |
| 4.5 | 3.6 | 80/67 | 36.2 | 24.8 | 1.74 | 42.1 |
50 |
|
| 85/72 | 39.5 | 24.4 | 1.77 | 45.5 |
|
| 75/62 | 33.7 | 25.4 | 1.60 | 39.1 | |
|
|
| |||||
|
|
|
|
|
|
|
|
| 7.5 | 9.0 | 80/67 | 37.1 | 25.2 | 1.62 | 42.6 |
|
|
|
|
|
|
|
|
|
|
| 85/72 | 40.5 | 24.8 | 1.64 | 46.1 |
|
|
| 75/62 | 31.2 | 24.3 | 1.92 | 37.7 |
| 4.5 | 3.5 | 80/67 | 34.5 | 24.2 | 1.94 | 41.1 |
60 |
|
| 85/72 | 37.5 | 23.8 | 1.98 | 44.2 |
|
| 75/62 | 32.0 | 24.7 | 1.82 | 38.2 | |
|
|
| |||||
|
|
|
|
|
|
|
|
| 7.5 | 8.7 | 80/67 | 35.5 | 24.6 | 1.84 | 41.8 |
|
|
|
|
|
|
|
|
|
|
| 85/72 | 38.7 | 24.2 | 1.86 | 45.0 |
|
|
| 75/62 | 29.5 | 23.6 | 2.09 | 36.6 |
| 4.5 | 3.3 | 80/67 | 32.7 | 23.5 | 2.12 | 39.9 |
70 |
|
| 85/72 | 35.7 | 23.2 | 2.17 | 43.1 |
|
| 75/62 | 30.5 | 24.0 | 1.99 | 37.3 | |
|
|
| |||||
|
|
|
|
|
|
|
|
| 7.5 | 8.2 | 80/67 | 33.9 | 23.9 | 2.02 | 40.8 |
|
|
|
|
|
|
|
|
|
|
| 85/72 | 37.0 | 23.6 | 2.05 | 44.0 |
|
|
| 75/62 | 27.0 | 22.6 | 2.31 | 34.9 |
| 4.5 | 3.1 | 80/67 | 30.0 | 22.5 | 2.37 | 38.1 |
85 |
|
| 85/72 | 32.7 | 22.1 | 2.45 | 41.0 |
|
| 75/62 | 27.8 | 22.9 | 2.24 | 35.4 | |
|
|
| |||||
|
|
|
|
|
|
|
|
| 7.5 | 7.8 | 80/67 | 31.0 | 22.9 | 2.27 | 38.7 |
|
|
|
|
|
|
|
|
|
|
| 85/72 | 33.9 | 22.5 | 2.33 | 41.8 |
|
|
| 75/62 | 24.5 | 21.5 | 2.50 | 33.0 |
| 4.5 | 3.0 | 80/67 | 27.2 | 21.4 | 2.58 | 36.0 |
100 |
|
| 85/72 | 29.6 | 21.1 | 2.70 | 38.8 |
|
| 75/62 | 25.1 | 21.8 | 2.46 | 33.5 | |
|
|
| |||||
|
|
|
|
|
|
|
|
| 7.5 | 7.5 | 80/67 | 28.2 | 21.8 | 2.51 | 36.7 |
|
|
|
|
|
|
|
|
|
|
| 85/72 | 30.8 | 21.5 | 2.60 | 39.6 |
EWT(ºF) | GPM |
| Heating |
| |
EAT | HC | KW | H Absrp. | ||
|
| (db) | (MBH) | (MBH) | |
|
|
| |||
|
| 60 | 27.0 | 1.91 | 20.5 |
| 4.5 | 70 | 26.6 | 2.04 | 19.7 |
50 |
| 80 | 26.4 | 2.16 | 19.0 |
| 60 | 28.2 | 1.95 | 21.5 | |
|
| ||||
|
|
|
|
|
|
| 7.5 | 70 | 27.8 | 2.09 | 20.7 |
|
|
|
|
|
|
|
| 80 | 27.5 | 2.22 | 20.0 |
|
| 60 | 30.9 | 2.04 | 23.9 |
| 4.5 | 70 | 30.4 | 2.18 | 23.0 |
60 |
| 80 | 30.1 | 2.31 | 22.2 |
| 60 | 32.7 | 2.09 | 25.6 | |
|
| ||||
|
|
|
|
|
|
| 7.5 | 70 | 32.2 | 2.24 | 24.6 |
|
|
|
|
|
|
|
| 80 | 31.8 | 2.38 | 23.7 |
|
| 60 | 35.7 | 2.18 | 28.2 |
| 4.5 | 70 | 35.1 | 2.34 | 27.1 |
70 |
| 80 | 34.6 | 2.49 | 26.1 |
| 60 | 37.9 | 2.19 | 30.4 | |
|
| ||||
|
|
|
|
|
|
| 7.5 | 70 | 37.2 | 2.35 | 29.2 |
|
|
|
|
|
|
|
| 80 | 36.7 | 2.50 | 28.1 |
|
| 60 | 40.2 | 2.31 | 32.3 |
| 4.5 | 70 | 39.4 | 2.48 | 31.0 |
80 |
| 80 | 38.9 | 2.64 | 29.9 |
| 60 | 42.2 | 2.38 | 34.0 | |
|
| ||||
|
|
|
|
|
|
| 7.5 | 70 | 41.4 | 2.55 | 32.7 |
|
|
|
|
|
|
|
| 80 | 40.8 | 2.71 | 31.5 |
NOTE: All capacity data shown is NET - includes motor power/heat at design CFM and HI fan speed. Tabulated kW values do not include allowance for external pumping power.
TC = TOTAL COOLING CAPACITY
SC = SENSIBLE COOLING CAPACITY
THR = TOTAL HEAT REJECTION
HC = TOTAL HEATING CAPACITY
WPD = WATER PRESSURE DROP
AIR FLOW CORRECTION FACTORS
AIRFLOW |
|
| HEATING |
|
|
| COOLING |
| ||
% OF |
| CFM | HC | Input | Heat | TC | SC |
| Input | THR |
Nominal |
| Power | Absrp. |
| Power | |||||
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
80 |
| 800 | 0.986 | 1.058 | 0.969 | 0.966 | 0.893 |
| 0.992 | 0.971 |
90 |
| 900 | 0.993 | 1.029 | 0.985 | 0.983 | 0.947 |
| 0.996 | 0.986 |
|
|
|
|
|
|
|
|
|
|
|
100 |
| 1000 | 1.000 | 1.000 | 1.000 | 1.000 | 1.000 |
| 1.000 | 1.000 |
110 |
| 1100 | 1.007 | 0.977 | 1.014 | 1.011 | 1.049 |
| 1.004 | 1.011 |
115 |
| 1150 | 1.010 | 0.965 | 1.021 | 1.017 | 1.074 |
| 1.006 | 1.016 |
|
|
|
|
|
|
|
|
|
|
|
Johnson Controls Unitary Products | 9 |