York BP 072 warranty BP072 Cooling Capacities 6 TON, 1800

Page 16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036-21630-001-B-0904

TABLE 3: BP072 COOLING CAPACITIES (6 TON)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR AMBIENT TEMPERATURE

 

 

 

 

 

 

 

 

RETURN AIR

 

 

 

85°F

 

 

 

 

 

 

 

 

95°F

 

 

 

 

 

GROSS

INPUT2

GROSS SENSIBLE CAPACITY1, MBH

GROSS

INPUT2

GROSS SENSIBLE CAPACITY1, MBH

 

 

 

 

RETURN AIR DRY BULB TEMP. °F

RETURN AIR DRY BULB TEMP. °F

 

 

CAP.1

POWER

 

 

 

 

 

 

 

 

CAP.1

POWER

 

 

 

 

 

 

 

 

 

WB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

TEMP

MBH

kW

86

83

 

80

77

74

71

68

MBH

kW

86

83

 

80

77

74

71

68

 

°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

76.1

5.26

45.5

39.7

 

33.8

28.0

22.2

-

-

72.6

5.80

43.1

38.0

 

32.9

27.7

22.6

-

-

1800

67

71.2

5.19

57.8

51.9

 

46.1

40.3

34.4

28.6

22.8

67.0

5.74

55.0

49.9

 

44.7

39.6

34.5

29.3

24.2

62

66.0

5.13

66.0

62.8

 

57.0

51.2

45.3

39.5

33.7

60.9

5.67

60.9

59.8

 

54.7

49.5

44.4

39.3

34.1

 

 

 

 

57

65.4

5.12

65.4

64.0

 

58.1

52.3

46.5

40.6

34.8

60.7

5.67

60.7

59.9

 

54.7

49.6

44.5

39.3

34.2

 

72

78.9

5.28

49.9

43.4

 

37.0

30.6

24.2

-

-

75.7

5.83

48.2

42.1

 

36.0

30.0

23.9

-

-

2100

67

73.8

5.21

63.3

56.9

 

50.4

44.0

37.6

31.2

24.8

69.8

5.77

61.2

55.1

 

49.0

43.0

36.9

30.8

24.8

62

68.3

5.15

68.3

66.8

 

62.4

56.0

49.6

43.1

36.7

63.4

5.70

63.4

62.9

 

59.9

53.9

47.8

41.7

35.7

 

 

 

 

57

67.8

5.14

67.8

67.0

 

63.6

57.2

50.8

44.4

38.0

63.2

5.70

63.2

62.8

 

60.0

53.9

47.9

41.8

35.7

 

72

81.6

5.30

54.2

47.2

 

40.2

33.2

26.2

-

-

78.7

5.86

53.2

46.2

 

39.2

32.2

25.2

-

-

2400

67

76.3

5.23

68.8

61.8

 

54.8

47.8

40.8

33.8

26.8

72.6

5.80

67.3

60.3

 

53.3

46.3

39.4

32.4

25.4

62

70.7

5.17

70.7

70.7

 

67.8

60.8

53.8

46.8

39.8

66.0

5.73

66.0

66.0

 

65.2

58.2

51.2

44.2

37.2

 

 

 

 

57

70.1

5.16

70.1

70.1

 

69.1

62.1

55.1

48.1

41.1

65.7

5.72

65.7

65.7

 

65.3

58.3

51.3

44.3

37.3

 

72

83.3

5.31

58.0

50.1

 

42.1

34.1

26.2

-

-

79.6

5.87

56.9

48.9

 

41.0

33.0

25.0

-

-

2700

67

77.9

5.24

73.3

65.3

 

57.4

49.4

41.4

33.5

25.5

73.4

5.81

70.8

63.7

 

55.8

47.8

39.8

31.9

23.9

62

72.1

5.18

72.1

72.1

 

70.7

62.7

54.7

46.8

38.8

66.7

5.74

66.7

66.7

 

66.3

58.4

50.4

42.4

34.4

 

 

 

 

57

71.6

5.17

71.6

71.6

 

71.1

63.1

55.1

47.2

39.2

66.5

5.74

66.5

66.5

 

66.3

58.3

50.3

42.3

34.4

 

72

84.9

5.32

61.9

52.9

 

44.0

35.0

26.1

-

-

80.5

5.89

60.6

51.7

 

42.8

33.8

24.9

-

-

3000

67

79.5

5.25

77.8

68.9

 

59.9

51.0

42.0

33.1

24.2

74.2

5.83

74.2

67.1

 

58.2

49.3

40.3

31.4

22.4

62

73.6

5.19

73.6

73.6

 

73.6

64.7

55.7

46.8

37.8

67.5

5.76

67.5

67.5

 

67.5

58.5

49.6

40.6

31.7

 

 

 

 

57

73.0

5.18

73.0

73.0

 

73.0

64.1

55.1

46.2

37.2

67.2

5.76

67.2

67.2

 

67.2

58.3

49.4

40.4

31.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR AMBIENT TEMPERATURE

 

 

 

 

 

 

 

 

RETURN AIR

 

 

 

105°F

 

 

 

 

 

 

 

 

115°F

 

 

 

 

 

 

INPUT2

GROSS SENSIBLE CAPACITY1, MBH

 

INPUT2

GROSS SENSIBLE CAPACITY1, MBH

 

 

 

 

 

 

GROSS

RETURN AIR DRY BULB TEMP. °F

GROSS

RETURN AIR DRY BULB TEMP. °F

 

 

CAP.1

POWER

 

 

 

 

 

 

 

 

CAP.1

POWER

 

 

 

 

 

 

 

 

 

WB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

TEMP

MBH

kW

86

83

 

80

77

74

71

68

MBH

kW

86

83

 

80

77

74

71

68

 

°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

67.5

6.47

40.8

35.7

 

30.6

25.5

20.3

-

-

62.3

7.14

38.6

33.4

 

28.3

23.2

18.0

-

-

1800

67

61.4

6.38

52.1

46.9

 

41.8

36.7

31.5

26.4

21.3

55.8

7.02

49.2

44.0

 

38.9

33.8

28.6

23.5

18.4

62

56.3

6.33

56.3

55.4

 

50.3

45.1

40.0

34.9

29.7

51.8

6.98

51.8

51.0

 

45.9

40.7

35.6

30.5

25.3

 

 

 

 

57

55.9

6.31

55.9

55.0

 

49.9

44.8

39.6

34.5

29.4

51.1

6.95

51.1

50.2

 

45.0

39.9

34.8

29.6

24.5

 

72

70.8

6.51

46.1

40.1

 

34.0

27.9

21.9

-

-

66.0

7.19

44.1

38.0

 

32.0

25.9

19.8

-

-

2100

67

64.4

6.41

58.5

52.6

 

46.5

40.4

34.4

28.3

22.2

59.1

7.06

55.7

50.0

 

43.9

37.9

31.8

25.7

19.7

62

59.1

6.36

59.1

58.7

 

55.9

49.8

43.7

37.7

31.6

54.8

7.03

54.8

54.4

 

51.8

45.7

39.7

33.6

27.5

 

 

 

 

57

58.6

6.34

58.6

58.2

 

55.4

49.4

43.3

37.3

31.2

54.0

6.99

54.0

53.6

 

50.9

44.8

38.8

32.7

26.6

 

72

74.2

6.55

51.4

44.4

 

37.4

30.4

23.4

-

-

69.6

7.23

49.6

42.6

 

35.6

28.6

21.6

-

-

2400

67

67.4

6.45

64.8

58.2

 

51.2

44.2

37.2

30.2

23.2

62.3

7.11

62.3

56.0

 

49.0

42.0

35.0

28.0

21.0

62

61.9

6.40

61.9

61.9

 

61.5

54.5

47.5

40.5

33.5

57.9

7.07

57.9

57.9

 

57.8

50.8

43.8

36.8

29.8

 

 

 

 

57

61.4

6.38

61.4

61.4

 

61.0

54.0

47.0

40.0

33.0

57.0

7.04

57.0

57.0

 

56.7

49.7

42.7

35.7

28.7

 

72

74.3

6.56

54.7

46.8

 

38.8

30.8

22.8

-

-

69.1

7.25

52.5

44.6

 

36.6

28.6

20.7

-

-

2700

67

67.6

6.47

66.3

61.0

 

53.0

45.1

37.1

29.1

21.2

61.8

7.13

61.8

58.3

 

50.3

42.3

34.4

26.4

18.4

62

62.1

6.42

62.1

62.1

 

61.9

53.9

45.9

37.9

30.0

57.4

7.09

57.4

57.4

 

57.4

49.4

41.4

33.5

25.5

 

 

 

 

57

61.5

6.40

61.5

61.5

 

61.3

53.4

45.4

37.4

29.5

56.6

7.06

56.6

56.6

 

56.4

48.5

40.5

32.5

24.6

 

72

74.5

6.58

58.0

49.1

 

40.2

31.2

22.3

-

-

68.6

7.27

55.4

46.5

 

37.6

28.6

19.7

-

-

3000

67

67.8

6.49

67.8

63.9

 

54.9

46.0

37.0

28.1

19.1

61.4

7.15

61.4

60.6

 

51.6

42.7

33.7

24.8

15.8

62

62.2

6.44

62.2

62.2

 

62.2

53.3

44.3

35.4

26.5

57.0

7.11

57.0

57.0

 

57.0

48.1

39.1

30.2

21.2

 

 

 

 

57

61.7

6.42

61.7

61.7

 

61.7

52.8

43.8

34.9

25.9

56.1

7.08

56.1

56.1

 

56.1

47.2

38.3

29.3

20.4

1.These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 X kW. Refer to the appropriate blower performance table for the KW of the supply air blower motor.

2.These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.

16

Unitary Products Group

Image 16
Contents Description Single Package Heat Pump UnitsAshrae 90.1-2001 Compliant Table of Contents 072 C00 Product NomenclatureProduct Nomenclature Johnson UNT Controller, DFS, APS, SS Drain Pan Technicoat Condenser Coil & Dirty Filter Switch Hinged Filter Door & Toolless Access Cabinet 036-21630-001-B-0904 Novar ETC-3 Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access Cabinet Features FACTORY-INSTALLED Options Unit CutawayFIELD-INSTALLED Accessories 036-21630-001-B-0904 Sound Power RATING1 Capacity RatingsESP Blower Unit CFMBP072 Cooling Capacities 6 TON 1800125F Outdoor AIR Temperature F 72% RH BP072 Heating CapacitiesID DB MBHStatic Resistances Belt Drive Blower Motor and Drive DataElectric Heater CFM Limitations FLA BrkrNone Tonnage Motor Outlet Electric Heat Correction Factors Physical DataVoltage LIMITATIONS1 Typical Power Wiring Typical Control WiringUnit Dimensions Front View Unit with Fixed Outdoor AIR/MOTORIZED Damper Rainhood Hole Opening Size DIA Used for Minimum ClearancesClearance Typical Applications Operating Weights LBS BP 6 Point Loads Weight DistributionCenter of Gravity General Guide SpecificationsDescription Indoor Evaporator FAN Assembly Manual Outdoor AIR Damper 036-21630-001-B-0904

BP 072 specifications

The York BP 072 is a prominent model within the York line of rooftop units. Renowned for its efficiency and robust performance, the BP 072 is designed to cater to the needs of commercial applications where reliable heating and cooling are paramount. With a focus on energy efficiency, this model offers optimal performance while minimizing energy consumption, making it a suitable choice for businesses aiming to reduce operational costs.

One of the standout features of the York BP 072 is its advanced scroll compressor technology. This technology not only enhances the unit's efficiency but also ensures quieter operation, thus creating a more comfortable environment for occupants. The compressor's design helps reduce vibration, which contributes to the overall longevity of the unit.

In terms of thermal performance, the BP 072 is engineered with a high-efficiency coil design that maximizes heat exchange. This design plays a crucial role in delivering superior cooling and heating capabilities throughout the year. Furthermore, the unit comes equipped with multiple stages of heating and cooling, ensuring precise temperature control and comfort, regardless of the weather outside.

The BP 072 benefits from York’s commitment to sustainability, featuring environmentally friendly refrigerants that align with modern environmental regulations. The use of these refrigerants not only provides minimal ecological impact but also contributes to energy efficiency, addressing both operational costs and environmental concerns.

Another characteristic that sets the York BP 072 apart is its user-friendly control system. The unit includes an integrated microprocessor-based control that streamlines operation and monitoring. This feature allows facility managers to easily adjust settings, enabling the unit to operate efficiently based on current demand and occupancy levels.

Ease of maintenance is another significant aspect of the BP 072. Designed with accessible components, routine upkeep is simplified, allowing technicians to perform inspections and repairs with minimal disruption to building operations. This focus on serviceability not only extends the life of the unit but also ensures continuous performance.

Overall, the York BP 072 stands out as a reliable and efficient solution for commercial heating and cooling needs. Its advanced features, energy-efficient technologies, and user-friendly characteristics make it an ideal choice for businesses looking to manage their environment effectively while minimizing costs. Whether for new construction or replacement of existing systems, the York BP 072 is a strong contender in today’s competitive market.